3
FRONT
SIDE VIEW
Top
Bottom
Top
Bottom
DOC: FPC-30040-CON
VER 1.0
TO RESET FAULT, PRESS MUTE BUTTON FOR 3 SECONDS
AN ACKNOWLEDGEMENT BEEP WILL SOUND WHEN FAULTS ARE CLEARED
WARNING: HIGH VOLTAGE
ALL ELECTRICAL CONNECTIONS MUST BE CARRIED OUT
BY A SUITABLY QUALIFIED ELECTRICIAN
ACCESS BY AUTHORISED PERSONNEL ONLY
TO RESET FAULT, PRESS MUTE BUTTON FOR 3 SECONDS
AN ACKNOWLEDGEMENT BEEP WILL SOUND WHEN FAULTS ARE CLEARED
WARNING: HIGH VOLTAGE
ALL ELECTRICAL CONNECTIONS MUST BE CARRIED OUT
BY A SUITABLY QUALIFIED ELECTRICIAN
ACCESS BY AUTHORISED PERSONNEL ONLY
INDICATOR LIGHTS GUIDE
WIRING CONNECTION DETAIL
FPC-30040-CON
ON STEADY
A pump fault/overload has occured
FLASHING
A prime loss fault has occured
ON STEADY
Pump is switched on to run
A high level alarm has been present for the preset time
FLASHING
A low level alarm is present
MOMENTARY PRESS
To mute audible buzzer
PRESS FOR 3 SECS
To reset alarms and faults
PRESS CONTINUOUS
To test indicator lights,
strobe and siren
MUTE/
RESET
PUMP ON
LEVEL ALARM
FAULT
INDICATOR LIGHTS GUIDE
ON STEADY
A pump fault/overload has occured
FLASHING
A prime loss fault has occured
ON STEADY
Pump is switched on to run
ON STEADY
A high level alarm has been present for the preset time
FLASHING
A low level alarm is present
MOMENTARY PRESS
To mute audible buzzer
PRESS FOR 3 SECS
To reset alarms and faults
PRESS CONTINUOUS
To test indicator lights,
strobe and siren
MUTE/
RESET
PUMP ON
LEVEL ALARM
FAULT
BMS
Volt/Free
Fault
Common
PUMP 1
PU
M
P 1
Ea
rt
h
PU
M
P 2
Ea
rt
h
PUMP 2
PUMP 2
PUMP 1
PROBES
Low/Voltage
E5 E1 E2 E3
COMMON
STOP
START
HIGH
Probe Holder
s/s Probe rodes
BRIDGE
IF NOT
REQUIRED
Thermal Switch
12Vdc
T1 T2 T1 T2
PUMP 1 PUMP 2
P1
P2
P3
P1
P2
P3
SUPPLY
415Vac
E A1 A2
N
415Vac
MAINS POWER
SUPPLY
A3
Mounting
Frame/
Wall
INSTALLATION
MOUNTING
1. Controller enclosure must be
mounted in a vertical position.
2. Ensure mounting method does
not compromise enclosure
weather proof rating.
3. Ensure access to main isolator is
not restricted.
4. Ensure cables/conduits entering
the panel have mechanical
protection and that the
penetrations are sealed and do
not compromise the weather
proof rating of the enclosure.
Note:
Controller must be earthed and all electrical connections must be carried out by a suitably qualified
Electrician. For Single Working Level Float Switch Applications, connect to “Start (Input 3)” terminals only, and NO
bridge wire is required in “Stop (Input 2)” terminals.
CONNECTION
PUMP ON
FAULT
PUMP ON
FAULT
MAIN ISOLATOR
240Vac
MAINS POWER
SUPPLY
SUPPLY
PROBES
240Vac CONNECTIONS
E
A
N
E1
COM
MO
N
E1
St
op
E2
St
art
E3
High
Low/Voltage
C
onductivit
y
Probe
Connections
COMMON
FAULT
Volt/Free
BMS
PU
M
P
1
Ea
rt
h
PUMP 1
A
N
PU
M
P
2
Ea
rt
h
PUMP 2
A
N
PUMP 2
PUMP 1