background image

22

After the gas piping to the furnace is complete, all 
connections must be tested for gas leaks. This includes 
pipe connections at the main gas valve, emergency shutoff 
valve and fl exible gas connectors (if applicable). The soap 
and water solution can be applied on each joint or union 
using a small paintbrush. If any bubbling is observed, 
the connection is not sealed adequately and must be 
retightened. Repeat the tightening and soap check process 
until bubbling ceases.

IMPORTANT NOTE: When pressure testing gas supply 
lines at pressures greater than 1/2 psig (14 inch W.C.), 
the gas supply piping system must be disconnected 
from the furnace to prevent damage to the gas control 
valve. If the test pressure is less than or equal to 1/2 
psig (14 inch W.C.), close the manual shut-off valve.

High Altitude Application

The installation of this furnace at altitudes above 2,000 
feet must meet the requirements of the National Fuel Gas 
Code or local jurisdiction. In Canada, the requirements for 
high altitude are different and governed by CGA B149.1. 
Please consult your local code authority. 

 WARNING:

The reduction of input rating necessary for high 
altitude installation may only be accomplished 
with factory supplied orifi ces. Do not attempt to 
drill out orifi ces in the fi eld. Improperly drilled 
orifi ces may cause fi re, explosion, carbon 
monoxide poisoning, personal injury or death.

The furnaces are shipped from the factory with orifi ces 
and gas regulator settings for natural gas operation at sea 
level altitudes. At 2000 feet, the NFGC requires that this 
appliance be derated 4% for each 1000 feet of altitude. 
For example, the input needs to be reduced 8% at 2,000 
feet, 12% at 3,000 feet, etc. This deration is in reference 
to the input rate and gas heating value at sea level.

RISQUE D’INDENDIE OU D’EXPLOSION

Le non-respect des avertissements de 
sécurité pourrait d’entraîner des blessures 
graves, la mort ou des dommages matériels.

Ne jamais utiliser une fl amme nue por vérifi er la 
présence des fuites de gaz. Pour la vérifi cation 
de tous les joints, utiliser plutôt une solution 
savonneuse commerciale fabriquée spécifi quement 
pur la détection des fuites de gaz. Un incendie ou 
une explosion peut entraîner des dommages 
matériels, des blessures ou la mort.

 AVERTISSEMENT:

To derate the furnace requires knowing the heating value of 
the gas at the installation site. Heating values at particular 
job sites vary for two reasons:
1.  The chemical mixture of the gas varies from region 

to region and is expressed as the “sea level heating 
value”.

2.  The heating value varies by altitude. For this reason, 

particularly in high altitude areas, the local gas utility 
usually specifi es the heating value at the residence’s 
gas meter as the “local value”.

For added fl exibility, two tables have been provided for 
natural gas installations with high or low heating values at 
sea level. Tables 15 and 16 (page 39) contain the orifi ce 
sizes and manifold pressure to use at various altitudes. 
Table 15 (HIGH) is for natural gas installations with a 
heating value of more than 1,000 Btu per cubic foot and 
Table 16 (LOW) is for less than 1,000 Btu per cubic foot. 
To determine which table to use:

1.  Consult your local utility for the local heating value at 

your installation.

2.  From Table 14 (page 38), fi nd your local heating value 

as supplied by the utility company. Follow down the 
column and stop at your altitude level.

3.  If your sea level heating value is HIGH, use Table 15 

or if it’s LOW, use Table 16. See example.

Installation Example

Elevation:

 .................................................. 5,000 feet

Type of Gas:

 ........................................... Natural  Gas

Local Heating Value of Gas:

 .............................. 750

From Table 14, fi nd 750 and follow down the column, 
stop at the 5,000 feet row. The heating value listed is 
LOW. Table 16 will be used to determine orifi ce size and 
manifold pressure.

After changing the regulator pressure or changing the 
orifi ces, it is required that you measure the gas input rate. 
This may be accomplished in the usual way, by clocking 
the gas meter and using the local gas heating value. See 
Verifying & Adjusting the Input Rate section (page 28).

IMPORTANT NOTE: Observe the action of the burners 
to make sure there is no yellowing, lifting or fl ashback 
of the fl ame.

Summary of Contents for *TC

Page 1: ...llow the gas supplier s instructions If you cannot reach your gas supplier call the fire department WARNING RISQUE D INCENDIE OU D EXPLOSION Le non respect des avertissements de s curit pourrait entra...

Page 2: ...R REQUIREMENTS 14 Plenums Air Ducts 14 Supply Air Connections 15 Upflow Horizontal Furnaces 15 Downflow Furnaces 15 Return Air Connections 15 Upflow Horizontal Furnaces 15 Side Return Installations 15...

Page 3: ...l Cooling Heat Pump CFM Variable Speed 36 Gas Information 37 Table 11 Gas Flow Rates 37 Table 12 Gas Pipe Capacities 37 Table 13 High Altitude Deration Chart for Propane Gas 38 Table 14 Natural Gas He...

Page 4: ...may be used for temporary heating of buildings or structures under construction See the guidelines listed on pages 5 This furnace is not approved for installation in mobile homes Installing this furn...

Page 5: ...uous return temperature must not be below 60 F 15 C Occasionally a temporary return temperature of 55 F 12 C is acceptable However operation with a return temperature below 55 F 12 C is not allowed He...

Page 6: ...hes Back 0 Inches Allow 24 in minimum clearance for servicing Recommended clearance is 36 in TOP FRONT UPFLOW APPLICATIONS HORIZONTAL APPLICATIONS VENT TOP FRONT DOWNFLOW APPLICATIONS SIDE TOP BOTTOM...

Page 7: ...rit ci dessus rouvrir les portes et les fen tres et remettre les ventilateurs d vacuation les registres de foyers et tout autre appareil fonctionnant au gaz leur tat de fonctionnement initial CARBON M...

Page 8: ...icted If the furnace is operated without adequate air for combustion the flame roll out switch will open turning off the gas supply to the burners NOTE This safety device is a manually reset switch DO...

Page 9: ...freely exchange with the outdoors Figure 2 Outdoor Air Using Vertical Ducts If combustion air is taken from outdoors through vertical ducts the openings and ducts must have a minimum free area of one...

Page 10: ...G Upon completion of the furnace installation carefully inspect the entire flue system both inside and outside the furnace to assure it is properly sealed Leaks in the flue system can result in seriou...

Page 11: ...aterial Vent and combustion air pipe and fittings must be one of the following materials in the list and must conform to the indicated ANSI ASTM standards Cement must conform to ASTM Standard D2564 fo...

Page 12: ...install a coupling 1 Slide the rubber coupling over the end of the pipe that is attached to the furnace and secure it with one of the hose clamps 2 Slide the other end of the rubber coupling onto the...

Page 13: ...gths noted in Table 2 page 11 For Canadian installations please refer to the Canadian Installation Code CAN CGA B149 1 or 2 and or local codes For extremely cold climates or for conditions of short fu...

Page 14: ...QUIREMENTS WARNING Do not allow combustion products to enter the circulating air supply Failure to prevent the circulation of combustion products into the living space can create potentially hazardous...

Page 15: ...rn air NOTE Do not use the back of the furnace for return air Side Return Installations To attach the return air duct to the left or right side of the furnace punchoutthefourknockouts Figure29 fromthe...

Page 16: ...ecifications Upflow Installation WARNING The furnace must not be installed directly on carpeting tile oranycombustiblematerialother than wood flooring Side Return Air Inlet TCseriesgasfurnacesareshipp...

Page 17: ...inducer assembly 2 See Figure 14 page 18 2 Remove the inducer assembly ground wire 3 from the blower deck 4 or door 3 Removefourscrews 5 securingtheinducerassembly 2 to the header box 6 4 Remove drain...

Page 18: ...have two pairs of switches One set is connected to the static tap on the inducer assembly and the other to the collector box Downflow TL furnaces require only one pair of switches to be connected to...

Page 19: ...r grommet should be installed in the 1 5 8 hole prior to running the gas pipe into the cabinet No sealants are required The 3 4 rubber grommet is used if venting out the left side of the cabinet and t...

Page 20: ...eral rules In some cases the lowest point in the vent system is where it connects to the inducer Options 6 8 In this case one drain at this location is sufficient If the vent exits the furnace horizon...

Page 21: ...comply with the latest edition of the National Fuel Gas Code ANSI Z223 1 or CAN CGA B149 1 or 2 Installation Codes IMPORTANT NOTES Some local regulations require the installation of a manual main shu...

Page 22: ...des fuites de gaz Pour la v rification de tous les joints utiliser plut t une solution savonneusecommercialefabriqu esp cifiquement pur la d tection des fuites de gaz Un incendie ou une explosion peut...

Page 23: ...Shut Off Valve to be 4 to 5 feet above floor NOTE B Inducer assembly omitted for clarity of pipe installation Figure 22 Typical Gas Connections 6 4 2 UPFLOW MODELS DOWNFLOW MODELS 1 See Note B See Not...

Page 24: ...to LP Propane gas must be performed by qualified service personnel using a factory supplied conversion kit Failure to use the properconversionkitcancausefire explosion propertydamage carbonmonoxidepo...

Page 25: ...be controleed by a 24 VAC thermostat The thermostat s wiring must comply with the current provisions of the NEC ANSI NFPA 70 and with applicable local codes having jurisdiction NORDYNE no longer supp...

Page 26: ...it s Y C terminals Single Stage AC Two Stage Thermostat This option uses the full two stage heating capability of the furnace with a single stage outdoor unit See Figure 22 Connect the thermostat s W1...

Page 27: ...7 2 If using a separate humidistat connect the DHUM R terminals on the humidistat to the DHUM R terminals on the motor control board In this option the DHUM output of the humidistat must be set to be...

Page 28: ...s until all of the checks in the previous steps have been completed 1 Set the thermostat to the lowest setting 2 Turn off all electrical power to the furnace 3 Follow the Operating Instructions on the...

Page 29: ...lowers should continue to run when the limit switch opens 1 Check the blower door for secure mounting and that there is power to the furnace 2 Block the return airflow to the furnace by installing a c...

Page 30: ...tinues to run the fan for a period of 60 seconds Fan Mode When the thermostat energizes the G terminal for continuous fan without calling for heat or cooling the indoor fan is energized on the selecte...

Page 31: ...gas control switch to the OFF position 5 Disconnect the wires from the gas valve igniter flame sensor and flame rollout switch CAUTION To prevent damage to the unit or internal components it is recomm...

Page 32: ...alified service technician to identify and repair the problem If the furnace still doesn t operate check the Flame Roll out Switches Figure 41 and reset if necessary If the furnace operates when the F...

Page 33: ...s 1 5 8 T stat 7 8 18 1 2 Front Brace LEFT SIDE RIGHT SIDE Electric 7 8 25 1 2 22 1 2 Gas 1 5 8 Vent pipe 3 Cond 1 1 16 B 19 FLANGES TOP VIEW 3 7 1 2 Flue C BOTTOM VIEW Electric 7 8 Vent pipe 3 Cond 1...

Page 34: ...5 0 0 1 0 1 525 58 1 450 61 1 375 64 1 300 68 1 225 72 1 150 76 1 075 82 1 000 88 1 0 1 0 1 620 54 1 540 57 1 465 60 1 390 63 1 315 67 1 240 71 1 165 76 1 090 81 0 1 1 0 1 695 52 1 620 54 1 545 57 1 4...

Page 35: ...345 52 1 345 65 1 0 0 1 460 48 1 460 60 1 0 1 1 575 45 1 575 56 1 1 0 1 690 42 1 690 52 1 1 1 1 805 39 1 805 49 D CABINET Switch Settings for Heat 0 OFF 1 ON TC TL 120D VD Input BTU 120 000 1 2 3 4 CF...

Page 36: ...7 8 LOW HIGH 0 0 0 0 705 1 025 2 5 TON 0 0 0 1 750 1 090 3 TON 0 0 1 0 795 1 155 0 0 1 1 840 1 220 0 1 0 0 885 1 285 3 5 TON 0 1 0 1 930 1 350 0 1 1 0 975 1 415 4 TON 0 1 1 1 1 020 1 480 1 0 0 0 1 065...

Page 37: ...ER REVOLUTION OF GAS METER 1 5 10 10 360 1 800 3 600 12 300 1 500 3 000 14 257 1 286 2 571 16 225 1 125 2 250 18 200 1 000 2 000 20 180 900 1 800 22 164 818 1 636 24 150 750 1 500 26 138 692 1 385 28...

Page 38: ...56 56 56 56 ORIFICE SIZE 4 2 9 0 4 2 9 0 4 2 9 0 4 2 9 0 MANIFOLD PRESSURE 8 000 to 10 000 FT 56 56 56 56 ORIFICE SIZE 4 2 8 5 4 2 8 5 4 2 8 5 4 2 8 5 MANIFOLD PRESSURE LOCAL HEATING VALUES FOR NATUR...

Page 39: ...PRESSURE 9 000 to 9 999 FT 48 48 48 48 ORIFICE SIZE 1 7 2 8 1 7 2 8 1 7 2 8 1 7 2 8 MANIFOLD PRESSURE Table 16 High Altitude Deration Chart for Natural Gas Low heating Value NATURAL GAS with LOW HEAT...

Page 40: ..._IN H_OUT L2 OUT L2 IN L1 IN L1 OUT Y1_OUT Y Y2_OUT W_OUT C EXPANSION PORT R RED GREEN NOT FOR FIELD USE CONNECTION TO FURNACE CONTROL BOARD CONNECTION TO IQ THERMOSTAT IF APPLICABLE MOTOR WIRING HARN...

Page 41: ...REEN BROWN BROWN YELLOW VIOLET VIOLET VIOLET ORANGE ORANGE ORANGE VENT LIMIT ON SELECT MODELS BLACK 120V WHITE NEUTRAL GROUND 710916 CONDENSATE ON SELECT MODELS Refer to the Installation Instructions...

Page 42: ...END 0409 LOW VOLTAGE HIGH VOLTAGE BLUE BLUE BLUE BLUE BLACK BLACK 120V WHITE BLACK BLACK BLACK BLACK BLACK BLACK WHITE WHITE NEUTRAL BLACK WHITE WHITE RED RED GREEN GROUND GREEN BROWN BROWN YELLOW VIO...

Page 43: ...AL GROUND CONDENSATE ON SELECT MODELS BLACK VIOLET For 80 and 90 2 Stage Variable Speed Upflow Furnaces WIRING DIAGRAM 7109180 FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE Refer to the Installation In...

Page 44: ...t Flash Off Low Flame Sensor Signal Flame Present Diagnostic Description FAULT CONDITIONS Diagnostic Description Yellow LED Continuous Flash On Alternating Flash Motor Fault On Off 0409 FLAME ROLL OUT...

Page 45: ...ance 6 inches 15cm for appliances 10 000 Btuh 3kW 6 inches 15cm for appliances 10 000 Btuh 3kW 4 ft 1 2m below or to side of opening 1 ft 300mm above opening 12 inches 30cm for appliances 10 000 Btuh...

Page 46: ...5 ft Intervals Upward Pitch 1 4 per foot Flue Pipe First support placed as close to furnace connection as possible Wall Normal Snow Level COMBUSTION AIR 90 Elbow both ends Seal Caulk Around Pipes at B...

Page 47: ...o length to resemble illustration NOTES Header box drain tubing is routed thru the blower deck and side of cabinet Header box drain tubing is routed thru the blower deck and side of cabinet Drain Line...

Page 48: ...TION AIR FLUE PIPE AIR FLOW 1 2 3 4 5 6 7 8 Rubber Grommet COMBUSTION AIR See VIEW C for drain line positions See VIEW C for drain line positions See VIEW D for drain line positions Plug Plug See VIEW...

Page 49: ...W E for drain line positions PVC TEE Reducer 1 2 x 1 2 Hose Barb 1 All drain lines must be trapped with J Trap or field supplied loop 2 Drain line traps may be positioned inside or outside the cabinet...

Page 50: ...Switches Inducer Motor Control Box Inducer Limit Switch Main Air Limit Switch AIR AIR FLOW FLOW 1 2 3 4 5 6 7 8 Burner Assembly Flame Sensor Roll Out Switch Finish Flange Blower Assembly behind blowe...

Page 51: ...51...

Page 52: ...NAME CITY STATE INSTALLATION ADDRESS CITY STATE UNIT MODEL UNIT SERIAL Minimum clearances per Table 1 page 6 YES NO Has the owner s information been reviewed with the home owner YES NO Has the literat...

Reviews: