FIGURE 9A.

Temperature-Pressure Relief Valve

This heater is provided with a properly certified combination
temperature - pressure relief valve by the manufacturer.

The valve is certified by a nationally recognized testing
laboratory that maintains periodic inspection of production of
listed equipment of materials as meeting the requirements for
Relief Valves and Automatic Gas Shut-off Devices for Hot Water
Supply Systems, ANSI Z21.22 • CSA 4.4, and the code
requirements of ASME.

If replaced, the valve must meet the requirements of local
codes, but not less than a combination temperature and
pressure relief valve certified as indicated in the above
paragraph.

The valve must be marked with a maximum set pressure not to
exceed the marked hydrostatic working pressure of the water
heater (150 psi = 1,035 kPa) and a discharge capacity not less
than the water heater input rate as shown on the model rating
plate.

For safe operation of the water heater, the relief valve must not
be removed from its designated opening nor plugged.

The temperature-pressure relief valve must be installed directly
into the fitting of the water heater designed for the relief valve.
Position the valve downward and provide tubing so that any
discharge will exit only within 6 inches (153 mm) above, or at
any distance below the structural floor.  Be certain that no contact
is made with any live electrical part.  The discharge opening
must not be blocked or reduced in size under any

circumstances.  Excessive length, over 30 feet (9.14 m), or use
of more than four elbows can cause restriction and reduce the
discharge capacity of the valve.

No valve or other obstruction is to be placed between the relief
valve and the tank.  Do not connect tubing directly to discharge
drain unless a 6 inch air gap is provided.  To prevent bodily
injury, hazard to life, or property damage, the relief valve must
be allowed to discharge water in quantities should
circumstances demand.  If the discharge pipe is not connected
to a drain or other suitable means, the water flow may cause
property damage.

The Discharge Pipe:

Shall not be smaller in size than the outlet pipe size of the
valve, or have any reducing couplings or other restrictions.

Shall not be plugged or blocked.

Shall be of material listed for hot water distribution.

Shall be installed so as to allow complete drainage of both
the temperature-pressure relief valve, and the discharge
pipe.

Shall terminate at an adequate drain.

Shall not have any valve between the relief valve and tank.

The temperature-pressure relief valve must be manually
operated at least once a year.  Caution should be taken to
ensure that (1) no one is in front of or around the outlet of the
temperature-pressure relief valve discharge line, and (2) the
water manually discharged will not cause any bodily injury or
property damage because the water may be extremely hot.

If after manually operating the valve, it fails to completely reset
and continues to release water, immediately close the cold
water inlet to the water heater, follow the draining instructions,
and replace the temperature-pressure relief valve with a new
one.

Summary of Contents for HRE11240S

Page 1: ...6001864 PRINTED IN THE U S A 1204 PART NO 184743 001 Series Twelve HRE11240S HRE41240S HRE11250S HRE41250S HRE11250T HRE41250T HRE11282T HRE41282T SAVETHISMANUALFORFUTUREREFERENCE GAMA certification applies to all residential electric water heaters with capacities of 20 to 120 gallons Input rating of 12 kW or less at a voltage no greater than 250V ...

Page 2: ...ce Center has the ability equivalent to a licensed tradesman in the fields of plumbing and electrical work including a thorough understanding of the requirements of the National Electric Code as it relates to the installation of electric water heaters The Service Center also has a thorough understanding of this instruction manual and is able to perform repairs strictly in accordance with the servi...

Page 3: ...3 GENERAL SAFETY GENERAL SAFETY GENERAL SAFETY GENERAL SAFETY GENERAL SAFETY ...

Page 4: ...ing the Water Heater 12 Converting the Lower Element 12 14 Wiring 14 15 Wiring Diagrams 16 SERVICEAND MAINTENANCE 17 22 Temperature Regulation 17 Thermostat 17 Temperature Settings 17 Thermostat Adjustment 17 18 Anode Rod Inspection 18 Temperature Pressure Relief Valve Operation 18 Draining 18 19 Thermostat Removal Replacement 19 Element Cleaning Replacement 19 22 Drain Valve Washer Replacement 22...

Page 5: ...rvicer Carefully plan the place where you are going to put the water heater Correct electrical wiring and connections are very important in preventing death from possible electrical shock and fires Examine the location to ensure the water heater complies with the Locating the New Water Heater section For California installation this water heater must be braced anchored or strapped to avoid falling...

Page 6: ...ENCH GARDEN HOSE 6 FOOT TAPE HACKSAW TUBING CUTTER PROPANE TORCH ROLL OF EMERY CLOTH 3 4 19 mm WIRE BRUSH 1 2 13 mm WIRE BRUSH ROLL OF LEAD FREE SOFT SOLDER SOLDER FLUX Accessories To simplify the installation Maytag has available the installation parts shown below You may or may not need all of these accessories depending on your type of installation Call Maytag Customer Service at 1 800 788 8899...

Page 7: ...the electrical supply connection from the water heater junction box FIGURE 5 5 a If you have copper piping to the water heater the two copper water pipes can be cut with a hacksaw approximately four inches away from where they connect to the water heater This will avoid cutting off the pipes too short Additional cuts can be made later if necessary Disconnect the temperature pressure relief valve d...

Page 8: ...e cold water and hot water pipes connected to the water heater INSULATION BLANKETS Insulation blankets are available to the general public for external use on electric water heaters but are not necessary with this product The purpose of an insulation blanket is to reduce the standby heat loss encountered with storage tank heaters Your water heater meets or exceeds the National Appliance Energy Con...

Page 9: ...ion must provide adequate clearances for servicing and proper operation of the water heater The Convertible Lower Element The Upper Element is a conventional 3800 watt element which only operates at its rated wattage on 240 volts See rating plate on the water heater The Lower Element of the water heater can be converted from operation at 3800 watts to 5500 watts on a 240 volt system Read and follo...

Page 10: ...ith a check valve etc in the cold water supply means must be provided to control thermal expansion Contact the local utility or call Maytag Customer Service at 1 800 788 8899 for an authorized servicer on how to control this situation NOTE If using copper tubing solder tubing to an adapter before attaching the adapter to the water inlet connection Do not solder the water supply lines directly to t...

Page 11: ... any circumstances Excessive length over 30 feet 9 14 m or use of more than four elbows can cause restriction and reduce the discharge capacity of the valve No valve or other obstruction is to be placed between the relief valve and the tank Do not connect tubing directly to discharge drain unless a 6 inch air gap is provided To prevent bodily injury hazard to life or property damage the relief val...

Page 12: ... the water heater The water heater is factory set to operate at 3800 watts The lower element can be converted to operate at 5500 watts Refer to The Convertible Lower Element section The Upper Element is a conventional 3800 watt element which only operates at its rated wattage on 240 volts See rating plate on the water heater The lower Element of the water heater can be converted from operation at ...

Page 13: ...e to expose the terminal cover FIGURE 15 4 Lower Element Lift out the tab as shown to unclip the terminal cover from the thermostat The terminal cover can now be removed from the thermostat FIGURE 16 5 Remove the screws from terminal 2 of the element and move the looped end of the wire aside FIGURE 17 6 The buss bar is labeled 5500 W Place the buss bar over terminals 2 and 3 with the 5500 W visibl...

Page 14: ...e thermostat and element FIGURE 20 11 Replace the access panel FIGURE 21 12 Complete wiring to the water heater or if completed turn ON electric power to the water heater after filling the tank with water FIGURE 22 Never use this water heater unless it is completely full of water To prevent damage to the tank and heating element the tank must be filled with water Water must flow from the hot water...

Page 15: ...g may be used for the grounding means if conduit or tubing is terminated in fittings approved for grounding C Flexible metal conduit or flexible metallic tubing shall be permitted for grounding if all the following conditions are met The length in any ground return path does not exceed 6 feet The circuit conductors contained therein are protected by overcurrent devices rated at 20 amperes or less ...

Page 16: ...ng Diagrams STANDARDWIRINGFOR2WIRELEADWATERHEATERS NON SIMULTANEOUS OPERATION 240 VOLT DOUBLE ELEMENT FIGURE 24 FIGURE 25 WIRING FOR 3 WIRE LEAD WATER HEATERS NON SIMULTANEOUS OPERATION 240 VOLT DOUBLE ELEMENT ...

Page 17: ...The thermostats of this water heater have been factory set at the HOT position which approximates 120 F 49 C The thermostats are adjustable if a different water temperature is desired Read all warnings in this manual and on the water heater before proceeding UPPER THERMOSTATADJUSTABLE BEHIND UPPER ACCESS PANEL FIGURE 27 FIGURE 28 Temperature Settings HOT Is a thermostat setting of approximately 12...

Page 18: ...ften than an anode rod that appears to be intact Replacement of a depleted anode rod can extend the life of your water heater Inspection should be conducted by calling Maytag Customer Service at 1 800 788 8899 for an authorized servicer At a minimum the anode s should be checked annually after the warranty period Temperature Pressure Relief Valve Operation The temperature pressure relief valve mus...

Page 19: ...o prevent damage to the tank and heating element the tank must be filled with water Water must flow from the hot water faucet before turning ON power Thermostat Removal Replacement 1 Turn OFF the electrical power to the water heater at the junction box 2 Remove the access panel and the insulation cap with handle 3 Lift out the tab as shown below to unclip the terminal cover from the thermostat The...

Page 20: ...rain or outdoors Open the water heater drain valve Open a nearby hot water faucet which will relieve pressure in the water heater and speed draining FIGURE 33 The water passing out of the drain valve may be extremely hot To avoid being scalded make sure all connections are tight and that the water flow is directed away from any person 4 Remove the two screws securing the access panel and remove pa...

Page 21: ... The cold water supply valve must be left open when the water heater is in use 13 To insure complete filling of the tank allow air to exit by opening the nearest hot water faucet Allow water to run until a constant flow is obtained This will let air out of the water heater and the piping Never use this water heater unless it is completely full of water To prevent damage to the tank and heating ele...

Page 22: ... have installed devices such as pressure reducing valves check valves back flow preventers etc to control these types of problems When these devices are not equipped with an internal by pass and no other measures are taken the devices cause the water system to be closed As water is heated it expands thermal expansion and closed systems do not allow for the expansion of heated water The water withi...

Page 23: ...GAS Hydrogen gas can be produced in a hot water system that has not been used for a long period of time generally two weeks or more Hydrogen gas is extremely flammable and explosive To prevent the possibility of injury under these conditions we recommend the hot water faucet be opened for several minutes at the kitchen sink before any electrical appliances which are connected to the hot water syst...

Page 24: ...o your house has not been interrupted If this is the case contact the electric company 6 Is the thermostat set to the desired temperature See Temperature Regulation section 7 If you had experienced very hot water and now no hot water the problem may be due to the high temperature shut off system See High Temperature Shut Off System in the Troubleshooting section 8 During very cold weather the inco...

Page 25: ...on the threads and replace Then follow Filling the Water Heater instructions in the Installation Instructions section FIGURE 44 REP REP REP REP REPAIR P AIR P AIR P AIR P AIR PARTS LIST ARTS LIST ARTS LIST ARTS LIST ARTS LIST MAYTAG STATEPARTNUMBER CONVERSIONKEY MAYTAG STATE 66001001 9000225 66001002 9000396 66001010 9002403 66001011 9001609 66001012 9001608 66001013 ETC2X 66001014 ETC5X 66001020 ...

Page 26: ... Not Illustrated Key Model No No Part Description HRE11240S HRE41240S HRE11250S HRE41250S 1 Buss Bar Kit 66001055 66001055 66001055 66001055 2 Drain Valve 66001747 66001747 66001747 66001747 3 Drain Valve Washer 17 32 x 13 64 x 1 8 Tick 66001021 66001021 66001021 66001021 4 Element Gasket 66001053 66001053 66001053 66001053 5 Element Gasket 66001053 66001053 66001053 66001053 6 Inlet Tube 66001520...

Page 27: ... Not Illustrated Key Model No No Part Description HRE11250T HRE41250T HRE11282T HRE41282T 1 Buss Bar Kit 66001055 66001055 66001055 66001055 2 Drain Valve 66001747 66001747 66001747 66001747 3 Drain Valve Washer 17 32 x 13 64 x 1 8 Tick 66001021 66001021 66001021 66001021 4 Element Gasket 66001053 66001053 66001053 66001053 5 Element Gasket 66001053 66001053 66001053 66001053 6 Inlet Tube 66001260...

Page 28: ...ase if a leak occurs in the tank a new water heater of the closest capacity and quality then available will be replaced free of charge for the water heater with the owner paying all other costs including labor mileage and transportation If the water heater is subjected to commercial institutional industrial or non residential use the above warranty coverage for the tanks that are proven to be defe...

Reviews: