11
This water heater must not be installed directly on carpeting.
Carpeting must be protected by metal or wood panel beneath
the appliance extending beyond the full width and depth of the
appliance by at least 3 inches (76.2 mm) in any direction, or if
the appliance is installed in an alcove or closet, the entire floor
must be covered by the panel. Failure to heed this warning
may result in a fire hazard.
Minimum clearances between the water heater and
combustible construction are 0 inch at the sides and rear, 4
inches (102 mm) at the front, and 6 inches (153 mm) from the
vent pipe. Clearance from the top of the jacket is 12 inches
(305 mm) on most models. Note that a lesser dimension may
be allowed on some models, refer to the label attached adjacent
to the gas control valve on the water heater, see Figure 9.
FIGURE 9.
A gas water heater cannot operate properly without the correct
amount of air for combustion. Do not install in a confined area
such as a closet, unless you provide air as shown in the
Locating and Installing The New Water Heater
section. Never
obstruct the flow of ventilation air. If you have any doubts or
questions at all, call your gas supplier. Failure to provide the
proper amount of combustion air can result in a fire or explosion
and cause death, serious bodily injury, or property damage.
FIGURE 10.
If this water heater will be used in beauty shops, barber shops,
cleaning establishments, or self-service laundries with dry
cleaning equipment, it is imperative that the water heater or
water heaters be installed so that combustion and ventilation
air be taken from outside these areas.
Propellants of aerosol sprays and volatile compounds,
(cleaners, chlorine based chemicals, refrigerants, etc.) in
addition to being highly flammable in many cases, will also
change to corrosive hydrochloric acid when exposed to the
combustion products of the water heater. The results can be
hazardous, and also cause product failure.
Insulation Blankets
Insulation blankets available to the general public for external
use on gas water heaters are not necessary with Maytag
products. The purpose of an insulation blanket is to reduce the
standby heat loss encountered with storage tank heaters. Your
Maytag water heater meets or exceeds the EPACT standards
with respect to insulation and standby loss requirements,
making an insulation blanket unnecessary.
WARNING
Should you choose to apply an insulation blanket to this heater,
you should follow these instructions (See Figure 7 for
identification of components mentioned below). Failure to follow
these instructions can restrict the air flow required for proper