SAFETY INSTRUCTIONS
IMPORTANT SAFETY INSTRUCTIONS
(CONT.)
15. A green coloured terminal or a terminal marked G, GR, Ground, Grounding or the symbol shown
in Figure 14.1 of UL1563 is located inside the supply terminal box or compartment. To reduce the
risk of electric shock, this terminal must be connected to the grounding means provided in the
electric supply service panel with a continuous copper wire equivalent in size to the circuit
conductors supplying this equipment.
16. At least two lugs marked “Bonding Lugs” are provided on the external surface or on the inside
of the supply terminal box or compartment. To reduce the risk of electric shock, connect the local
common bonding grid in the area of the spa to these terminals with an insulated or bare copper
conductor not smaller than No. 6 AWG.
17. All field-installed metal components such as rails, ladders, drains, or other similar hardware within
3m of the spa shall be bonded to the equipment grounding bus with copper conductors not smaller
than No. 6 AWG.
SAVE THESE INSTRUCTIONS.
8