INSTRUCTION MANUAL FOR: 

 

LOBOY 16 

AIR CONDITIONERS 

 

McLean Midwest Corp. 
dba: McLean Cooling Technology 
11611 Business Park Blvd. N   Champlin, MN 55316 
Tel: 763-323-8200   Fax: 763-576-3200 

 

www.mcleancoolingtech.com

                           

 

 

Summary of Contents for LOBOY 16

Page 1: ...STRUCTION MANUAL FOR LOBOY 16 AIR CONDITIONERS McLean Midwest Corp dba McLean Cooling Technology 11611 Business Park Blvd N Champlin MN 55316 Tel 763 323 8200 Fax 763 576 3200 www mcleancoolingtech co...

Page 2: ...in it is placed in an upright vertical or mounting position for a minimum of five 5 minutes before operating Warning Do not attempt to operate the air conditioner while it is horizontal or on its side...

Page 3: ...air conditioner and the approximate height i e LB16 LOBOY family about 16 high 2 This is the air conditioner s listed capacity in Btu hr at rated conditions i e 10 10 000 Btuh at 125 125F 3 1 115 Volt...

Page 4: ...ith the mounting gasket attached as this could cause rips or tears in the gasket and risk losing the water tight seal Step 4 Allow unit to remain upright for a minimum of five 5 minutes before startin...

Page 5: ...tain is limited If moisture flows from the drain tube continuously this can only mean that ambient air is entering the enclosure Be aware that frequent opening of the enclosure s door admits humid air...

Page 6: ...5 26 1 17 3 9 3 85 29 4 179 2 153 1 10 23 3 21 1 12 4 90 32 2 193 6 166 5 5 20 6 25 2 15 8 95 35 208 8 180 8 0 17 8 29 6 19 5 100 37 8 224 9 195 8 5 15 34 4 23 6 105 40 6 241 8 211 8 10 12 2 39 6 28 1...

Page 7: ...p 125 F 52 C Minimum Ambient Temp 40 F 40 C Condensate Management Hose discharge Electrical Data Rated Voltage 50 60 Hz 230 V Rated Frequency 50 60 Hz Voltage Range 10 of rated Cooling Amps at Max Con...

Page 8: ...Page 7 10 1008 05 Rev 1 Wiring Point to Point Diagram Figure 3 Wiring Diagram...

Page 9: ...frigerant Loss Each air conditioner is thoroughly tested prior to leaving the factory to insure against refrigeration leaks Shipping damage or microscopic leaks not found with sensitive electronic ref...

Page 10: ...thermostat Open motor winding Stuck blower motor Obstructed wheels blades 6 Carefully check the compressor for operation motor should cause slight vibration and the outer case of the compressor shoul...

Page 11: ...r tries to start but won t run Low line voltage at start Should be 10 rated voltage Compressor motor stuck Bad contactor Bad overload switch Bad run start capacitor Unit blows breakers Under sized bre...

Page 12: ...rranty Parts supplied as warranty replacement parts will assume the balance of the warranty on the part returned for warranty consideration Please be advised According to the Federal Register no perso...