background image

K

E

K
K
K

E

K

E

E

E

K

E

0

.

0

0

.

0

0

0

.

0

0

0

.

0

0

0

.

0

0

.

0

0

0

0
0
0

to

to

to

to

to

to

to

to

to

to

200

200

.

0

200

.

0

400

400

300

.

0

300

300

.

0

600

400

.

0

400

.

0

400

1300

800

A4
A6
B3

A2

D2

A4

D2

D4

A8

D3

 

Wu3

_

Re25

S

R
B
N

S
R

B
N

W

0
0

2 0 0
0
60 0

to
to

to
to
to

1600

1769

1800
1300
2200

B6
B8

B8
B3
B0

T

T
T

to
to

D4
A4

J

J

J
J

J
J

0
0
0

to
to
to

to
to

300

400
1000

A3

D3
D4

A4
A0

AN1
AN2
AN3
AN3
AN4
AN4
AN4
AN3
AN3

10

to 9999

-

1999

to

to

99

.

99

9

.

999

-

19

.

99

-

1

.

999

to 999

.

9

-

199

.

9

0

0

0
0

-

100

-

200

-

200

-

200

D
D
D

D

D

D
D
D
D
D
D
D
D

D1
D2
G2

F3

F2

A1

A2

A4
A8
C2
C4
C6
C8

100

200

400
800
200
400
600
800

**

6

B

mA

V

TC

A

B

OP1

OP2

RS

-

485

A

+

B

-

AL1

AL2

85

~

265V

AC

L

N

17

18

16

15

14

13

23

24

22

21

20

19

7

10

12

11

9

8

1

2

6

5

4

3

TRS

GND

-

+

5V

INP2

+

INP3

+

AU3

SET

SET

SET

A

/

M

A

/

M

A

/

M

MAN

MAN

MAN

PRG

PRG

PRG

F1

F1

F1

F2

F2

F2

F3

F3

F3

SET

A

/

M

MAN

PRG

F1

F2

F3

SET

A

/

M

MAN

PRG

F1

F2

F3

SET

A

/

M

MAN

PRG

F1

F2

F3

SET

SET

A

/

M

A

/

M

MAN

MAN

MAN

MAN

MAN

MAN

MAN

PRG

PRG

PRG

PRG

PRG

PRG

PRG

F1

F1

F2

F2

F2

F3

F3

F3

D1

D2

 

220V

M

10. SV Panel setting and remote setting 

10.1 Remote setting SV,   use D1/D2 terminals at the back to set the SV 

1: D1/D2 SV setting function was specified when order
2: PASS-0303 parameter RESV=1 or 2, enable the SV external setting

Condition:

4 SV can be assigned to SV1,SV2,SV3,SV4 under F01 menu
D1 open/D2 open:  SV=SV1,   D1 close/D2 open:  SV=SV2
D1 open/D2 close: SV=SV3,   D1 close/D2 close: SV=SV4

SV1,SV2,SV3,SV4                                on the panel indicates respective SV value(except FT200)

10.2 Remote setting SV via external analong signal input from INP2 or INP3

GND

-

or

condition 1: remote SV via analong signal from INP2 or INP3 was specificed when order
                 2: parameter RESV=1 or 2 (under menu PASS-0303), enable remote SV function
                 PASS-0101 menu, LSPL corresponding to the lower limit SV when analog singnal at lower limit
                                                USPL cooresponding to the higher limit SV when analog signal at higher limit
                                                SV1 and SV2 indicator              lights up at the same time indicate the SV is 
                                                being configured via external analog signal(except FT200)

10.3 Switch between SV remote setting and SV panel setting

Goes to PASS-0303 and set RESV=2, quick swtich between remote SV setting and panel SV setting enabled, enter into
remote SV mode after power on

SV panel set mode

Remote SV mode

Press F2 and F3 at the same time
for approxi 2 seconds to switch 
back and forth between SV panel set
mode and SV remote setting mode
Only applicable when RESV=2(under
PASS-0303 menu)

11. Three wires motor valve control

This is only available for valve control version of controller
please specify if you need position feedback or not when order 
with us,output: OP1 for valve direct acting (open), OP2 for valve 
reverse acting(close),make sure to put the motor valve on the 
intermediate relay or AC contractors,You can also goes to 
PASS-0303 and set PFbK=0 and switch off the position 
feedback function in case you’ve already ordered a controller 
with position feedback feature, the motor valve travel 
time must be specifed via rUCY parameter under PASS-0101 
menu in a no position feedback case,Quick start meanu 
parameter MVFb is a monitoring parameter for the valve 
feedback value, this can be configured via parameter MoNI 
under PASS-0303, the bargraphic can also be used to indicate
the feedback value, this 
can be configured via 
bEAM under 
PASS=0303

1: No connection goes to terminals 
    16,17,18 for no feedback valve
2: Postive input on terminal 18 and 
    negative goes to terminal 17 for 
    analog feedback valve

Potentiometer feedback

Valve 
close

Valve 
open

Actuator

Fuel pipe

Fuel injection point

Thermocouple

Burner

Potentiometer 
feedback

(object 
being 
controlled)

W

ir

e l

en

g

th

>

2

 m

et

er

s

W

ir

e l

en

g

th

>

2

 m

et

er

s

12. Positiion feedback caliberation and operation

GND

-

GND

-

+

5V

INP2

+

INP2

+

Condition
1:  Position analong feedback via terminal INP2 ordered( only applicable for 3 wires motor valve or analog output controller)
2:  PFbK=1, position feedback enabled for close loop control
General feedback signal,   1) standard analog signal,  2)Potentiometer feedback signal, specify when order

3 wires potentiometer as feedback source
Controller auto detect direct/reverse act 
of the potentiometer

input +

input -

analog input

4-20mA, 0-5V input
from INP2 terminals

Auto caliberatioin on the position feedback

PV/SV mode

Password input

Position feedback caliberation

PV/SV mode, press SET and F3 
at the same time PASS pop-up

Put PASS=0111
press SET to enter

Position feedback
“0" point caliberation

Position feedback
“maximum” point caliberation

PV/SV mode

Auto

Auto

1. 3 wires motor valve auto caliberation 
Upper shows AA2L, OP2 light on, OP2 relay
pull-in, motor reverse act, lower display 
changes along with the motor reverse act, 
display switch to one at right after some 
while, “0" point caliberation finished
2. Analog output controller
upper shows AA2L, OP1 output at 0% 
value, lower display changes along with 
the feedback signal,display switch to the 
one at right after some while, “0"caliberation 
finished

1.Upper shows AA2H, OP1 light on
OP1 relay pull-in, valve direct act
lower display changes along with the 
direct act, display switch to the right
one after some while, caliberation finished

2.for analong output, upper shows AA2H, 
OP1output 100%,lower display changes 
along with the valve feedback signal, 
display changes to the right after some 
while, process finished

Caliberation finish, goes back to PV/SV 
mode,these process always carried out 
automatically, user shall only oberserve 
the lower display changes, MVFb can be 
used to monitor the feedback value,MoNI 
under PASS-0303 used to define the 
status of MVFb
Bargraphic % display can be used to 
shows the feedback %, bEAM uner 
PASS-0303 used to define the status of 
the bargraphic display

13. Temp constant mode and ramp/soak mode

This is only applicable for programmable version of controller. specify when order 

13.1 Parameters that involved 

Assign the unit for timer
0: unit is second
1: unit is minute

Parameters under PASS-0101

0: standard type
1: temp constant mode
2: ramp and soak mode

Assign the temperature where timer kick-in 
constant temp/ramp and soak start temp=SV-tSP
when PV>SV-tSP and stays for 5 seconds, program activated
Define the control status after timer finished
=0, PID stop working after timer finished
=1, PID continue the output after timer finished
power interruption or press F1 for 2 seconds can re-start 
the program

F03 group of parameters

Ramp and soak mode,Ramp
is the temperature increase rate
degree per minute, degree/minut

Timer configuration 
T1=0 means timer off

Parameter “Unit” under PASS-0303
 

Setting value

power on or 
input SV value

alarm output when timer starts

alarm output when timer finish

PV> SV-tSP, stays for 5 seconds
lower display starts to indicate the timer 
process, PRG light flashes

PV=SV+rAMP

output 
continous 
after timer 
finish,PRG 
lights on

output stop
after timer 
finish
PRG light 
on

END MODE

Temp

Time

Ramp and soak mode

lower display starts to indicate 
the PV when ramp/soak mode activated
PRG light on

power on or 
input SV value

5 seconds

Ramp period

Soak period

minute/second

13.2 Ramp and soak mode detailed working flow chart PMd=2
 1. program execute: power-on, lower display shows SV, this will delay 5 seconds before the program starts, PRG lights on during the 
     ramp and soak process,lower display starts to indicate the PV value, PV increase gradually based on the preset ramp up rate 
     torwards to SV value 
2. Timer kick-in: When PV >SV-tSP for at 5 seconds, timer kick-in, lower display shows the timer, PRG flashes,timer range is t1 value, 
     timer starts alarm and timer finish alarm can be configured, refer to PASS-0101 ALd1 and ALd2
3. Timer finish: when timer finish, PRG light on, based on PENd parameter under PASS-0101, output can be configured 
   as continoue working or stop, when alarm mode=18, alarm will be triggered after timer finish
4. program terminated: if PEND=0 configured, program ends after timer finish, lower display shows “End”
    main output off, press F1 for 2 seconds can enter into STOP mode or active the program again

13.3 Temp constant mode working flow chart PMd=1
         1. Program activate: lower shows SV, and heatup torwards SV immediately
         2. Timer kick-in: when PV>SV-tSP, stays for 5 seconds, timer activated, lower display shows 
              timing process, PRG flashes,timer range is t1 value, an alarm can go off when timers starts by 
               configuring the ALd1 or ALd2=17 under PASS-0101
         3. Timer finish: when timer finish, PRG light on, based on PENd parameter under PASS-0101, output can be configured 
             as continoue working or stop, when alarm mode=18, alarm will be triggered after timer finish
         4. program terminated: if PEND=0 configured, program ends after timer finish, lower display shows “End”
             main output off, press F1 for 2 seconds can enter into STOP mode or active the program again

14. RS-485 communication brief

15. Input sensors and range

(1) Communication based on modbus RTU, support 03 read command, 06 and 10 
      write command
(2) Communication format, 2 wires system, half-duplex, single drop connection
(3) Communication speed: 2400, 4800,9600,19200 baud rate, data format, 1 start bit+
      8 data bit+parity(N,o.E)+1 /2 stop bit
(4) Support maximum 36 wirte command and 37 read command
(5) Detailed setting goes to PASS-0101 and locate parameter IdnO, bAUd, UCR parameters
(6) Refer to “COM-800-C1" for detailed communication protocol information

Input type

Code

Input type

Code

Input type

Code

The accuracy is not guaranteed for type S thermocouple in the range of 0-100
Remark 1:  user can switch input between thermocouple and RTDs via software
Remark 2:  analong input except 0-50mA, 10-50mV needs to be specified when order

FT20X

-

800

-

C1

Summary of Contents for FT200

Page 1: ...rm relay 250Vac 3A resistive load 4 20mA output maximum load resistance 500 ohm 12VDC pulse output 20mA Remark Above is a general wiring diagram please always refer to the connection diagram on the side of the controller INP2 INP3 used for remote SV or position feedback or remote output under manual mode Please refer to wiring diagram on the unit for single phase or three phase triac output option...

Page 2: ...uration mode Press once or press once or press once Upper display shows SV lower shows the current SV value with the unit s digits flashing the flashing digits can be modifited Press key move the cursor to the hundred s digits and flashing 4 SV value modified 5 Save the configuration 6 PV SV display mode Press key change the hundred s digit to 2 Press SET save the configuration or press A M key sa...

Page 3: ...SV setting features only Notation Name Description Default SV setting configured by external D1 D2 terminals SV1 D1 open D2 open SV SV1 SV setting configured by external D1 D2 terminals SV2 D1 open D2 close SV SV2 SV setting configured by external D1 D2 terminals SV3 D1 close D2 open SV SV3 SV setting configured by external D1 D2 terminals SV4 D1 close D2 close SV SV4 Event input SV1 Event input S...

Page 4: ...ers 0 Absent 1 Present in quick start menu 1 2 Present in quick start menu 2 3 Present in quick start menu 3 Three approaches to exist and save the configuration under F menu 1 Press SET key for 3 seconds 2 Quick press A M key once 3 Press SET and F3 at the same time 6 2 Engineer paremeter PASS 0101 menu PV SV display mode Password interface Engineer parameter Press SET and F3 at the same time ent...

Page 5: ...is an ON OFF control mode AT light flashes AT light off when auto tuning finished P I D values will be caculated automatically Configure the ATVL parameter under F04 menu the SV can be shifted down to prevent large overshoot during the auto tuning Auto tuning will be terminated if you enter into manual mode or STOP mode or encounter a power interruption Auto tuning will be terminated if the AT val...

Page 6: ...right after some while 0 point caliberation finished 2 Analog output controller upper shows AA2L OP1 output at 0 value lower display changes along with the feedback signal display switch to the one at right after some while 0 caliberation finished 1 Upper shows AA2H OP1 light on OP1 relay pull in valve direct act lower display changes along with the direct act display switch to the right one after...

Reviews: