background image

PV

SV

Repeat same steps 
as above to display the 
parameters listed at right.

Operating display

Level1 (User level)

press the            key 
for 4 seconds to level 2

SET

Level2 (PID level)

Press the           key

27.5

27.5

PV

SV

Operating display

Name

Description

Ex-

factory

OUTL

Output

percentage

Range of setting:0~100%

Skip

AT

Auto tuning

“RUN/NO”

to be used when setting PID

NO

AL1/RAMP/RATE

AL2/RAMP/RATE

AL3/RAMP/RATE

Alarm setting range: 0-100%F.S.

But if select ramp function, it will display ”rAmP”
setting range from 00.00 to 99.99

/min If 

select soak function, it will display “AL1” setting 
range from 00.00 to 99.99 min/sec or hour/min. 
If select slaver function, it will display “rAtE”
setting range from 0 to 9999. If select program 
segment ending alarm function, it will display 
“AL1”, setting range from 1-8 or 1-16

(AL2 and AL3 are the same as above)

0

Name

Description

Ex-

factory

P1

Main Control 

Proportional Band

Range of setting:0-100% 

ON/OFF at P=0

30

I1

Main Control 

Integral Time

Range of setting:0-3600 Sec 

Integral off at I=0

240

D1

Main Control 

Derivative Time

Range of setting:0-3600 Sec

Derivative off at D=0

60

DB1

Main Control 

Dead-band

Dead-band of main control

Range of setting:-10-+10

0

ATVL

Main Control 

Auto tuning off-set

Range of setting:0-100% F.S.

0

CYT1

Main Control 

Output cycle time

When output is SSR, it is set at 3, 4-20 mA is set at 1 but output 
is relay usually it is set at 20. Range of setting:0-100 Sec

20

HYS1

Main Control 

Hystersis

For ON/OFF control only 

Range of setting :0.4-100

0.4

P2

Sub Control 

Proportional Band

Range of setting:0-100% 

ON/OFF at P=0

30

I2

Sub Control 

Integral Time

Range of setting:0-3600 Sec 

Integral off at I=0

240

D2

Sub Control

Derivative Time

Range of setting:0-3600 Sec

Derivative off at D=0

60

CYT2

Sub Control

Output cycle time

When output is SSR, it is set at 3, 4-20 mA is set at 1 but output 
is relay usually it is set at 20. Range of setting:0-100 Sec

20

HYS2

Sub Control

Hystersis

For ON/OFF control only 

Range of setting :0.4-100

0.4

RST1

Reset1

Adjust offset of output1 when I1 set at “0”

0

RST2

Reset2

Adjust offset of output2 when I2 set at “0”

0

AR

Anti- Integral

Setting range from 0-100 to limit integral

100

LCK

Function Lock

LCK=0000, SV, level 1 & 2 open

LCK=0001, SV, open only

LCK=0010, SV, level 1 open 

LCK=0011, lock all except LCK

LCK=0100, SV, level 1 & prog. open

LCK=0101, SV,level 1,2,3 open
LCK=1010, level 4 open only

0101

P1

30

PV

SV

SET

i1

240

Press the           key

Repeat the same steps 
as above to display the 
parameters listed at right.

27.5

27.5

PV

SV

Out L

100.0

PV

SV

SET

At

no

PV

SV

Press the           key

SET

Return to “

Return to “

Operation flow

Operation flow

P.3

Summary of Contents for MC-2438

Page 1: ...MC 2 SERIES OPERATION MANUAL MAXTHERMO MAXTHERMO GITTA GROUP CORP GITTA GROUP CORP Version Version 0711070001 0711070001...

Page 2: ...cification Error information Error information Input selection table Input selection table Alarm selection table Alarm selection table P 1 P 2 P 3 P 7 P 11 P 11 P 12 P 17 Alarm action description Alar...

Page 3: ...44 5 44 5 65 70 50 50 80 17 MC 2538 44 5 90 5 111 116 50 96 80 17 MC 2638 90 5 44 5 65 70 96 50 80 17 MC 2738 68 5 68 5 89 94 74 74 80 17 MC 2838 90 5 90 5 111 116 96 96 80 17 A C D B F E H G unit mm...

Page 4: ...Output1 action indication 1 1 PV Process value display 9 9 OUT 2 Output2 action indication 10 10 AT Auto tuning action indication 2 2 SV Set value 11 11 AL 1 Alarm1 action indication 3 3 SET Set key e...

Page 5: ...tuning off set Range of setting 0 100 F S 0 CYT1 Main Control Output cycle time When output is SSR it is set at 3 4 20 mA is set at 1 but output is relay usually it is set at 20 Range of setting 0 100...

Page 6: ...utput only 400 CHO1 Output1 span set Calibrate the high value of output1 Range of setting 0 2000 current output only 2000 OPrL Transmitter zero set Calibrate the low value of transmitter Range of sett...

Page 7: ...0 the parameter is skipped If the digit set at 1 the parameter is opened PrOG 0 Program no repeat 1 Program repeat 0 Without power failure 1 With power failure 0 Start from 0 1 Start from PV 0 Alarm...

Page 8: ...of setting LSPL USPL tM 4 Set time for seg 4 Range of setting 0 99 hours 59 min OUT4 Set output for Seg 4 Range 0 100 SV 5 Set volume for seg 5 Range of setting LSPL USPL tM 5 Set time for seg 5 Rang...

Page 9: ...OH time it is loop open 3 Program It doesn t need installing hardware but has to modify software as following steps a Open MODE in level 4 and set mode 3rd 4th digit to 01 then the parameter of proces...

Page 10: ...ogram will perform again from stopped segment when the power is recovered On the contrary if the PROG 1st digit set 0 it hasn t power failure function the program always perform again from first segme...

Page 11: ...to 01 in level4 to open motor valve control function d Set CYT1 to open close cycle time of motor valve in level2 and RUCY to time from open to close of motor valve in level3 e The LED bar on the pan...

Page 12: ...2438 series don t have this function SET A M A M P 10 1 I 1 Input Main nput Main 1 T C Thermocouple S B R K E J W N Cu or PT100 selectable 2 DC V 10 10mV 0 10mV 0 20mV 0 50mV 0 1V 0 5V 0 10V selectab...

Page 13: ...failed AutF Auto tuning failed NOTE If the marked error occurs the Temperature Controller need repair Please send it to the nearest sales office or retail dealer Error information Error information T...

Page 14: ...13 Deviation high low limit alarm NO 04 14 Dand alarm NO 05 Absolute value high limit alarm YES 15 Absolute value high limit alarm NO 06 Absolute value low limit alarm YES 16 Absolute value low limit...

Page 15: ...Option A Power Supply B Control Output C Input D Alarm F Communication Relay SSR mA V Relay SSR Proportional Motor Valve Control OUT1 Option CLOSE OPEN COM AL1 AL2 OUT1 OUT2 mA V RTD TC mV Use OUT1 O...

Page 16: ...MC 2738 AC 85 265V DC 15 50V Option A Power Supply B Control Output C Input D Alarm E Retransmission F Remote G Communication Relay SSR mA V Relay SSR OUT1 OUT2 NO NC COM mA V RTD TC mV TRS NO COM NC...

Page 17: ...538 MC 2638 AC 85 265V DC 15 50V Option A Power Supply B Control Output C Input D Alarm E Retransmission G Communication F Remote Relay SSR mA V Relay SSR OUT1 OUT2 OUT1 Option Proportional Motor Valv...

Page 18: ...18 19 20 12 13 11 4 5 3 6 7 14 15 MC 2838 AC 85 265V DC 15 50V Option A Power Supply B Control Output C Input D Alarm G Communication F Remote OUT1 OUT2 Relay SSR mA V Relay SSR Proportional Motor Va...

Page 19: ...HIGH OFF ON LOW HIGH OFF ON LOW HIGH OFF ON 06 Absolute low alarm inhibit 16 Absolute low alarm no inhibit 07 Segment end alarm use for Program Model only 1 ALD1 3 set 07 2 AL1 3 alarm segment No set...

Page 20: ...phase SCR A 0 5V B 0 10V C 1 5V C C Out 2 control output mode for cooling Out 2 control output mode for cooling 0 None 1 Relay contact SPDT 5A 240VAC 2 SSR Voltage pulse 20VDC 20mA 3 Current 4 20mA A...

Page 21: ...VE MC 2438 V V V V V V V MC 2538 V V V V V V V V MC 2638 V V V V V V V V MC 2738 V V V V V V V MC 2838 V V V V V V V V MC 2438 1 6 select 1 4 6 select 1 2 5 7 8 select 1 MC 2738 1 6 select 1 2 4 selec...

Reviews: