background image

www.mavili.com.tr  

21

In case of a �ire risk above the false ceiling, �ire detectors (at least 

1 per each independent 

zone

) should be mounted above the false ceiling according to the values in the Table A.

In case of a �ire risk below the raised �loor, �ire detectors (

at least 1 

per each independent 

zone) should be mounted below the �loor according to the values in the Table A.

Summary of Contents for mavigard

Page 1: ...BASED ON EN 54 14 PROJECT MANUAL generating confidence ...

Page 2: ... working hard for CUSTOMER SATISFACTION The ISO 9001 2015 Quality Management System of Mavili Elektronik A S has been audited and conformed by LPCB Loss prevention Certi ication Board ENGLAND Our Fire Detection and Alarm System products were EN 54 and CPR certi ied by LPCB and Dedal thus approving our quality by internationally accredited institutions TSE TURKEY Turkish Standards Institute entitle...

Page 3: ...amp Test Silence Alarm Alarm Silence Buzzer Reset FIRE ZONE FIRE ZONE FAULT ZONE FAULT ZONE Button Control Enable Disable Disable Disable Sounder Fault Disable 1 9 2 10 3 11 4 12 5 13 6 14 7 15 8 16 Power On General Fault Power Fault System Fault Earth Fault FIRE Silence Alarm Silence Buzzer ML 22116 Conventional Fire Alarm Control Panel Lamp Test Silence Alarm Alarm Silence Buzzer Reset FIRE ZONE...

Page 4: ...e Buzzer ML 22116 Conventional Fire Alarm Control Panel Lamp Test Silence Alarm Alarm Silence Buzzer Reset FIRE ZONE FIRE ZONE FAULT ZONE FAULT ZONE Button Control Enable Disable Disable Disable Sounder Fault Disable 1 9 2 10 3 11 4 12 5 13 6 14 7 15 8 16 Power On General Fault Power Fault System Fault Earth Fault FIRE Silence Alarm Silence Buzzer ML 22116 Conventional Fire Alarm Control Panel Lam...

Page 5: ...circuit in the system www mavili com tr 05 In addressable systems the detection circuit should be designed so that no more than 20 addressable devices will be disconnected in case of short or open circuit 1600m 1600m 1600m 1600m 1600m Short circuit isolator Short circuit isolator Short circuit isolator Short circuit isolator Short circuit isolator ...

Page 6: ...eiling height NC Not applicable in given height range SA Used only for special applications Limits of operation radius and ceiling height for ire detectors www mavili com tr 06 h 0 1xH h 7 5m 7 5m H Transmitter Receiver h 7 5m 7 5m 100m TABLE A Beam type smoke detectors are composed of 1 receiver and 1 emitter Receiver and emitter should see each other in max 100m distance Receiver and emitter hor...

Page 7: ...us every detector covers a square of 10 6m x 10 6m equaling to 112m 7 5m Smoke detector 5 3m 10 6m 10 6m x 10 6m 112m A heat detector covers a 5 m radius circle area To avoid blind points among coverage areas detectors coverage areas should be overlapping as shown in the igure above Thus every detector covers a square of 7 1m x 7 1m equaling to 50m Heat detector 3 55m 7 1m 7 1m x 7 1m 50m 5m ...

Page 8: ...eed to overlap the coverage area of the detectors If corridors have more than 2 m width smoke detectors are mounted in 10 m gaps according to the Table A If corridors have less than 2 m width heat detectors can be mounted with max 10 m gap There is no need to overlap the coverage area of the detectors If corridors have more than 2 m width heat detectors are mounted with 7 m gaps according the Tabl...

Page 9: ...t be deeply mounted all the way into the ceiling and should be in the range of 5 of the ceiling height to provide healthy operation of the thermistor Due to cold air layer present just under the ceiling smoke detectors should not be deeply mounted all the way into the ceiling and should be in the range of 5 of the ceiling height to provide healthy operation of the optical chamber ...

Page 10: ...d in the range of 5 of upper part of the room height Detectors should be mounted 500mm away from walls or partitions If the top edge of walls partitions racks etc are less than 300mm from ceiling they are accepted as walls In every vertical downward and horizontal direction from a detector 500mm gaps should be provided ...

Page 11: ...n ceiling height H ceiling should be treated as lat and radius values in Table A should be applied If the beam height h is 5 more than ceiling height H then the conditions in the igure should be applied Detectors should not be mounted adjacent to an air inlet if it is closer than 1 m or if there is an air low in the medium more than 1 m s 1m 1m Air conditioner Ventilation Beam Beam Beam Beam ...

Page 12: ...alues of the Table A Radius values can be modi ied up to 25 of the actual values Flat ceiling Inclined ceiling h H 0 05 h H 0 05 h h H H TCV V H h Heat detector V 6m x H h Photo electric smoke detector V 12m x H h THH V Volume m H Room height m h Cell height m TCV Total cell volume m If the ceiling is composed of a group of cells a point type detector within the limits of radius in the Table A can...

Page 13: ...ww mavili com tr 13 Main stories of each stairs landing 1 detector should be placed Detector should be mounted inside area of circle enclosing elevator doors which has 1 5 m radius ELEVATOR ELEVATOR 1 5m ...

Page 14: ... picture formats Determined areas can be monitored graphical and it provides to exchange between maps in case of ire and fault events Remote commands can be sent in situations that require intervention Animations device types and event voices can be changed by users In case of ire and fault events e mail and or sms report can be sent to the authorized people at determined periods or instantly The ...

Page 15: ...etermination Arhitectural site plans of the building are de ined to the Supervisor graphic software program as maps and all the ire alarm system devices are igured on these maps Can be integrated to all kinds of CCTV systems all brands and models with remote monitoring software In determined areas present CCTV cameras can be monitored manually or automatically through automation ability With ONVIF...

Page 16: ...OFF information Urgent security announcement system information Emergency lighting system information Gas stop system Earthquake early warning system Alarm system Extinguishing system ML 1248 NP Fire alarm control panel GCU panel ML 1632 X Supervisor graphic monitoring and control software intagrated with environmental systems and managing Modbus Bacnet Server ML 1140 SCI Multisensor detector shor...

Page 17: ...e detector ML 2130 Conventional rate of rise heat detector ML 2140 Conventional multisensor detector ML 1430 Intelligent addressable system sounder beacon ML 1355 8 inputs 8 outputs smoke damper control panel with toggle switch card ML 1130 SCI Heat detector short circuit isolator ML 1101 Loop powered base sounder Super low air duct sampling unit AGD 1224M VIP Methane natural gas detector ML 1371 ...

Page 18: ...ventilation f Lift Control g Security Doors Control and Monitoring devices should be possible to relate easily and without any dif iculties with location of detector or manual callpoint RS 232 RS 485 GPRS TCP IP Intelligent Addressable System 16 way I O Panel 8 Input 8 Output Graphical Monitoring and Control Software Mimic Panel Intelligent Addressable System Smoke Damper Control Panel c w 16 way ...

Page 19: ...onger distance With UART connection cable for short distance access with TCP IP via internet for long distance TCP IP can be connected to Supervisor Superviewer Android software enables monitoring and control of ire alarm system without the user s need to be at the computer Superviewer Android 1 1 n n 1 n Superviewer Graph Supervisor Graphical Monitoring and Control Software ...

Page 20: ... ighter s telephone handset in the socket and without the need of dialing any number automatically calls the security center by hot line feature Fire ighter s Telephones Fire ighter s Telephone Control Unit 1 2 3 32 Detectors should be mounted two times far away from the light itting height 200mm 100mm Light Fitting ...

Page 21: ...t least 1 per each independent zone should be mounted above the false ceiling according to the values in the Table A In case of a ire risk below the raised loor ire detectors at least 1 per each independent zone should be mounted below the loor according to the values in the Table A ...

Page 22: ... Manual call points should be mounted at walking distance up to 30 m MCP are also placed near the escape routes In case of searching ire source in the zone 60 m walking distance never be exceeded www mavili com tr 22 ...

Page 23: ...ints should be mounted on 1 4 m 0 2 height from the loor Audible and or visual warning devices and remote indicators should be mounted at 2 1 m height from loor and cables should be properly protected www mavili com tr 23 2 1m ...

Page 24: ... present for longer than 30 sec Fire alarm sound level should not exceed 120 dB A for places where people are present Minimum alarm sound levels can be heard from the all needed places Alarm devices should be enough quantities in order to provide suggested alarm sound level To wake sleeping people up ire alarm sound level should be at least 75 dB A at the edge of the bed www mavili com tr 24 ...

Page 25: ... Loop Line 64 Programmable Alarm Alert Outputs Announce System Sound Output 8 16 32 Announce Input 4 8 Maxlogic ML 125XX Series Intelligent Addressable Fire Alarm Control Panel 75dB A One or more microphones should be de ined as a ire microphone if ire status message is needed to provide by a person Fire microphones access should be limited with only authorised people ...

Page 26: ...OR www mavili com tr 26 Power On General Fault Power Fault System Fault Earth Fault FIRE Silence Alarm Silence Buzzer ML 22116 Conventional Fire Alarm Control Panel Lamp Test Silence Alarm Alarm Silence Buzzer Reset FIRE ZONE FIRE ZONE FAULT ZONE FAULT ZONE Button Control Enable Disable Disable Disable Sounder Fault Disable 1 9 2 10 3 11 4 12 5 13 6 14 7 15 8 16 EOL End of line resistor 230V 50Hz ...

Page 27: ...s detector CO LPG Methane 5 3m 10 6m 10 6m x 10 6m 112m A gas detector has detection coverage of 7 5 m radius circle To prevent any blind points among the coverage areas they should be overlapping as shown in the igure above Thus every detector covers a square of 10 6m x 10 6 m equaling to 112 m2 area www mavili com tr 27 ...

Page 28: ...d be mounted 150 cm above loor and 150 cm away from the gas source Highly poisonous gas carbon monoxide occurs on incomplete combustion It is dif icult to detect because it is colorless and odorless It blocks oxygen in blood cells and when breathed in high concentrations may cause fatal poisoning 150cm 150cm Conventional Carbon monoxide Gas Detector www mavili com tr 28 ...

Page 29: ...ge Therefore an LPG detector must be mounted 15 25 cm above loor and within 1 2 m horizontally within the range of possible gas leakage Methane natural gas is an explosive hydrocarbon gas It is lighter than air and rises to ceiling in case of leakage Therefore a natural gas detector must be mounted 5 15 cm below ceiling and 150 cm horizontally within the range of possible gas leakage www mavili co...

Page 30: ...g in addressable system ZONE ZONE ZONE ZONE CONVENTIONAL SYSTEM Connect end of line resistor to the last device on the zone 1 3 4 5 2 1 3 4 5 2 INTELLIGENT ADDRESSABLE SYSTEM Ground connection should be made LOOP LOOP LOOP LOOP Please contact for short circuit isolated detector base connection diagram ...

Page 31: ... ML 2710 The connection diagram of addressable manual call point ML 1710 CONVENTIONAL SYSTEM ZONE ZONE ZONE ZONE 6K8 end of line resistor Connect end of line resistor if the MCP is the last device on the zone 1 2 3 4 1 2 3 4 LOOP LOOP LOOP LOOP LOOP LOOP 1 Loop 2 Loop 3 Loop 4 Loop 1 Loop 2 Loop 3 Loop 4 Loop ...

Page 32: ...en refer this presentation These information contains EN 54 14 2004 standarts manufacturing irm recommendations and product information These informations are suggestions and Mavili Elektronik Tic ve San A S do not responsible for these informations recommandations and printer errors 2019 V0 www mavili com tr en www city groupco com info city groupco com ...

Reviews: