background image

Troubleshooting

The power cord is not plugged in.

The motor’s thermal overload 
protection has tripped. 

POSSIBLE CAUSE

PROBLEM

The motor will 
not run or start 

Plug the power cord into a grounded outlet.

Set the power switch to the ON position.

The power switch is in the 
O (OFF) position.

The extension cord is the wrong 
wire gauge or is too long. 

A fuse has blown or a circuit 
breaker has been tripped. 

The air tank pressure exceeds 
the preset power switch limit.

The safety valve is stuck open.

Electrical connections are loose.

The motor, capacitor, or safety 
valve is defective.

The motor runs 
continuously 
when the 
power switch
is in the ON

 

position.

Check extension cord information (page 6) 
for the proper wire gauge and cord length.
Turn the air compressor off, unplug the 
power cord and wait until the motor has 
cooled down. Plug in the power cord only 
after the motor has cooled down, and wait 
for at least 5 minutes to make sure the 
thermal overload protector has recovered.  

Replace the fuse or reset the circuit 
breaker.
Verify that the fuse has the proper 
amperage.
Check for low voltage conditions.

Disconnect any other electrical appliances 
from the circuit or operate the compressor 
on a dedicated circuit.

The motor will start automatically when the
tank pressure drops below the cut-in 
pressure. 

Clean or replace the safety valve.

Contact an authorized service center.

Contact an authorized service center.

Set the power switch to the OFF 
position. If the motor does not shut off, 
unplug the air compressor. If the power
switch is defective, replace it.  

Check the air requirements of the 
accessory that is being used. If it is higher 
than the CFM (Cubic Feet per Minute )and 
pressure supplied by the compressor 
(page 7), a larger capacity air compressor 
is needed. Most accessories are rated at 
25% of actual CFM while running 
continuously.   

The prower switch does not 
shut off the motor when the air 
compressor reaches the cut-out 
pressure and the safety valve 
activates. 

The compressor’s capacity is 
not enough.

The regulator 
does not 
regulate the 
pressure.

The regulator or its internal parts 
are dirty or damaged.

Replace the regulator.

SOLUTIONS

Troubleshooting

Prolonged excessive use of air.

POSSIBLE CAUSE

PROBLEM

The pressure 
is low or 
there is not 
enough air. 

Close the tank drain.

Clean or replace the air filter element.

Check the fittings with soapy water. Tighten 
or reseal leaking fittings (apply plumber’s 
tape on threads). Do not over tighten.

SOLUTIONS

The tank drain is open.

There is a leak at one of the 
fittings.

The air intake is restricted.

There is a hole in the air hose.

There is condensation in the air 
tank caused by a high level of 
atmospheric humidity or because 
the air compressor has not been 
running long enough.  

The tank leaks.

The ventilation is inadequate.

Cooling surfaces are dirty.

There is 
moisture in 
the discharge 
air.

Decrease the amount of air used.

Check the air hose and replace it if 
necessary.

Replace the tank immediately. Do not 
attempt to repair it.

Relocate the compressor to an area with 
cool, dry and well-circulated air.

Clean all cooling surfaces on the pump 
and the motor thoroughly.

Replace worn parts and reassemble using 
new plumber's tape. 

The 
compressor 
overheats.

Check for worn parts and replace them if 
necessary.
Drain the air tank after each use. Drain the 
air tank more often in humid weather and 
use an air-line filter.

The valve is leaking.

The valve is leaking.

Page 15

Page 14

Summary of Contents for 207-1508

Page 1: ...207 1508 To Reduce The Risk Of Injury User Must Read And Understand Operator s Manual Save These Instructions For Future Reference OPERATOR S MANUAL CAUTION Toll Free Helpline 1 888 899 0146 E Mail i...

Page 2: ...Canadian Standards Association A Hz W n0 lbs min Symbol Amperes Hertz Watts Alternating current Direct current No load speed Pounds Per minute Class II construction Read the operator s Manual Wear sa...

Page 3: ...vents often cover moving parts and should also be avoided Loose clothing jewelry or long hair can be caught in moving parts 5 Avoid accidental starting Be sure switch is in OFF position before pluggin...

Page 4: ...or W These cords are rated for outdoor use and reduce the risk of electric shock Page 7 Page 6 Item Motor 120V 60Hz Universal Running Horsepower 1 5 HP Amperes 13 A Tank Size 6 0 U S gallons Air Deliv...

Page 5: ...on the valve to open manually Power Switch This switch turns the compressor on and off manually ALWAYS set this switch to the OFF position when the compressor is not being used and before unplugging A...

Page 6: ...identification label to ensure that you have purchased the intended model and that it has the required pressure rating for its intended use Operating Instructions 1 Set the power switch to the OFF pos...

Page 7: ...es will substantially reduce the air compressor and tool performance Spray a small amount of soapy water around the area of suspected leaks with a spray bottle If bubbles appear repair replace or rese...

Page 8: ...used If it is higher than the CFM Cubic Feet per Minute and pressure supplied by the compressor page 7 a larger capacity air compressor is needed Most accessories are rated at 25 of actual CFM while...

Page 9: ...0632 Q0874308001 AT3802 00 00 01 J0905070201 X3110590032 J2983410668 J0801810032 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 Quick Coupler Manifold Pressure Regulator Safe...

Page 10: ...se or misuse of the Merchandise This warranty 1 excludes expendable parts including but not limited to blades brushes belts bits light bulbs and or batteries 2 shall be void if this tool is used for c...

Page 11: ...2021 Menard Inc Eau Claire WI 54703 05 2021...

Reviews: