background image

 

 

 

 

 

A.1 OIL BURNER AIR ADJUSTMENT 

The burner air supply is adjusted to maintain the 

fuel to 

air

 

ratio

 to obtain ideal combustion conditions. A lack of 

air causes "soft" and "sooty" flames, resulting in soot 
build-up throughout the heat exchanger passages. 
Excess combustion air causes a bright roaring fire and 
high stack temperatures resulting in poor fuel 
efficiency. The POF1HD140AVFA and 
POF1HD091AVFA furnaces operate most efficiently 
with a No. 1 smoke spot on the Bacharach Scale. This 
is not necessarily the optimum setting; however, 
because dust will inevitably build up on the air moving 
components of the oil burner assembly. This will result 
in decreased air supply with the potential result of soot 
building up in the flue gas passageways of the heat 
exchanger. Soot behaves as an insulator and impairs 
good heat transfer. Stack temperature will increase, 
and the overall efficiency will decrease. As a means of 
avoiding this problem, it is advisable to adjust the air 
supply to provide no more than a trace smoke spot on 
the Bacharach Scale.  

For complete details, consult the oil burner instruction 
manual provided in the furnace documents envelope. 

 

Beckett AF Burner 

Adjust the air shutter by loosening the locking screws 
and moving the air shutter, and if necessary, the bulk 
air band. 

 

A.2 BURNER ELECTRODES 

Adjustment of the electrode tips with respect to each 
other, the nozzle, and to the rest of the burner is very 
important to ensure smooth start-ups and to permit 
efficient combustion. 

Beckett AF Burner

 

Electrode gap: 5/32 inch. 

Distance above horizontal centerline: 5/16 inch. Older 
instruction sheets specify 7/16 inch. The current 
specification is 5/16 inch. 

Distance ahead of nozzle: 1/16 inch. 

“Z” dimension, the distance from the front of the end 
cone (head) to the face of the nozzle should be 1-1/8 
inches. If a ceramic head is used, the distance from 
the end cone to the nozzle face is increased to 1-3/8 
inches. 

 

 

 

 

A.3 START UP 

The furnace should be operated for a minimum of 10 
minutes to reach steady state conditions before fine 
tuning combustion. The warm up time is ideal for 
testing the oil pump pressure. 

Drill a 1/4-inch test port in the venting between the 
furnace flue outlet and draft regulator (barometric 
damper). Insert a stack thermometer and note the flue 
gas temperature. The flue gases should be within a 
range of 350°F to 450°F. If the flue gases are below 
the range, it may be necessary to slow down the 
blower fan. If the flue gases are above the range, the 
blower fan may require speeding up. Stack 
temperature varies directly with the system 
temperature rise. System temperature rise is the 
difference between the furnace outlet temperature and 
furnace inlet temperature as measured in the vicinity of 
the connection between the plenum take-offs and the 
trunk ducts.  Temperature rise value is listed on the 
system rating plate. 

Perform a smoke spot test. The smoke spot should not 
exceed No. 1 on the Bacharach Scale. 

After the air adjustments have been completed, re-
check the draft pressure at the test port on the burner 
mounting plate as shown in Figure 2. The draft should 
be adjusted to -0.02 inches w.c. 

In the United States, the Beckett AF Burner may be 
equipped with Beckett's "

Inlet Air Shut-Off

" to increase 

efficiency. (Beckett Part No. AF/A 5861).

  

 

NOTE: USE OF THE INLET AIR SHUT-OFF 
COULD CAUSE POST COMBUSTION NOZZLE 
DRIP. 

 

 

 

 

 

 

 

 

11

Summary of Contents for POF1HD091AVFA

Page 1: ...Do not store or use gasoline or other flammable liquids or vapors in the vicinity of this or any other appliance ALL INSTALLATIONS MUST MEET ALL LOCAL PROVINCIAL STATE AND FEDERAL CODES WHICH MAY DIF...

Page 2: ...NER PRIMARY SAFETY CONTROL 6 18 COMBUSTION CHAMBER 6 19 CIRCULATING AIR BLOWER 7 19B CIRCULATING AIR BLOWER 7 20 MAINTENANCE AND SERVICE 8 21 OPERATING INSTRUCTIONS 8 22 ECM BLOWER MOTOR OPERATION 9 A...

Page 3: ...rdance with local codes Regulations prescribed in the National Codes and Local regulations take precedence over the general instructions provided on this installation manual When in doubt please consu...

Page 4: ...windows or where basement windows are well sealed a permanent opening communicating with a well ventilated attic or with the outdoors shall be provided using a duct if necessary The duct opening shall...

Page 5: ...similar device The power requirement for the POF1HD140AVFA and POF1HD091AVFA models is 120 VAC 1 60 Hz 12A Accessories requiring 120 VAC power sources such as electronic air cleaners and humidifier t...

Page 6: ...trace smoke spot on the Bacharach Scale BEFORE OPERATING THE FURNACE CHECK BURNER ALIGNMENT WITH COMBUSTION CHAMBER THE END CONE OF THE AIR TUBE MUST BE CENTRED TO THE ACCOMODATING RING PROVIDED IN TH...

Page 7: ...er sized duct systems may require a higher blower speed to obtain a reasonable system temperature rise Some older duct systems were not designed to provide static pressure They typically feature speci...

Page 8: ...ace or burner It is advisable to change the oil burner nozzle and oil filter on an annual basis The venting system should be cleaned and inspected for signs of deterioration Replace pitted or perforat...

Page 9: ...POUR OR WHEN THE COMBUSTION CHAMBER IS VERY HOT NEVER BURN GARBAGE OR PAPER IN THE FURNACE AND NEVER LEAVE PAPER OR RAGS AROUND THE UNIT Soft Stop At the end of the heating cycle the ECM variable spee...

Page 10: ...usgph F3 3 in POF1HD105AVFA 87 000 AF76BNHS 0 75 80 A 100 psig 0 75 usgph F3 3 in 1 Head is shielded by ceramic insulator 2 Low Firing Rate Baffle required when using a 0 50 gallon nozzle Bold models...

Page 11: ...16 inch Older instruction sheets specify 7 16 inch The current specification is 5 16 inch Distance ahead of nozzle 1 16 inch Z dimension the distance from the front of the end cone head to the face of...

Page 12: ...8 inches w c 0 5 inches w c POF1HD105AVFA POF1HD119AVFA POF1HD140AVFA 100 10 DD 1 2 HP ECM 7 7 70 F 500 700 1100 1525 600 1400 CFM RANGE Continuous Heating Cooling Furnace Model Blower Motor HP Motor...

Page 13: ...ions Inches Cabinet Plenum Openings Filter Return Furnace Model Width Depth Height Supply Side Bottom Flue Diameter Type Size Shipping Weight POF1HD140AVFA 22 30 3 4 58 20 x 20 14 x 22 14 x 22 6 Perma...

Page 14: ...ns Inches Cabinet Plenum Openings Filter Return Furnace Model Width Depth Height Supply Side Bottom Flue Diameter Type Size Shipping Weight POF1HD091AVFA 22 30 3 4 49 5 8 20 x 20 14 x 22 14 x 22 5 Per...

Page 15: ...F ON C 2 ON ON D 0 50 ON ON D 1 5 SW3 ADJUST SW4 DELAY DIP Switch Position CFM DIP Switch Position INPUT 1 2 POS 1 2 POS USGPH OFF OFF A 0 OFF OFF A 0 65 ON OFF B 15 ON OFF B N A OFF ON C 15 OFF ON C...

Page 16: ...equal to 400 CFM SW3 ADJUST Heating Mode Increase OR decrease temperature rise respectively Cooling Mode Increase OR decrease CFM respectively INPUT DIP Switch Position AC Size 1 2 POS USGPH 1 2 POS T...

Page 17: ...a basse vitesse si quipp e AL limite auxiliaire si quipp e REQUIRED FOR CANADIAN INSTALLATIONS BLOCKED VENT SAFETY L BVS RIELLO 40F BURNER br leur BECKETT AF BURNER br leur 4 1 2 3 OR BK WH VI N L 530...

Page 18: ...adjustments can be made by moving the dipswitch settings on the timer control board for fan off delay To check the operation of the limit switch shut off power to the furnace Temporarily remove the n...

Page 19: ...spark for 10 sec a Provides continuous spark after flame is sensed to assure that burner remains lit b Turns on LED diagnostic light c Starts carryover timer i Flame and call for heat are monitored I...

Page 20: ...present Thermostat calls for W The 24VAC input signal is passed to pin 2 of P1 and will drive the K1 relay that provides dedicated contacts to the T T input of the Oil Primary Control Thermostat calls...

Page 21: ...URNS TO IDLE STATE FLAME FLAME FLAME FLAME NO FLAME NO FLAME FLAME LOST FLAME LOST REMAINS IN IDLE STATE OIL PRIMARY CONTROL SEQUENCE of OPERATION LOCKOUT STATE OIL PRIMARY CONTROL Shuts off burner mo...

Page 22: ...sing the reset button The LED diagnostic light will flash the following code Table C 2 Cad Cell Resistance Flashes Resistance in Ohms 1 Less than 400 2 Between 400 800 3 Between 800 1600 4 Between 160...

Page 23: ...ad cell with new cad cell and recheck If indicator light does not turn off remove yellow lead wires from oil primary control and recheck If indicator light is still on replace the oil primary control...

Page 24: ...Step 7 6 Reset oil primary control by pushing in and releasing red reset button Indicator light continues to flash at 1 Hz rate Verify that the control is not in restricted mode See notes at end of th...

Page 25: ...ero each time a call for heat is successfully completed To reset from RESTRICTED MODE press and hold the reset button for 30 seconds When the LED flashes twice the device has reset NOTE Disable functi...

Page 26: ...aximum of 1500 in the presence of light Ensure that room light is not leaking into the cad cell compartment See diagnostic light section No fuel oil Check fuel oil supply Check that all hand operated...

Page 27: ...radiator Poor alignment between oil burner blast tube and fire pot Check alignment Blast tube should be centered with fire pot burner opening Oil burner head should be inch back from the inside surfac...

Page 28: ...y joints and seams Insulate ductwork if necessary FINAL CHECK OUT 3 Where the oil shut off valve from the oil storage tank is located ENSURE THAT ALL SAFETY DEVICES AND ELECTRICAL COMPONENTS HAVE BEEN...

Page 29: ...al No Date Installed Contractor Contact Address Postal Code Telephone No After Hours No FUEL SUPPLIER Fuel Oil Supplier Contact Telephone No After Hours No IF DIFFERENT FROM INSTALLATION CONTRACTOR Se...

Page 30: ...30...

Page 31: ...sket 2080175 15 Air Baffle 109007733 16 Insulation Retainer 20602 17 Radiator Clean out Cover 2 per unit 29162 17 18 18 Radiator Clean out Cover Gasket 2 per unit Clean out Gasket Retainer Clean out T...

Page 32: ...il Primary Combustion Control Genisys 240007858 Flame Retention Head F6 Nozzle 1 00 60 W 11961 14619329 Ref No Description Part No 35a Blower Assembly Direct Drive 3 Ton ECM Motor 109007723 Blower Hou...

Page 33: ...33...

Page 34: ...Tube Gasket 240006333 29161 29163 19 Filter Frame 16 X 25 18020 20 Filter Frame End Support 5592B2 21 Filter 16 X 25 X 1 Permanent 2180023 24 Control Box 29362 25 Upper Door Panel 30164L Logo Bezel 28...

Page 35: ...ECM 30146 109007271 Blower Housing and Wheel 100 10T DD POF1HD091AVFA 30626 Blower Motor 1 2 hp ECM Programmed 109007272 Motor Mounting Band TR6884B 17811 Motor Mount Arms 10 10 DD Blower 3 per unit 2...

Page 36: ...NOTES Nordyne Inc 8000 Phoenix Parkway O Fallon Missouri 63368 766B 0909...

Reviews: