background image

29

1.  Place thermometers in the return and supply air 

stream as close to the furnace as possible. To avoid 
false readings, the thermometer on the supply air side 
must be shielded from direct radiation from the heat 
exchanger.

2.  Adjust all registers and duct dampers to the desired 

position and run the furnace for 10 to 15 minutes in 
high fi re before taking any temperature readings. The 
temperature rise is the difference between the supply 
and return air temperatures.

For typical duct systems, the temperature rise will fall 
within the limits specifi ed on the rating plate with the 
blower speed at the factory recommended setting. If 
the measured temperature rise is outside the specifi ed 
limits, it may be necessary to change the speed of the 
blower. 

NOTE:

 Lowering the blower speed increases the 

temperature rise and a higher blower speed will decrease 
the temperature rise.

The furnace is equipped with a multi-speed motor. Heating 
and cooling speed selection is made by moving the 
switches on the integrated control located in the furnace.

Verifying Burner Operation

 CAUTION:

The door over the burners may only be open 
for inspection purposes only. The door must be 
installed during unattended operation.

1.  Remove the burner compartment door.

2.  Set the thermostat above room temperature and 

observe the ignition sequence. The burner fl ame should 
carry over immediately between all burners without 
lifting off, curling, or fl oating. The fl ames should be 
blue, without yellow tips.

3.  After validating flame characteristics, change 

thermostat setting to below room temperature.

4.  Verify burner fl ame is completely extinguished.

5.  Replace the burner compartment door.

HI Input 

Adjusting Screw

Lo Input 
Adjusting Screw

Figure 28. HI & LO Input Adjusting Screws

Verifying Operation of the Supply Air Limit 
Switch

A properly functioning limit switch should turn off the 
gas valve when the return is blocked (time depends on 
how well the return air is blocked). The circulating air and 
combustion blowers should continue to run when the limit 
switch opens.
1.  Check the blower door for secure mounting and that 

there is power to the furnace.

2.  Block the return airfl ow to the furnace by installing a 

close-off plate in place of or upstream of the fi lter(s).

3.  Set the thermostat above room temperature and 

observe the Operating Sequence.

4.  Remove the close-off immediately after the limit switch 

opens. If the furnace continues to operate with no 
return air, set the thermostat below room temperature, 
shut off the power to the furnace, and replace the limit 
switch.

OPERATING SEQUENCE

The operating sequences for the heating, cooling, and fan 
modes are described below. Refer to the fi eld and furnace 
wiring diagrams: (Figure 23, page 25), (Figures 24 - 26, 
page 26), & (Figures 33 - 36, pages 41 - 44).

Heating Cycle

1.  The thermostat calls for heat by energizing the 

W1 

terminal with 24VAC.

2.  The control checks to see the pressure switch is open. 

If the switch is closed, the furnace will shut down for 
5 minutes before retrying

3.   If the pressure switch is open, the control energizes 

the inducer motor and waits for the pressure switch 
to close. The pressure switch must close within 12 
seconds.

4.  The control runs the inducer for a 30 second pre-purge 

time.

5.  The control energizes the igniter output for the 

appropriate adaptive warm-up time limit.

6.  The furnace always ignites the burners in 

high

 fi re. If 

the call for heat is for 

low

 rate, the furnace will move 

down to 

low

 fi re after the fl ames stabilize.

7.  If the fl ame is proved and ignites the gas, the control 

de-energizes the igniter. The gas valve and inducer 
remains energized. The control goes to blower on 
delay.

8.  The control energizes the blower on the selected 

HEAT speed 30 seconds after the gas valve opened. 
The gas valve and inducer remain energized.

9.  If there is a call for 

high

 fi re, the gas valve moves 

to the 

high

 fi re position and the blower speeds are 

increased. The furnace will remain in high fi re until 
the demand for heat is satisfi ed.

10. If autostaging is enabled (single stage thermostat) the 

demand for heat has lasted more than the selected 
time, the furnace automatically moves up to 

high

 fi re. 

Autostage times are either 

SHORT

 (8 minutes), 

LONG

 

Summary of Contents for *TC

Page 1: ...llow the gas supplier s instructions If you cannot reach your gas supplier call the fire department WARNING RISQUE D INCENDIE OU D EXPLOSION Le non respect des avertissements de s curit pourrait entra...

Page 2: ...R REQUIREMENTS 14 Plenums Air Ducts 14 Supply Air Connections 15 Upflow Horizontal Furnaces 15 Downflow Furnaces 15 Return Air Connections 15 Upflow Horizontal Furnaces 15 Side Return Installations 15...

Page 3: ...l Cooling Heat Pump CFM Variable Speed 36 Gas Information 37 Table 11 Gas Flow Rates 37 Table 12 Gas Pipe Capacities 37 Table 13 High Altitude Deration Chart for Propane Gas 38 Table 14 Natural Gas He...

Page 4: ...may be used for temporary heating of buildings or structures under construction See the guidelines listed on pages 5 This furnace is not approved for installation in mobile homes Installing this furn...

Page 5: ...uous return temperature must not be below 60 F 15 C Occasionally a temporary return temperature of 55 F 12 C is acceptable However operation with a return temperature below 55 F 12 C is not allowed He...

Page 6: ...hes Back 0 Inches Allow 24 in minimum clearance for servicing Recommended clearance is 36 in TOP FRONT UPFLOW APPLICATIONS HORIZONTAL APPLICATIONS VENT TOP FRONT DOWNFLOW APPLICATIONS SIDE TOP BOTTOM...

Page 7: ...rit ci dessus rouvrir les portes et les fen tres et remettre les ventilateurs d vacuation les registres de foyers et tout autre appareil fonctionnant au gaz leur tat de fonctionnement initial CARBON M...

Page 8: ...icted If the furnace is operated without adequate air for combustion the flame roll out switch will open turning off the gas supply to the burners NOTE This safety device is a manually reset switch DO...

Page 9: ...freely exchange with the outdoors Figure 2 Outdoor Air Using Vertical Ducts If combustion air is taken from outdoors through vertical ducts the openings and ducts must have a minimum free area of one...

Page 10: ...G Upon completion of the furnace installation carefully inspect the entire flue system both inside and outside the furnace to assure it is properly sealed Leaks in the flue system can result in seriou...

Page 11: ...aterial Vent and combustion air pipe and fittings must be one of the following materials in the list and must conform to the indicated ANSI ASTM standards Cement must conform to ASTM Standard D2564 fo...

Page 12: ...install a coupling 1 Slide the rubber coupling over the end of the pipe that is attached to the furnace and secure it with one of the hose clamps 2 Slide the other end of the rubber coupling onto the...

Page 13: ...gths noted in Table 2 page 11 For Canadian installations please refer to the Canadian Installation Code CAN CGA B149 1 or 2 and or local codes For extremely cold climates or for conditions of short fu...

Page 14: ...QUIREMENTS WARNING Do not allow combustion products to enter the circulating air supply Failure to prevent the circulation of combustion products into the living space can create potentially hazardous...

Page 15: ...rn air NOTE Do not use the back of the furnace for return air Side Return Installations To attach the return air duct to the left or right side of the furnace punchoutthefourknockouts Figure29 fromthe...

Page 16: ...ecifications Upflow Installation WARNING The furnace must not be installed directly on carpeting tile oranycombustiblematerialother than wood flooring Side Return Air Inlet TCseriesgasfurnacesareshipp...

Page 17: ...inducer assembly 2 See Figure 14 page 18 2 Remove the inducer assembly ground wire 3 from the blower deck 4 or door 3 Removefourscrews 5 securingtheinducerassembly 2 to the header box 6 4 Remove drain...

Page 18: ...have two pairs of switches One set is connected to the static tap on the inducer assembly and the other to the collector box Downflow TL furnaces require only one pair of switches to be connected to...

Page 19: ...r grommet should be installed in the 1 5 8 hole prior to running the gas pipe into the cabinet No sealants are required The 3 4 rubber grommet is used if venting out the left side of the cabinet and t...

Page 20: ...eral rules In some cases the lowest point in the vent system is where it connects to the inducer Options 6 8 In this case one drain at this location is sufficient If the vent exits the furnace horizon...

Page 21: ...comply with the latest edition of the National Fuel Gas Code ANSI Z223 1 or CAN CGA B149 1 or 2 Installation Codes IMPORTANT NOTES Some local regulations require the installation of a manual main shu...

Page 22: ...des fuites de gaz Pour la v rification de tous les joints utiliser plut t une solution savonneusecommercialefabriqu esp cifiquement pur la d tection des fuites de gaz Un incendie ou une explosion peut...

Page 23: ...Shut Off Valve to be 4 to 5 feet above floor NOTE B Inducer assembly omitted for clarity of pipe installation Figure 22 Typical Gas Connections 6 4 2 UPFLOW MODELS DOWNFLOW MODELS 1 See Note B See Not...

Page 24: ...to LP Propane gas must be performed by qualified service personnel using a factory supplied conversion kit Failure to use the properconversionkitcancausefire explosion propertydamage carbonmonoxidepo...

Page 25: ...be controleed by a 24 VAC thermostat The thermostat s wiring must comply with the current provisions of the NEC ANSI NFPA 70 and with applicable local codes having jurisdiction NORDYNE no longer supp...

Page 26: ...it s Y C terminals Single Stage AC Two Stage Thermostat This option uses the full two stage heating capability of the furnace with a single stage outdoor unit See Figure 22 Connect the thermostat s W1...

Page 27: ...7 2 If using a separate humidistat connect the DHUM R terminals on the humidistat to the DHUM R terminals on the motor control board In this option the DHUM output of the humidistat must be set to be...

Page 28: ...s until all of the checks in the previous steps have been completed 1 Set the thermostat to the lowest setting 2 Turn off all electrical power to the furnace 3 Follow the Operating Instructions on the...

Page 29: ...lowers should continue to run when the limit switch opens 1 Check the blower door for secure mounting and that there is power to the furnace 2 Block the return airflow to the furnace by installing a c...

Page 30: ...tinues to run the fan for a period of 60 seconds Fan Mode When the thermostat energizes the G terminal for continuous fan without calling for heat or cooling the indoor fan is energized on the selecte...

Page 31: ...gas control switch to the OFF position 5 Disconnect the wires from the gas valve igniter flame sensor and flame rollout switch CAUTION To prevent damage to the unit or internal components it is recomm...

Page 32: ...alified service technician to identify and repair the problem If the furnace still doesn t operate check the Flame Roll out Switches Figure 41 and reset if necessary If the furnace operates when the F...

Page 33: ...s 1 5 8 T stat 7 8 18 1 2 Front Brace LEFT SIDE RIGHT SIDE Electric 7 8 25 1 2 22 1 2 Gas 1 5 8 Vent pipe 3 Cond 1 1 16 B 19 FLANGES TOP VIEW 3 7 1 2 Flue C BOTTOM VIEW Electric 7 8 Vent pipe 3 Cond 1...

Page 34: ...5 0 0 1 0 1 525 58 1 450 61 1 375 64 1 300 68 1 225 72 1 150 76 1 075 82 1 000 88 1 0 1 0 1 620 54 1 540 57 1 465 60 1 390 63 1 315 67 1 240 71 1 165 76 1 090 81 0 1 1 0 1 695 52 1 620 54 1 545 57 1 4...

Page 35: ...345 52 1 345 65 1 0 0 1 460 48 1 460 60 1 0 1 1 575 45 1 575 56 1 1 0 1 690 42 1 690 52 1 1 1 1 805 39 1 805 49 D CABINET Switch Settings for Heat 0 OFF 1 ON TC TL 120D VD Input BTU 120 000 1 2 3 4 CF...

Page 36: ...7 8 LOW HIGH 0 0 0 0 705 1 025 2 5 TON 0 0 0 1 750 1 090 3 TON 0 0 1 0 795 1 155 0 0 1 1 840 1 220 0 1 0 0 885 1 285 3 5 TON 0 1 0 1 930 1 350 0 1 1 0 975 1 415 4 TON 0 1 1 1 1 020 1 480 1 0 0 0 1 065...

Page 37: ...ER REVOLUTION OF GAS METER 1 5 10 10 360 1 800 3 600 12 300 1 500 3 000 14 257 1 286 2 571 16 225 1 125 2 250 18 200 1 000 2 000 20 180 900 1 800 22 164 818 1 636 24 150 750 1 500 26 138 692 1 385 28...

Page 38: ...56 56 56 56 ORIFICE SIZE 4 2 9 0 4 2 9 0 4 2 9 0 4 2 9 0 MANIFOLD PRESSURE 8 000 to 10 000 FT 56 56 56 56 ORIFICE SIZE 4 2 8 5 4 2 8 5 4 2 8 5 4 2 8 5 MANIFOLD PRESSURE LOCAL HEATING VALUES FOR NATUR...

Page 39: ...PRESSURE 9 000 to 9 999 FT 48 48 48 48 ORIFICE SIZE 1 7 2 8 1 7 2 8 1 7 2 8 1 7 2 8 MANIFOLD PRESSURE Table 16 High Altitude Deration Chart for Natural Gas Low heating Value NATURAL GAS with LOW HEAT...

Page 40: ..._IN H_OUT L2 OUT L2 IN L1 IN L1 OUT Y1_OUT Y Y2_OUT W_OUT C EXPANSION PORT R RED GREEN NOT FOR FIELD USE CONNECTION TO FURNACE CONTROL BOARD CONNECTION TO IQ THERMOSTAT IF APPLICABLE MOTOR WIRING HARN...

Page 41: ...REEN BROWN BROWN YELLOW VIOLET VIOLET VIOLET ORANGE ORANGE ORANGE VENT LIMIT ON SELECT MODELS BLACK 120V WHITE NEUTRAL GROUND 710916 CONDENSATE ON SELECT MODELS Refer to the Installation Instructions...

Page 42: ...END 0409 LOW VOLTAGE HIGH VOLTAGE BLUE BLUE BLUE BLUE BLACK BLACK 120V WHITE BLACK BLACK BLACK BLACK BLACK BLACK WHITE WHITE NEUTRAL BLACK WHITE WHITE RED RED GREEN GROUND GREEN BROWN BROWN YELLOW VIO...

Page 43: ...AL GROUND CONDENSATE ON SELECT MODELS BLACK VIOLET For 80 and 90 2 Stage Variable Speed Upflow Furnaces WIRING DIAGRAM 7109180 FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE Refer to the Installation In...

Page 44: ...t Flash Off Low Flame Sensor Signal Flame Present Diagnostic Description FAULT CONDITIONS Diagnostic Description Yellow LED Continuous Flash On Alternating Flash Motor Fault On Off 0409 FLAME ROLL OUT...

Page 45: ...ance 6 inches 15cm for appliances 10 000 Btuh 3kW 6 inches 15cm for appliances 10 000 Btuh 3kW 4 ft 1 2m below or to side of opening 1 ft 300mm above opening 12 inches 30cm for appliances 10 000 Btuh...

Page 46: ...5 ft Intervals Upward Pitch 1 4 per foot Flue Pipe First support placed as close to furnace connection as possible Wall Normal Snow Level COMBUSTION AIR 90 Elbow both ends Seal Caulk Around Pipes at B...

Page 47: ...o length to resemble illustration NOTES Header box drain tubing is routed thru the blower deck and side of cabinet Header box drain tubing is routed thru the blower deck and side of cabinet Drain Line...

Page 48: ...TION AIR FLUE PIPE AIR FLOW 1 2 3 4 5 6 7 8 Rubber Grommet COMBUSTION AIR See VIEW C for drain line positions See VIEW C for drain line positions See VIEW D for drain line positions Plug Plug See VIEW...

Page 49: ...W E for drain line positions PVC TEE Reducer 1 2 x 1 2 Hose Barb 1 All drain lines must be trapped with J Trap or field supplied loop 2 Drain line traps may be positioned inside or outside the cabinet...

Page 50: ...Switches Inducer Motor Control Box Inducer Limit Switch Main Air Limit Switch AIR AIR FLOW FLOW 1 2 3 4 5 6 7 8 Burner Assembly Flame Sensor Roll Out Switch Finish Flange Blower Assembly behind blowe...

Page 51: ...51...

Page 52: ...NAME CITY STATE INSTALLATION ADDRESS CITY STATE UNIT MODEL UNIT SERIAL Minimum clearances per Table 1 page 6 YES NO Has the owner s information been reviewed with the home owner YES NO Has the literat...

Reviews: