Chapter 4
Start-up and operation
27
"BACNET" area
BACnet > Settings
On this configuration page you set the following settings, for instance:
Router mode, password for DCC/RD and network security (DDC/RD - device
communication control/reinitialize device)
Router mode:
The MBS UBR routers can communicate both via Ethernet (BACnet IP) and
via a two-wire RS485 connection (BACnet MS/TP). Whereas the UBR-01
router has one Ethernet and one RS485 (MS/TP) interface, the UBR-02 has
two of each of these interfaces.
The router mode drop-down list is used to set the router's operating mode:
• BACnet IP only: BACnet IP communication
The data link for BACnet IP is preset.
• BACnet MS/TP only: BACnet MS/TP communication only
A data link for BACnet MS/TP is preset.
• BACnet IP and MS/TP: BACnet IP + BACnet MS/TP communication
Both a data link for BACnet IP and a data link for BACnet MS/TP are preset.
• "Non default operation":
The user can freely configure the number and type of data links.