Installation and operation instructions for 

INDITHERM

®

 

burners

Application requirements

Supporting burner air and gas piping

The INDITHERM

®

burner shall not be used as support for the piping to the burner. Gas and air piping shall be supported in such a 

way that no additional loads will be created on the burner.

Burner mounting flange loads

Check burner weight and reinforce burner mounting flange or combustion chamber/furnace back wall if necessary to support the 
complete burner weight.

Installation instructions

Storage of INDITHERM

®

 

burners

INDITHERM

®

burners shall be stored dry (inside). Burner blocks have been cured carefully before shipment and shall be kept dry.

Wetting of the blocks could result in premature failures.

Handling of INDITHERM

®

 

burners

INDITHERM

®

burners are shipped as complete units. Handle burners with care, using proper equipment during unpacking, 

transport, lifting and installation. Any impact on the burner could result in damage. To prevent damage in transit, accessories such 
as flame rods, control valves, UV-scanners, may be packed separately and shipped loose.

Orientation of INDITHERM

®

 burners

INDITHERM

®  

burners can be mounted and fired in any direction. However we advise to avoid orientations which can permit flame 

supervision ports to collect debris and/or moisture. Also check limitations on orientation of other components mounted on the 
burner head.

Burner mounting

Bolt the burner to the installation’s burner mounting flange. Use proper gaskets between burner and burner mounting flange 
(option available).Tighten the flange bolting with correct torque. Retighten all bolts after first firing and regularly after 
commissioning.

Summary of Contents for INDITHERM 100

Page 1: ...be available at burner inlet throughout the entire capacity range 8 Differential pressure to be measured between burner test connection and combustion chamber 9 Flame lengths are derived from measured...

Page 2: ...o alter specifications and data without prior notice 2008 Copyright Maxon Corporation All rights reserved 1 2 3 7 E m 7 08 Materials of construction 1 Housing Cast iron 2 Standard sleeve AISI 310 1 48...

Page 3: ...ilable in ANSI and ISO version Each version will have the main gas inlet connection following either NPT or ISO standards All burners include an adjustable orifice needle valve for pilot flame fine tu...

Page 4: ...ry block for installation in applications where high temperatures can be expected In following cases the use of high temperature version discharge sleeve is required Dimension A is larger than 50mm In...

Page 5: ...und the entire discharge sleeve should be present at all times Piloting and ignition INDITHERM burners have an internal pilot burner Piloting is accomplished by internally bypassing the built in gas b...

Page 6: ...the burner flame Consult MAXON for proper combustion chamber lay out Gas pipe train design The INDITHERM burner is very sensitive to variations in gas pressures at burner gas inlet The burner gas inl...

Page 7: ...e standard 8 Flame supervision port 9 Spark ignitor Dimensions in mm unless stated otherwise burner size gas inlet 1 A B C D E F G H I J K L M N P S Weight kg 100 1 365 225 200 160 111 442 93 390 431...

Page 8: ...8 Flame supervision port 9 Spark ignitor Dimensions in mm unless stated otherwise burner size gas inlet 1 A B C D E F G H I J K L M N P S Weight kg 100 1 365 232 200 257 111 442 100 397 438 224 289 35...

Page 9: ...fice is standard included with the burner and is factory mounted onto the burner pilot gas port In case a burner has been ordered for direct ignition this adjustable orifice is omitted Two available v...

Page 10: ...gnitor can be mounted directly onto the burner spark ignitor connection port To be used on all burner sizes See table below for mounting position C depending on burner size Filter Elements FLT INDI Re...

Page 11: ...nting plate of the burner and the duct wall Optionally available in 2 different types GSK INDI STD to be used in combination with standard discharge sleeves square GSK INDI HT to be used in combinatio...

Page 12: ...have been cured carefully before shipment and shall be kept dry Wetting of the blocks could result in premature failures Handling of INDITHERM burners INDITHERM burners are shipped as complete units...

Page 13: ...t to alter specifications and data without prior notice 2008 Copyright Maxon Corporation All rights reserved 1 2 3 18 E m 7 08 INDITHERM with standard sleeve INDITHERM with block with seal and support...

Page 14: ...reserved 1 2 3 19 E m 7 08 Burner mounting flange Refer to below figure to design a correct burner mounting flange on the installation Mounting flange for INDITHERM burners with standard sleeve Dimen...

Page 15: ...ice 2008 Copyright Maxon Corporation All rights reserved 1 2 3 20 E m 7 08 Mounting flange for INDITHERM burners with high temperature block sleeve Dimensions in mm unless stated otherwise Burner size...

Page 16: ...art up During and after start up check the integrity of the system Check all bolted connections after first firing first time on tempera ture and retighten if necessary Purge For safety reasons it is...

Page 17: ...ded preventative maintenance routine Inspect burner internal parts for wear and oxidation paying special attention to the refractory of the burner block when applicable Inspect associated control inst...

Reviews: