The positions provided for the installation of vibration dampers for each type of machine are shown in the pictures below.
P1
P2
P3
P4
329
309
3.2
TECHNICAL SERVICE AREAS
All models in the series are designed and constructed for outdoor installation.
It is good practice to create a support slab of adequate size for the unit. The units transmit a low level of vibration to the ground: it is nevertheless
advisable to place anti-vibration mounts between the base frame and the support surface.
SUSPENDED INSTALLATION IS PROHIBITED
The support surface must have a sufficient capacity to support the weight of the unit, which can be seen on the technical
label affixed to the machine and in the specific chapter of this manual. The support surface must not be inclined to ensure
correct operation of the unit and to prevent it from tipping over. The installation surface of the unit must not be smooth, to
avoid the deposit of water/ice, potential sources of danger.
The installation site of the unit must be free from foliage, dust, etc., which could block or cover the heat exchange coils.
Installation should be avoided in areas subject to stagnant or falling water, for example from gutters.
Also avoid locations subject to snow accumulation (such as corners of buildings with sloping roofs). When installing in areas
subject to snowfall, mount the unit on a base 20 to 30 cm above the ground to prevent snow from accumulating around the
unit.
It is recommended to ensure sufficient air exchange to dilute the R32 gas in case of accidental leakage, thus avoiding the
formation of explosive atmospheres. For this reason, a minimum distance of 1 metre must be maintained from openings or
wells, where the gas could accumulate.
Do not install the unit under any type of cover,such as roofs, canopies, install the unit under cover of anything type as
roofs,shelters and similar.
It is very important to avoid recirculation phenomena between suction and delivery, otherwise the performance of the unit will deteriorate or
even interrupt normal operation.
In this respect it is absolutely necessary to guarantee the minimum service spaces indicated below.