d. The “RATE” parameter is for setting how many percentage of SV in Slaver unit according with master unit. For
example, if the master SV is “1000” then we set “RATE” to “90” in slaver, the SV of slaver will be “900”.
e. One set of alarm can be used for “RATE” only.
6.Ramp and Soak function:
It doesn’t need installing hardware but has to modify software as following steps.
a. Set “MODE. 4
th
& 3
rd
digit” to “10” in level4.
b. For ramp function , it needs setting one among “ALD1/ALD2/ALD3” to “9” then one among “AL1/AL2/AL3” will
convert to “ramp” function. Setting unit for “RAMP” is “xx.xx
℃
/MIN.
”, and the PV will raise according to setting
volume until it finishes.
c. For soak function, it needs setting “MODE. 1
st
digit” to “0” for H/M or “1” for M/S, and one among “ALD1/ALD2
/ALD3” must be set to “19”, then one among “AL1/AL2/AL3” will convert to “soak” function and a time can be set
among “AL1/AL2/AL3”. When the PV reach the SV, it starts time counting, in the meantime one among “AL1/AL2
/AL3” and time will display alternately. When the time reach setting volume, the alarm perform and the control
output stop.
d. One set of alarm can be used for ramp and one set of alarm can be used for soak only.
7.Motor valve control function:
a. It needs installing hardware. (contact the distributor).
b. Set “MODE. 1
st
digit” to “1” in level4 to open second input.
c. Set “OUTY. 4
th
& 3
rd
digit” to “01” in level4 to open motor valve control function.
d. Set “CYT1” to open/close cycle time of motor valve in level2 and “RUCY” to time from open to close of motor valve
in level3.
e. The LED bar on the panel will display the position of motor valve.
f . Second input is for feedback use, it has 4~20mA,0~10mA,0~10VDC,2~10VDC,0~5VDC,1~5VDC or potentiometer.
8.SCR control output (resistance load only):
a. It needs installing hardware (contact the distributor).
b. Set “TIM2. 4
th
and 3
rd
digit” to “01” in level4 to open PWM output function.
c. Set “OUTY. 4
th
and 3
rd
digit” to “10” in level4 to open single phase function or “11” to open three phase function.
9.Analogue output function:
a. It needs modifying hardware, there are 4~20mA, 0~20mA, 0~5VDC, 0~10VDC, 1~5VDC, 2~10VDC. (contact
the distributor).
b. Set “CLO1” to lowest limit in level3. For example, if lowest output is 4mA, then set it to “400”.
c. Set “CHO1” to highest limit in level3. For example, if highest output is 20mA, then set it to “2000”.
d. Set “TIM2. 4
th
and 3
rd
digit” to “01” in level4 to open PWM function. (Relay & SSR Output set “00”)
e. Set “OUTY. 4
th
and 3
rd
digit” to “00” in level4.
10.Analogue input (Input 1 only):
a. It needs modifying hardware, there are 0~10mA,4~20mA,0~1VDC,0~5VDC,0~10VDC (contact the distributor).
b. Set “INP 1” to “AN1~4” in level3, and set “LSPL” to lowest range, “USPL” to highest range in level3.
c. Set “LCK” to “0111” in level 2.
d. Push key and key for 4 sec. until “INPL” is displayed on upper window.
e. Send input signal for lowest range until display is stable, then push key to enter.
SET
SET
P.9