Chapter 4
Start-up and operation
50
Help > Process Information (System)
Overview of the processes started on the router
Exiting the web interface
Click on the
door
symbol at the top right and confirm the logout dialogue.
The MBS UBR router is thus configured for the BACnet network.
Reset – Restoring factory settings
To reset the MBS UBR to the factory settings, press and hold the reset button
for more than 15 s.
The following functions are also performed depending on how long the reset
button is held:
• Press and hold for between 1 and 5 s (red flashing phase of the reset LED)
to trigger a restart.
• Hold the reset button for up to 10 s (green flashing phase of the reset LED)
to temporarily change the IP address to the default address 169.254.0.1.
• Hold the reset button for up to 15 s (green flashing phase of the reset
LED) to temporarily start the server on the UBR, in addition to the previous
address change.