6 Electric Power Connection
P
ř
i provád
ě
ní elektroinstalace vždy nahlédn
ě
te do elektrického schematu zapojení, které je
sou
č
ástí dodávky tepelného
č
erpadla.
6.1 Hlavní napájení
Heat pumps are always provided with a main switch and current zero and grounding terminal.
Connect the power supply cable to the main switch connectors and current zero and grounding
terminal. For heat pumps with outer part (AM, EM, BA), special attention must be paid to
protection against contact voltage. This can be made two ways. First one is installation of earth
leakage circuit breaker (RCD)
(Not recommended for Inverter models)
. The second
possibility is installation of additional connection using conductor with cross-section of 6 to
10mm2. Recommended protection of power supply is in the following table:
heat pump type
no aux. heater
aux. heater (kW)
3x400V
4,5
6
7,5
AQ9Z1
-
16A“B“
-
-
AQ17Z
9A“C“
16A“B“
16A“B“
20A“B“
AQ22Z
9A“C“
16A“B“
20A“B“
20A“B“
AQ22I
-
20A“B“
20A“B“
-
AQ26Z
13A“C“
20A“B“
20A“B“
20A“B“
AQ30Z
13A“C“
20A“B“
25A“B“
25A“B“
AQ30I
-
20A“B“
20A“B“
-
AQ37Z
16A“C“
25A“B“
25A“B“
25A“B“
AQ45Z
16A“C“
25A“B“
25A“B“
25A“B“
AQ45I
16A“B“
25A“B“
25A“B“
25A“B“
AQ60Z
25A“C“
32A“C“
32A“C“
32A“C“
AQ75Z
25A“C“
32A“C“
32A“C“
32A“C“
AQ90Z
32A“C“
40A“B“
40A“B“
40A“B“
1x230V
AQ9Z1D
10A“C“
32A“B“
-
-
AQ17Z1
16A“C“
40A“B“
50A“B“
AQ22Z1
20A“C“
40A“B“
50A“B“
-
AQ22I
20A“B“
40A“B“
50A“B“
-
AQ26Z1
25A“C“
50A“B“
50A“B“
-
AQ30Z1
32A“C“
50A“B“
63A“B“
-
AQ30I
25A“B“
50A“B“
63A“B“
-
AQ37Z1
32A“C“
50A“B“
63A“B“
-
heat pump type
no aux. heater
aux. heater (kW)
3x400V
2x4,5
2x6
2x7,5
AM3015Z
9A“C“
16A“B“
16A“B“
25A“B“
AM3021Z
9A“C“
16A“B“
20A“B“
25A“B“
AM3030Z
13A“C“
20A“B“
20A“B“
25A“B“
AM3038Z
16A“C“
20A“B“
25A“B“
25A“B“
AM3045Z
16A“C“
25A“B“
25A“B“
25A“B“
1x230V
AM3015Z1
16A“C“
50A“B“
63A“B“
-
AM3021Z1
20A“C“
50A“B“
63A“B“
-
AM3030Z1
32A“C“
50A“B“
63A“B“
-
AM3038Z1
32A“C“
50A“B“
63A“B“
-