40
STARTUP PROCEDURE & ADJUSTMENT
Furnace must have a 115 VAC power supply properly
connected and grounded. Proper polarity must be
maintained for correct operation. In addition to the
following start-up and adjustment items, refer to further
information in
Operational Checks
section.
f
urnace
c
aBInet
Check that all furnace cabinet sealing components are in
place (plugs, grommets, gaskets). NOTE: If the furnace
bottom panel has not been removed for a return duct
connection, all perforations must be sealed with duct
sealant compound or other suitable method to prevent
air leakage. For optimal performance verify that all door
gaskets are properly in place and replace as needed to
prevent air leakage.
D
raIn
t
raP
P
rIMIng
The drain trap
MUST
be primed prior to furnace startup.
To prime, fill both sides of the drain trap with water. This
ensures proper furnace drainage upon startup and
prohibits the possibility of flue gases escaping through the
drain system.
f
urnace
o
PeratIon
Purge gas lines of air prior to startup. Be sure not purge
lines into an enclosed burner compartment. Follow NFPA
54, National Fuel Gas Code for proper purging methods.
In Canada, follow approved purging methods in CAN/CSA
B149.1-15.
Check for leaks using an approved chloride-free soap and
water solution, an electronic combustible gas detector,
or other approved method. Verify that all required kits
(propane gas, high altitude, etc.) have been appropriately
installed.
f
urnace
s
tartuP
1. Close the manual gas shutoff valve external to the
furnace.
2. Turn off the electrical power to the furnace.
3. Set the room thermostat to the lowest possible
setting.
4. Remove the burner compartment door.
note: t
HIs
furnace
Is
equIPPeD
wItH
an
IgnItIon
DeVIce
wHIcH
autoMatIcallY
lIgHts
tHe
Burner
. D
o
not
trY
to
lIgHt
tHe
Burner
BY
HanD
.
5. Move the furnace gas valve manual control to the
OFF position.
6.
Wait five minutes then smell for gas. Be sure check
near the floor as some types of gas are heavier than
air.
7.
If you smell gas after five minutes, immediately follow
the safety instructions in the
Safety Considerations
on
page 3 of this manual. If you do not smell gas after
five minutes, move the furnace gas valve manual
control to the ON position.
•
Profile D
(4) ramps up to 50% of the demand for 1/2
minute, then ramps to 85% of the full cooling demand
airflow and operates there for approximately 7 1/2
minutes. The motor then steps up to the full demand
airflow. Profile D has a 1/2 minute at 50% airflow OFF
delay.
OFF
OFF
f
Igure
61
115 V
olt
l
Ine
c
onnectIon
or
e
lectronIc
a
Ir
c
leaner
WARNING
H
IgH
Voltage
!
t
o
aVoID
Personal
InjurY
or
DeatH
Due
to
electrIcal
sHock
,
DIsconnect
electrIcal
Power
Before
serVIcIng
or
cHangIng
anY
electrIcal
wIrIng
.
The accessory load specifications are as follows:
EAC
1.0 AMP maximum at 120 VAC
The furnace integrated control module is equipped with a
line voltage accessory terminal for controlling power to an
optional field supplied electronic air cleaner or any device
required to operate inparallel with a circulating fan demand.
To connect an electronic air cleaner using the line voltage
EAC terminal:
• Turn OFF power to the furnace before installing any
accessories.
• Follow the air cleaner manufacturers’ instructions
for locating, mounting, grounding, and controlling
accessories. Utilize 1/4” quick connect terminals to
make accessory wiring connections to the furnace
integrated control module.
• Connect the hot terminal utilized for accessory
operation to the EAC terminal and the neutral side
of power to NEUTRAL bus on the integrated furnace
control or the neutral connection in the furnace
junction box.
•
All field wiring must conform to applicable codes.
• If it is necessary for the installer to supply additional
line voltage wiring to the inside of the furnace, the
wiring must conform to all local codes, and have a
minimum temperature rating of 105°C.
• All line voltage wire splices must be made inside the
furnace junction box.