PARAMETERS
www.maxcessintl.com
DLCA NET-S1
MI 850A374 1 A
Page 33 of 67
7.2.1
Alarm operation with hysteresis
Alarm activation type 0
Alarm turns on when tension is greater than High value.
Alarm turns off when tension is less than
(HighValue – (HysteresisPercent * Maximum Tension))
Alarm activation type 1
Alarm turns on when tension is less than Low value.
Alarm turns off when tension is greater than
(Lo (HysteresisPercent * MaximumTension))
Alarm activation type 2
Alarm turns on when tension is greater than High value or less
than Low value.
Alarm turns off when tension is less than
(HighValue - (HysteresisPercent * MaximumTension))
and when tension is greater than
(Lo (HysteresisPercent * MaximumTension))
Alarm activation type 3
Alarm output is the complement of alarm activation type 2.