Installation & Operation
Electrical Connection:
1.
Use the M5 Socket Tool to loosen the three M5 Socket head cap screws with spring washers of Tank Cover with torque
value
5 N-m
.
2.
The thread of entry hole of Tank is 3/4” NPT. Attach the Tank to suitable conduit.
3.
Insert the wire from outside through the conduit and the entry hole of Tank, and then connect to Terminal Block.
4.
Introduce the wires of branch circuit as following:
Black-wire connects to Line
White-wire connects to Neutral
Green-wire connects to Ground
1.
Re-attach the Tank Cover and tighten it using the three M5 socket head screws with spring washers with a
torque value
5 N-m
.
2.
Check the tightness of the conduit and Tank Cover.
General Wiring Diagram
CAUTION:
Turn off electrical power at fuse
or circuit breaker box before wiring fixture to
the power supply.
Connecting panels to AC source supply:
All units must be individually connected to
the AC supply.
Black = Line
White = Neutral
Green = Ground