AM, EM, AQ, BA, ASW - IOM
page: 23/64
Ing.Ji
ř
í Jiránek
3.2.2 Distributor and Collector for AQ9Z1D
2 pieces of standard T fitting are used for distribution and collection of 2 refrigerant lines.
Vertical inlet orientation is required for refrigerant distribution (vapor and liquid mixture). If elbow
is used in front of the distributor, it must be oriented perpendicularly to the loop lines. There is
no direction limitation for collector fitting, cause vapour inside only.