7
DO NOT DIVE.
105
DO NOT DIVE.
SAFETY INSTRUCTIONS
IMPORTANT SAFETY
INSTRUCTIONS (CONT.)
The unit should be subjected to periodic routine maintenance once every quarter to
make sure that the it is operating properly.
DANGER –
Risk of Electric Shock. A green colored terminal or a terminal marked G,
GR, Ground, Grounding or the symbol shown in Figure 14.1 of UL 1563 is located
inside the supply terminal box or compartment. To reduce the risk of electric shock,
this terminal must be connected to the grounding means provided in the electric
supply service panel with a continuous copper wire equivalent in size to the circuit
conductors supplying this equipment.
At least two lugs marked “Bonding Lugs” are provided on the external surface or
on the inside of the supply terminal box or compartment. To reduce the risk of
electric shock, connect the local common bonding grid in the area of the swim spa
to these terminals with an insulated or bare copper conductor not smaller than
8AWG.
All field installed metal components such as rails, ladders, drains, or other similar
hardware within 10 feet (3m) of the swim spa shall be bonded to the equipment
grounding bus with copper conductors not smaller than 8AWG.
SAVE THESE INSTRUCTIONS