 3-Phase Rotation function 

Inputs  are  made  through  the  test  lead  terminals 

L1

/

L2

/

L3

.  Phase 

Rotation  directions  are  indicated  as  symbolic  movements  by  the  LCD 
segments.  Defaults  at 

.  Press 

SELECT

  button  momentarily  toggles 

between 

 and 

 modes. 

 :  Hi-sensitivity  mode,  which  detects  relatively  low  signal  outputs 

generated from motor spinning, for checking phase connections 
of Motors.  

 :  Normal-sensitivity  mode  for  identifying  phase  sequence  of 

MAINS (electricity supply). 

 
CAUTION 
Proper  Rotation  detection  relies  on  solid  signal  connection  to  all  three 
test lead terminals simultaneously. Any single disconnection will lead to 
detection  failure  and  may  produce  false  indication.  To  verify  signal 
connection and hence proper meter indication, swap any two connects 
(between  the  meter  and  the  test  points)  to  check  for  indication  of 
reverse movement 
 

 

Summary of Contents for MD79

Page 1: ...USER S MANUAL MD79 AC DC Clamp on Multimeter...

Page 2: ...pment intended to be supplied from the building wiring It applies both to plug connected equipment and to PERMANENTLY CONNECTED EQUIPMENT OVERVOLTAGE CATEGORY lll CAT III is for equipment intended to...

Page 3: ...or exposed metal before using the instrument If any defects are found replace them immediately Only use the test lead provided with the equipment or UL Listed Probe Assembly rated CAT III 600V or bett...

Page 4: ...unction 4 3 5 6 digits 6000 counts numeric LCD display 5 Additional input Jack for Phase Rotation function only 6 Input Jack for all functions EXCEPT non invasive DCA DC ACA or ACA current functions 7...

Page 5: ...han that of EF as described below are made through the test lead terminals COM Defaults at ACV Function Press SELECT button momentarily to select DCV DC ACV Line level Hz or EF NCV function in sequenc...

Page 6: ...end of the stationary clamp jaw which detects electric field surrounds energized conductors It is ideal for tracing live wiring connections locating wiring breakage and to distinguish between live or...

Page 7: ...tial current like identifying leakage current measurement Align the conductor s to the Jaws center indicators Regular or AmpTip indicators where applicable as much as possible to get the best measurin...

Page 8: ...CA DCA DC ACA Hz Input is made via the clamp jaws with best accuracy specified near the jaw tip area for small conductors low current measurements Defaults at ACA function Press SELECT button momentar...

Page 9: ...Current Funtions ACA DCA DC ACA Hz Input is made via the clamp jaws with best accuracy specified at the jaw center for regular current measurements Press SELECT button momentarily to select the subjec...

Page 10: ...cates a leaky diode defective A zero reading indicates a shorted diode defective An OL indicates an open diode defective Reverse the test leads connections reverse biased across the diode The digital...

Page 11: ...type K temperature bead probe Bkp60 with correct polarities You can also use a plug adapter Bkb32 Optional purchase with banana pins to type K socket to adapt other type K standard mini plug temperatu...

Page 12: ...with inadequate strength or fluctuation beyond 10 check the following to avoid the risk of unwanted flame relay dropout For gas or oil flames Minipeeper Low supply voltage Detector location Defective...

Page 13: ...rom motor spinning for checking phase connections of Motors Normal sensitivity mode for identifying phase sequence of MAINS electricity supply CAUTION Proper Rotation detection relies on solid signal...

Page 14: ...onnects between the meter and phases Then retest Connect the above mentioned L1 L2 and L3 of a Motor and that of the MAINS respectively should get a clockwise motor movement Using the Complementary Be...

Page 15: ...to warn for null activation if the residual is beyond a reasonable hysteresis reading of 5 to 5 DCA 80ms PEAK RMS mode Press PEAK RMS button for one second or more to toggle PEAK RMS mode to capture...

Page 16: ...age resistance input terminal has subjected to high voltage transient caused by lightning or switching surge to the system under test by accident or abnormal conditions of operation the protective imp...

Page 17: ...up to 31 C decreasing linearly to 50 relative humidity at 40 C Pollution degree 2 Storage Temperature 20 C to 60 C 80 R H with battery removed Altitude Operating below 2000m Temperature Coefficient n...

Page 18: ...otal Accuracy Specified Accuracy 25 digits Other Functions in an RF field of 3V m Total Accuracy Specified Accuracy 20 digits Power Supply 1 5V AAA Size battery X 2 Power Consumption Typical 13mA Low...

Page 19: ...acy 600 0V 1 0 5d Input Impedance 10M 100 pF nominal AC Voltage with Digital Low Pass Filter RANGE Accuracy 50Hz 60Hz 600 0V 1 0 5d Input Impedance 10M 100 pF nominal DC AC Voltage with Digital Low Pa...

Page 20: ...5d 3 5mV A Temperature RANGE Accuracy 40 0 o C 99 9 o C 1 0 0 8o C 100 o C 400 o C 1 0 1o C 40 0 o F 211 8 o F 1 0 1 5o F 212 o F 752 o F 1 0 2o F K type thermocouple range accuracy not included AmpT...

Page 21: ...ed to offset the non zero residual readings if any 3 Add 10d to the specified accuracy 4A Regular Clamp on ACA RANGE Accuracy 1 2 3 50Hz 100Hz 60 00A 4 5 600 0A 1 8 5d 100Hz 400Hz 60 00A 4 5 600 0A 2...

Page 22: ...400 0Hz Accuracy 1 5d 1 DC bias if any not more than 50 of Sine RMS Non Contact EF Detection Typical Voltage Bar Graph Indication 20V tolerance 10V 36V 55V tolerance 23V 83V 110V tolerance 59V 165V 22...

Page 23: ...H IN MATCO TOOL S OPINION HAS BEEN MISUSED ALTERED NEGLECTED OR DAMAGED BY ACCIDENT OR ABNORMAL CONDITIONS OF OPERATION OR HANDLING THIS WARRANTY IS EXCLUSIVE AND IS IN LIEU OF ALL OTHER WARRANTIES EX...

Page 24: ...1 MANUAL DEL USUARIO MD79 CA y CD Pinza amperim trica...

Page 25: ...cableado del edificio Aplica tanto para los equipos conectados con enchufe como para los EQUIPOS CONECTADOS PERMANENTEMENTE CATEGOR A DE SOBREVOLTAJE III CAT III es para los equipos dise ados para fo...

Page 26: ...aislamiento da ado o metal expuesto antes de utilizar el instrumento Si encuentra cualquier defecto reempl celas inmediatamente Solo use la sonda de prueba provista con el equipo o un conjunto de sond...

Page 27: ...ntalla LCD num rica de 6000 conteos y 3 5 6 d gitos 5 Enchufe de entrada adicional para la funci n de Rotaci n de fases solamente 6 Enchufe de entrada para todas las funciones EXCEPTO las funciones no...

Page 28: ...z de nivel de l nea y EF NCV Las entradas excepto la de EF seg n se describe a continuaci n se realizan a trav s de las terminales de las sondas de prueba COM La funci n predeterminada es ACV VCA Opri...

Page 29: ...ubicada a lo largo del extremo superior derecho de la quijada estacionaria de la pinza que detecta el campo el ctrico alrededor de conductores energizados Es ideal para rastrear conexiones de cables...

Page 30: ...i n de corriente de fuga Alinee el los conductor es con los indicadores del centro de la pinza indicadores regulares o AmpTip en donde aplique lo m s posible para obtener la mayor precisi n de medici...

Page 31: ...se realiza a trav s de las pinzas con la mejor precisi n especificada cerca del rea del extremo de la pinza para mediciones de baja corriente en conductores peque os La funci n predeterminada es ACA O...

Page 32: ...CD CD ACA y Hz La entrada se realiza a trav s de las pinzas con la mejor precisi n especificada cerca del rea central de la pinza para mediciones de corriente regular Oprima el bot n SELECT moment nea...

Page 33: ...gas defectuoso Una lectura en cero indica un diodo en corto defectuoso Una lectura OL indica un diodo abierto defectuoso Invierta las conexiones de las sondas de prueba polarizaci n inversa a trav s d...

Page 34: ...ncia Nota Aseg rese de insertar la sonda de temperatura tipo K con enchufe banana Bkp60 con las polaridades correctas Tambi n puede utilizar un adaptador de enchufe Bkb32 opcional con clavijas de tipo...

Page 35: ...por lo menos 2 A para un tipo de rectificaci n o 1 5 A para un tipo ultravioleta 8 A para los sistemas de auto verificaci n Si existe una se al de corriente de llamas con intensidad inadecuada o con...

Page 36: ...tecta salidas de se ales relativamente bajas generadas por el giro del motor para la verificaci n de las conexiones de las fases en los motores Modo de sensibilidad Normal para identificar la secuenci...

Page 37: ...mo R S y T respectivamente Si el mult metro indica un movimiento en contra de las manecillas del reloj intercambie dos conexiones entre el mult metro y el motor Luego realice de nuevo la prueba Uso de...

Page 38: ...ura MAX m xima o MIN m nima es actualizada La lectura promedio AVG es calculada a trav s del tiempo Oprima el bot n moment neamente para leer las lecturas MAX MIN y AVG en secuencia Oprima el bot n du...

Page 39: ...i n significativas de m s de 8 5 de los rangos 3 Lecturas que no indican OL en cuanto a resistencia continuidad o funci n de diodo 4 Lecturas no equivalentes a cero para la funci n de Hz 5 Indicaci n...

Page 40: ...nciones de medici n a trav s de este terminal podr a mostrar un circuito abierto Estos componentes deben ser reemplazados solamente por un t cnico calificado Limpieza y almacenamiento Limpie peri dica...

Page 41: ...d relativa de 50 a 40 C Grado de contaminaci n 2 Temperatura de almacenamiento de 20 C a 60 C 80 H R sin la bater a Altitud En funcionamiento a menos de 2000 m Coeficiente de temperatura nominal 0 15...

Page 42: ...RF de 3 V m Exactitud total Exactitud especificada 20 d gitos Fuente de energ a Bater a 1 5 V tama o AAA X 2 Consumo de energ a T pico 13 mA Bater a baja Menos de unos 2 85 V para capacitancia y Hz M...

Page 43: ...d Impedancia de entrada 10 M 100 pF nominal Voltaje CA con filtro digital de bajo paso RANGO Exactitud 50 Hz 60 Hz 600 0 V 1 0 5 d Impedancia de entrada 10 M 100 pF nominal Voltaje de CD CA con filtr...

Page 44: ...3 5 mV A Temperatura RANGO Exactitud 40 0 C 99 9 C 1 0 0 8 C 100 C 400 C 1 0 1 C 40 0 F 211 8 F 1 0 1 5 F 212 F 752 F 1 0 2 F El rango y la exactitud del termopar de tipo K no est n incluidos ACA de p...

Page 45: ...as residuales que no son cero si las hay 3 Agregar 10 d a la exactitud especificada a 4 A ACA de pinza regular RANGO Exactitud1 2 3 50 Hz 100 Hz 60 00 A 4 5 600 0 A 1 8 5 d 100 Hz 400 Hz 60 00 A 4 5 6...

Page 46: ...e 50 RMS sinusoidal Detecci n del campo el ctrico EF sin contacto Voltaje t pico Indicaci n de gr fico de barras 20 V tolerancia 10 V 36 V 55 V tolerancia 23 V 83 V 110 V tolerancia 59 V 165 V 220 V t...

Page 47: ...TCO TOOLS HAYA SIDO USADO INCORRECTAMENTE ALTERADO IGNORADO O DA ADO DEBIDO A ALG N ACCIDENTE O A CONDICIONES ANORMALES DE FUNCIONAMIENTO O MANEJO ESTA GARANT A ES EXCLUSIVA Y REEMPLAZA TODAS LAS DEM...

Reviews: