background image

0

0

0

1

0

1

0

0

5

V

W

P

R

Q

3

4

21

22

23

09

19

17

18

SV

SV

Ah1

Ah1

SET

SET

SET

SET

SET

SET

A

/

M

A

/

M

A

/

M

A

/

M

A

/

M

A

/

M

MAN

MAN

MAN

MAN

MAN

MAN

PRG

PRG

PRG

PRG

PRG

PRG

F1

F1

F1

F1

F1

F1

F2

F2

F2

F2

F2

F2

F3

F3

F3

F3

F3

F3

1

0

0

0

SET

SET

SET

A

/

M

A

/

M

A

/

M

MAN

MAN

MAN

PRG

PRG

PRG

F1

F1

F1

F2

F2

F2

F3

F3

F3

SV high alarm

When SV   AL1, AL1 on, When SV<AL1-AH1, AL1 off

AL1 ON

AL1 OFF

SV low alarm

When SV   AL1, AL1 on, When SV>AL1+AH1, AL1 off

Process value limit alarm

LBA loop break alarm

Heater short circuit alarm

timer kick-in alarm

timer finish alarm 

Engineer parameter

Password interface

6.3 Engineer paremeter (PASS-0202 menu) 

PV/SV display mode

Press SET and F3 at the same 
time enter into PASS interface

SET PASS=0202
Press SET to F menu

6.4 Engineer paremeter menu 3 (PASS-0303 menu) 

Engineer parameter

Password interface

PV/SV display mode

Press SET and F3 at the same 
time enter into PASS interface

SET PASS=0303
Press SET to F menu

Auto/manual control
configuration

Depends on the specific functions
some of parameter may or may not be available

Notation

Name

Range

Factory 
default

Remark

Auto/manual control 
switch configuration

0: A/M key disabled
1: A/M Keky enable( press A/M key 3 seconds to switch)

Run/Stop function 
configuration

0: Disable RUN function active by F1 key
    Disable STOP function active by F2 key
1: Enable RUN function active by F1 key
    Enable STOP function active by F2 key

0: Disable auto-tuning active by F3 key
1: Enable auto-tuning active by F3 key

Auto-tuning 
short cut key

Power on 
control mode

0: Auto control mode after power on
1: Stop mode after power on
2: Manual control mode after power on
    intial output value defined by PK01 parameter
3: Controller continue the status from where it left off

soft-start function
configuration

0: Disable soft-start function
1: Enable soft-start function

0: PV re-transmission
1: SV re-transmission

0: Position feedback disabled
1: Position feedback enable for close loop control

Re-transmission 
configuration

Position feedback 
configuration

Remote SV

Quick start menu 1
configuraion

Bar graphic display
configuration

Timer unit

manual output % remote 
setting

0: Remote SV off
1: Remote SV on( panel SV setting off)
2: Remote SV on(panel SV setting on)

0: MV1,MV2,MVFb absent in quick menu 1
1: MV1,MV2, present in quick menu 1, MVFb absent
2: MVFb present in quick menu 1, MV1,MV2 absent
3: MV1,MV2,MVFb present in quick menu 1
0: Bargraphic for OP1 %
1: Bargraphic for OP2 %
2: Bargraphic for TRS%
3: Bargraphic for MVFb%

0: Manual output % set via key pad
1: Manual output % set via remote signal

0: Timer unit “ second”
1: Timer unit “ minute”

A

/

M

SET

Three approaches to exist and save the configuration under F menu

1: Press SET key for 3 seconds

2: Quick press A/M key once

3:Press SET and F3 at the same time

7. Auto-Tuning

MAN

PRG

SET

SET

SET

SET

SET

A

/

M

A

/

M

A

/

M

MAN

MAN

MAN

PRG

PRG

PRG

F1

F1

F1

F2

F2

F2

F3

F3

F3

F3

2s

Enter into F02 menu
choose “AT”

F3 key quick access to AT

If PASS-0303 KAtU=1
thisparameter set as 1
enable the quick access to AT via 
F3 key for 2 seconds

Change the AT value from NO to YES to active the auto-tuning, auto-tuning is an ON/OFF 
control mode, AT light flashes, AT light off when auto-tuning finished, P.I.D values will 
be caculated automatically.

Configure the ATVL parameter under F04 menu, the SV can be shifted down to prevent large overshoot during the auto-tuning
Auto-tuning will be terminated if you enter into manual mode or STOP mode or encounter a power interruption
Auto-tuning will be terminated if the AT value change from YES to NO during the auto-tuning process
Under remote SV pattern, the SV will be locked if auto-tuning actived,  the auto-tuning SV will be the SV
when it was locked, recommend to switch to panel SV setting mode before auto-tuning
*Please start the auto-tuning at the ambinent temp to get best auto-tuing result

8. Auto manual control switch

SET

A

/

M

MAN

PRG

F1

F2

F3

Auto/manual switch via parameter 
menu

Locate AMRS under F02 group
Set MAN as the AMRS value

Auto/manual switch via  A/M key
on the front panel

If KA/M=1 under PASS-0303 menu
then shortcut key A/M on the front is 
enabled you can switch between 
auto/manual conotrol
on the front panel

Manual control mode

How to switch back to auto control mode from manual mode
1: Goes to F02 menu and locate AMRS, change the value from MAN to Auto. exit and save
2: Press A/M key for 2 seconds to auto control mode 

1: Manual control mode, MAN light on
2: Lower display indicates the output %
3: Use F1 and F2 key to quick configure the output %
    under remote setting mode, the output % will be 
    determined by external analog signals, MAN 
     indicator flashes( refer to PASS-030 REMS)
** Controller can be configured as manual control 
    mode right after power on,the output % defined 
    by parameter Pk01 and POWN parameters 

9. RUN/STOP function

SET

SET

SET

SET

A

/

M

A

/

M

A

/

M

MAN

MAN

MAN

PRG

PRG

PRG

F1

F1

F1

F2

F2

F2

F3

F3

F3

SET

A

/

M

MAN

PRG

F1

F2

F3

SET

A

/

M

MAN

PRG

F1

F2

F2

F3

F1

 

RUN/STOP switch via parameter menu

Goes to F02 menu and locate AMRS
put StoP on the lower display and 
set to STOP mode
put Auto on the lower display and 
set to AUTO control mode

Swtich RUN/STOP via F1 on the panel

Goes to PASS-0303 menu, set KR/S
=1 to enable the shortcut key for 
RUN/STOP changover
Press F1 for 2 seconds to switch 
between RUN/STOP

STOP

ACTIVE

Output terminated, alarm off
under STOP mode

Auto mode

Stop mode

Engineer parameters menu  “0202"(PASS-0202)

Notation

Name

Range

Default

Remark

AL1 relay
excitation

AL2 relay
excitation

AL2 interlock

AL1 interlock 

0: AL1 relay pull-in when alarm 1 triggered
1: AL1 relay release when alarm 1 triggered

0: AL1 output standard mode
1: AL1 output interlock mode

0: AL2 relay pull-in when alarm 2 triggered
1: AL2 relay release when alarm 2 triggered

0: AL2 output standard mode
1: AL2 output interlock mode

AL1 relay excitation configuration

 6.3.1 Alarm interlock disenaged procedure

Approach 1: go to F07 menu, press SET

Approach 2: when S.F07=1, press
F1 and F2 for 2 seconds

AL1 interlock, 1LR=1

AL2 interlock, 2LR=1

SET

SET

put 1LR=0 to unlock the
AL1 interlock

put 2LR=0 to unlock the
AL2 interlock

Press SET for 
3 seconds

Press SET

P

V

/S

V m

on

it

or

in

g m

od

e

Note: The alarm action will be suppressed right after power on even the condition is satistifed, and the alarm standby on works 1 time
right after power on, the alarm will go off if the condition satisfied again after supression at the first time

FT20X

-

800

-

C1

Summary of Contents for FT200

Page 1: ...rm relay 250Vac 3A resistive load 4 20mA output maximum load resistance 500 ohm 12VDC pulse output 20mA Remark Above is a general wiring diagram please always refer to the connection diagram on the side of the controller INP2 INP3 used for remote SV or position feedback or remote output under manual mode Please refer to wiring diagram on the unit for single phase or three phase triac output option...

Page 2: ...uration mode Press once or press once or press once Upper display shows SV lower shows the current SV value with the unit s digits flashing the flashing digits can be modifited Press key move the cursor to the hundred s digits and flashing 4 SV value modified 5 Save the configuration 6 PV SV display mode Press key change the hundred s digit to 2 Press SET save the configuration or press A M key sa...

Page 3: ...SV setting features only Notation Name Description Default SV setting configured by external D1 D2 terminals SV1 D1 open D2 open SV SV1 SV setting configured by external D1 D2 terminals SV2 D1 open D2 close SV SV2 SV setting configured by external D1 D2 terminals SV3 D1 close D2 open SV SV3 SV setting configured by external D1 D2 terminals SV4 D1 close D2 close SV SV4 Event input SV1 Event input S...

Page 4: ...ers 0 Absent 1 Present in quick start menu 1 2 Present in quick start menu 2 3 Present in quick start menu 3 Three approaches to exist and save the configuration under F menu 1 Press SET key for 3 seconds 2 Quick press A M key once 3 Press SET and F3 at the same time 6 2 Engineer paremeter PASS 0101 menu PV SV display mode Password interface Engineer parameter Press SET and F3 at the same time ent...

Page 5: ...is an ON OFF control mode AT light flashes AT light off when auto tuning finished P I D values will be caculated automatically Configure the ATVL parameter under F04 menu the SV can be shifted down to prevent large overshoot during the auto tuning Auto tuning will be terminated if you enter into manual mode or STOP mode or encounter a power interruption Auto tuning will be terminated if the AT val...

Page 6: ...right after some while 0 point caliberation finished 2 Analog output controller upper shows AA2L OP1 output at 0 value lower display changes along with the feedback signal display switch to the one at right after some while 0 caliberation finished 1 Upper shows AA2H OP1 light on OP1 relay pull in valve direct act lower display changes along with the direct act display switch to the right one after...

Reviews: