37
DO NOT DIVE.
SPA TROUBLE SHOOTING GUIDE
Note: For wiring outside of U.S. and Canada, GFCI may be referred to as a RCD (residual current
device). Be sure all local electrical codes are followed.
SPA NOT HEATING
If the spas heater has failed, the majority of the time it will trip the GFCI breaker. If the spa is not
heating and has not tripped the breaker, please follow these steps:
1.
Check the topside control panel for diagnostic messages. Refer to your spa models diagnostic
message area. Follow steps to alleviate message.
2.
Check water set temperature at topside control panel.
3.
Check for dirty filters. Clean or replace if necessary.
4.
Check “heat mode” the spa is set in. Spa should be in standard/ready mode.
5.
Check the control panel for heater indicator, see controls section of manual. If the indicator is
on, the spa should be heating. With the cover closed on the spa, wait a reasonable amount of
time (approximately 1 to 2 hours) to see if the water temperature is increasing.
6.
Check to make sure that the pump is primed and all slice valves are open.
7.
Reset power to the spa at GFCI breaker.
8.
If spa is still not heating, contact your dealer for service.
GFCI IS TRIPPING
A ground fault circuit interrupter (GFCI) is required by the National Electrical Code for your
protection. The tripping of the GFCI may be caused by a component on the spa or by an electrical
problem. Electrical problems include but are not limited to, a faulty GFCI breaker, spa component,
power fluctuations, or improper wiring. If this is a new electrical service and GFCI installation, an
instantly tripping GFCI may likely be caused by improper wiring of the load neutral from the GFCI
to the spa. It may be necessary to contact an electrician if your dealer recommends doing so.
Summary of Contents for TS 240
Page 1: ...OWNER S MANUAL...
Page 2: ......
Page 20: ...18 DO NOT DIVE SITE PREPARATION GENERAL GUIDELINES...
Page 46: ...44 DO NOT DIVE Spa Controls Icon Spa Touch The Main Screen...
Page 83: ......