background image

4

3.  Check proper connection and support of compressed air 

lines to the dryer; check bypass valve system, if installed.

4.  SLOWLY pressurize the dryer. The outlet valves of the dryer 

should be closed to prevent flow through the dryer.

5.  Turn on the main electrical power to the dryer.
6.  Ensure adequate ventilation for air cooled dryers.
7.  Do not operate the dryer with any dryer cabinet panel 

removed.

 

 

 

Cooling air flow across the condenser may be reduced 

if a dryer panel has been removed while the dryer 

is operating, resulting in the dryer not functioning 

properly and/or dryer failure. Failure to follow these 

instructions may result in a non-warrantable dryer 

failure.

 

To start dryer

IMPORTANT: Energize dryer for 24 hours prior to starting 

refrigerator compressor! Failure to follow these instruc-

tions may result in a non-warrantable compressor failure. 

1.  Turn the power switch to ON. The refrigerant compressor 

will turn on.

2.  Allow the dryer to run 15 minutes. Confirm that the tem-

perature indicators are in the green zone.

3.  SLOWLY open the dryer outlet valves permitting flow 

through the dryer.

4.  Confirm that condensate is discharging from the drain valve 

by pressing the “Push-to Test” button (on drain).

5.  Confirm that the inlet air temperature, pressure and airflow 

to the dryer meet the specified requirements (see Engi-

neering Data section).

6.  Confirm that the condensate lines from the drain valve 

discharge into a collection tank or an environmentally ap-

proved disposal system.

The FLEX dryer is designed to run and stop repeatedly. Let the 

FLEX dryer operate even when the demand for compressed air 

is interrupted; the FLEX dryer will not freeze up.

Shutdown

When the dryer must be shutdown for maintenance or other 

reasons, use the following procedure.
1.  Turn off the power switch.
2.  Disconnect the main power supply.
3.  Lock out and tag the power supply in accordance with OSHA 

requirements.

If mechanical repairs are to be made or service is performed, 

vent the internal pressure of the dryer to atmospheric pressure. 

Restart the dryer according to the start-up instructions.

 

Disconnect power supply and depressurize dryer before 

servicing. Dismantling or working on any component of 

the compressed air system under pressure may cause 

equipment failure and serious personal injury.

Operation

1.  To start the dryer, turn on the (a) dryer on/off switch.
2.  When the refrigeration compressor and the condenser fan 

are running, the cold refrigerant in the chiller (evaporator) 

cools the liquid Phase Change Material (PCM) which gradu-

ally solidifies. During this time, the refrigeration compressor 

running light (c) is illuminated on the LCD window. 

3.  Energy saving percent (e) is displayed on the LCD window 

by calculating dryer running time and refrigeration com-

pressor operating time.

4.  Pressure dew point level (f) is displayed on the LCD window. 
5.  Dryer running time (h) is displayed on the LCD window while 

the power is on. Pressing (g) will toggle the compressor 

running time where the dryer running time (h) was dis-

played. When the (j) button is pressed and held for over 10 

seconds, dryer and compressor running times are erased 

and displayed “0 H”. (timer reset)

6.  Check the dryer operating status when the alarm light (b) 

blinks according to Table 1 below.

No. Alarm display

Description

1

lamp (b) blinks rapidly 

and “E01” is displayed 

on (h)

Ref. compressor has 

no signal

2

lamp (b) blinks and 

“E02” is displayed on 

(h)

Temperature sensor 

signal open

3

lamp (b) light is on

“E03” is displayed on 

(h)

Drain valve has some 

trouble

Table 1. Alarm display mode

START-UP/OPERATION

Never use the disconnect switch to shut down the dryer 

for an extended period of time (except for repair). Failure 

to follow these instructions may result in a non-warrant-

able compressor failure.
IMPORTANT:  Energize dryer for 24 hours prior to starting 

refrigerator compressor! Failure to follow these instruc-

tions may result in a non-warrantable compressor failure.

Follow the procedure below to start your dryer. Failure to follow 

the prescribed start-up procedure will invalidate the warranty. 

If problems arise during start-up, call your distributor. Before 

repair, vent the internal pressure of the dryer to atmospheric 

pressure.

Before starting dryer 

Drain connections must be made before the dryer can be op-

erated. The dryers are fully automatic and require no auxiliary 

controls.
1.  Turn the dryer on/off switch to off.
2.  Check that the main electrical supply voltage matches the 

voltage specified on the dryer data plate.

MCGUIRE AIR COMPRESSORS INC

1-888-229-9999

MCGUIRE AIR COMPRESSORS INC

1-888-229-9999

Summary of Contents for SPXFLOW FLEX DFX 12.5

Page 1: ...FX 12 5 DFX 15 1 DFX 20 1 FOR M NO 7473076 R EVI S ION 08 2019 R EAD AN D U N D E R STAN D TH I S MAN UAL PR IOR TO OPE RATI NG OR S E RVICI NG TH I S PROD UCT I N STR UCTION MAN UAL MCGUIRE AIR COMPR...

Page 2: ...7 DRAWINGS General Arrangement Model DFX 8 1 8 Models DFX 12 5 DFX 15 1 9 Model DFX 20 1 10 Electrical Schematic 11 Air and Refrigerant Flow Schematic Model DFX 8 1 12 Models DFX 12 5 DFX 15 1 DFX 20...

Page 3: ...ity have the potential to cause personal injury or equipment damage Before doing any work on the dryer be sure the electrical supply has been locked and tagged and the internal pressure of the dryer h...

Page 4: ...ittings must be rated for the maximum operating pressure given on the dryer data plate and must be in accor dance with applicable codes Support all piping do not allow the weight of any piping to stre...

Page 5: ...ated by incoming warm air as it passes back through the air to air heat exchanger Using the outgo ing air to pre cool the inlet air condenses up to 65 percent of the moisture out of the inlet air befo...

Page 6: ...omponent of the compressed air system under pressure may cause equipment failure and serious personal injury Operation 1 To start the dryer turn on the a dryer on off switch 2 When the refrigeration c...

Page 7: ...HA approved air nozzle that limits its discharge pressure to 30 psig 2 1 kgf cm2 Yearly Maintenance It is recommended to replace the drain service unit annually For units purchased with a filtration p...

Page 8: ...let air temperature too high Reduce aftercooler discharge temperature to design conditions See Engineering Data Tables Excessive airflow Check airflow and system capacity Reduce airflow or resize and...

Page 9: ...Setting cut in cut out 217 5 275 6 psig 15 19 barg Electrical Data Nominal Voltage 460 3 60 Input Power Rated Flow watts 4 300 7 600 9 000 10 000 Minimum Circuit Ampacity 9 8 16 5 16 9 20 4 Maximum Ov...

Page 10: ...92 760 31 50 800 58 59 1488 3 94 100 54 02 1372 50 08 1272 3 ANSI Flange 1133 514 HOLE FOR MAIN POWER DRAIN OUTLET 4 10 MOUNTING HOLES FOOT PRINT H G C F A B E J VENT DRAIN VALVE D WETTED AIR INLET D...

Page 11: ...1350 4 ANSI Flange 1537 697 DFX 15 1 10 85 276 19 69 500 6 09 155 37 80 960 39 37 1000 58 59 1488 3 94 100 57 09 1450 53 15 1350 4 ANSI Flange 1766 801 HOLE FOR MAIN POWER DRAIN OUTLET 4 10 MOUNTING H...

Page 12: ...09 155 37 80 960 39 37 1000 58 59 1488 3 94 100 63 78 1620 59 84 1520 4 ANSI Flange 2028 920 HOLE FOR MAIN POWER DRAIN OUTLET 4 10 MOUNTING HOLES FOOT PRINT H G A B F E C J D VENT DRAIN VALVE TOPVIEW...

Page 13: ...SW 2 3 4 T R S MC1 COMP 0V 480V 0V 120V 460V 3PH 60HZ W1 U1 V1 E 2 1 MAIN POWER TH1 AC IN COMP ALARM DRAIN COM ON R1 S1 FG S2 R2 COM ON COM N C N 0 TS3 TS2 DRAIN TRAP 24 21 12 25 20 30 TS1 DRAIN TRAP...

Page 14: ...VE DRAIN OUTLET NO LOSS VALVE EXPANSION DEVICE TEMP SENSOR2 TS2 SEPARATOR FILTER TEMP SENSOR3 TS3 MANUAL REFRIGERANT COMPRESSOR CONDENSER COOLING AIR FLOW AIR COOLED FILTER CONDENSER AIR COOLED HIGH P...

Page 15: ...OOLED TEMP SENSOR2 TS2 TEMP SENSOR3 TS3 FILTER CONDENSER AIR COOLED HEAT EXCHANGER AIR AIR REF PCM AIR REHEATER CHILLER BRAZED PLATE HEAT EXCHANGER BRAZED PLATE DRAINVALVE DRAIN OUTLET NO LOSS VALVE S...

Page 16: ...06 Separator 7473007 7473008 7473008 7473009 White Temperature Sensor 7440388 7440388 7440388 7440388 Red Temperature Sensor 7440389 7440389 7440389 7440389 Yellow Temperature Sensor 7440390 7440390 7...

Page 17: ...15 NOTES MCGUIRE AIR COMPRESSORS INC 1 888 229 9999 MCGUIRE AIR COMPRESSORS INC 1 888 229 9999...

Page 18: ...MCGUIRE AIR COMPRESSORS INC 1 888 229 9999 MCGUIRE AIR COMPRESSORS INC 1 888 229 9999...

Page 19: ...manufacturer s product The maximum damages liability of the manufacturer is the original purchase price of the product or part THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES W...

Page 20: ...vements and research are continuous at SPX FLOW Inc Specifications may change without notice ISSUED 08 2019 Form No 7473076 Revision None COPYRIGHT 2019 SPX FLOW Inc FLEX Series Refrigerated Type Comp...

Reviews: