7
STEP 3 - Testing
a.
Open the inlet valve (X) and the outlet
valve (Y). Check for any leakage.
If there are any leaky connections, close
the inlet and outlet valves and correct
the problem.
b.
Turn the boiler’s electric power on and fill
it to the manufacturer's recommended
normal water level by depressing the red
manual feed button (Z) on the water
feeder.
X
Y
FEE
D
INDIC
ATOR
MANUA
L
FEED
Z
B
c.
Check the water feeder (B) operation by performing the following steps:
1.
Slowly drain water from the boiler.
2.
The burner should turn off when the water level drops below the cut-off level of the LWCO, which
will activate the water feeder's delay feed cycle.
3.
Feeder should turn on to feed water to boiler after delay period has expired.
NOTE:
Delay period is determined by position of selector.
Unit is shipped
with switch in Position 2.
Refer to chart on page 8 for alternate settings.
4.
Feeder will be deactivated when water level is restored to level as determined by LWCO.
NOTE:
McDonnell & Miller Series
PSE
LWCO's have a
30
second DOM (Delay on Make) to
restore
water level in boiler to an appropriate level without overfeeding.
Consult other
manufacturer's LWCO
installation literature
for DOM times.
5.
Repeat steps to ensure feeder is operating satisfactorily.
If burner does not turn off when water level falls below level of LWCO, turn
off power to boiler and check operation of LWCO.
!
WARNING
Multi-Color LED
Upon receiving a signal from LWCO (power to terminal ‘W’) the multi-color LED will indicate the status
of the feeder.
Flashing Green Dwell Period -Solenoid Closed
————
Solid Green
Feed Period -Solenoid Open
————
Flashing Red
Invalid Feed Cycle Switch Setting
Only one of the switches should be in the ‘ON’ position.
Solid Red
Dwell/Feed Cycle Exceeded
Check operation of LWCO.
LED
Condition
Solution
Summary of Contents for Uni-Match WFE-24
Page 1: ...INSTRUCTION MANUAL MM 323G 211163...
Page 6: ......