i-32V5H MIDI
Chiller and Inverter Air/Water heat pumps with axial fan
14
A1
A
A2
C
B2
B
B1
MODEL
A1
A2
B1
B2
i-32V5H Midi 0121,
0126
mm
1500
400
400
700
i-32V5H Midi 0128,
0132
mm
1500
400
400
700
Obstruction or covering of ventilation openings must be avoided.
For installations in locations with strong winds refer to the area classification according to the Beaufort scale. If the value is
≥ 7 (strong wind, average wind speed = 13.9-17.1 m/s) it is strictly necessary to keep the fan powered at all times, in order to
prevent its involuntary rotation.
In the case of side-by-side units, the minimum distance Lmin between them is 700 mm.
Lmin
Covering with canopies or positioning near plants or walls should be avoided in order to
prevent air circulation.