Change LCK to 0101 then press
the key and key for
4 seconds to level 3
Operating display
Level3 (Input level)
Name
Description
Ex-
factory
Inp1
Main input selections
Select the input range, refer to input selection
K1
dP
Decimal point
Set the position of decimal point
000.0
LSPL
Lower set point limit
Set lower point within INP1
0.0
USPL
Upper set point limit
Set highest point within INP1
400
ALd1
Alarm mode of AL1
Range of setting; oo~19
11
ALt1
Alarm 1 time set
It is used in program function. Range:
00~99.59mm, 0=flicker alarm, 99.59=continued
alarm, others=on delay time
99.59
ALd2
Alarm mode of AL2
Range of setting: 00~19
11
ALt2
Alarm 2 time set
It is used in program function. Range:
00~99.59mm, 0=flicker alarm. 99.59=continued
alarm, others=on delay time.
99.59
ALd3
Alarm mode of AL3
Range of setting: 00~19
11
ALt3
Alarm 3 time set
It is used in program function Range
00~99.59mm 0=flicker alarm 99.59=continued
alarm, others=on delay time
99.59
HYSA
Hystersis of alarm
Range of setting: 0.4~100.0
0.4
CLO1
Output1 zero set
Calibrate the low value of output1
Range of setting: 0-2000( current output only )
400
CHO1
Output1 span set
Calibrate the high value of output1
Range of setting; 0-2000( current output only )
2000
OPrL
Transmitter zero set
Calibrate the low value of transmitter
Range of setting; 0-2000
400
OPrH
Transmitter span set
Calibrate the high value of transmitter
Range of setting; 0-2000
2000
rUCY
The time from open
to close of motor
Full run time of proportional motor, Range of
setting: 0~150Sec
5
WAit
Use in program for
SV wait PV
0=No wait
Other=Wait Volume
0.0
idNO
ID number
Communication ID number
1
bAUd
Baud-rate
UART baud rate selection
Range of setting:110-38.4K BIT/sec
2.4k
SVOS
Compensate SV
Range of setting:-100.0~100.0
0.0
PVOS
Compensate PV
Range of setting:-100.0~100.0
0.0
Unit
Unit of PV
﹠
SV
Range of setting: C,F,A (analog)
℃
SOFt
Soft filter
Adjust the response time of PV, the little the
faster Range of setting:0~254
200
CASC
Cluster control
(don’t care)
Range of setting:0~1000
0.0
TOH
The time for loop
open
Range of setting:0~120 sec.
60
TsH
The time for loop
short
Range of setting:0~120 sec.
20
Press the key
Repeat the same
steps as above to
display the parameters
listed at right.
27.5
27.5
PV
SV
InP1
K1
PV
SV
SET
dP
000.0
PV
SV
SET
Press the key
SET
LSPL
000.0
PV
SV
Press the key
SET
USPL
400.0
PV
SV
Press the key
SET
ALd1
000.0
PV
SV
Return to “
“
P.4