INSTRUCTION MANUAL FOR: 

 

T15 AIR CONDITIONER

 

 

McLean Thermal 
11611 Business Park Blvd. N   Champlin, MN 55316 
Tel: 763-323-8200   Fax: 763-576-3200 

 
www.mcleanthermal.com

 

Summary of Contents for T15-0116-GXXX Series

Page 1: ...INSTRUCTION MANUAL FOR T15 AIR CONDITIONER McLean Thermal 11611 Business Park Blvd N Champlin MN 55316 Tel 763 323 8200 Fax 763 576 3200 www mcleanthermal com...

Page 2: ...n and packing material and request an inspection Then file a claim with the delivering carrier McLean Thermal cannot accept responsibility for freight damages however we will assist you in any way pos...

Page 3: ...ill continue to operate and the compressor will restart after it has cooled to within the thermal overload cut in temperature setting INSTALLATION Step 1 Inspect air conditioner Verify functionality b...

Page 4: ...ltage Hz Amps Phase Temp o F o C Lbs Kgs T15 0116 GXXX 115 60 3 6 1 800 131 55 27 12 3 T15 0116 GXXX 100 50 3 8 1 800 125 52 27 12 3 T15 0126 GXXX 230 60 1 5 1 900 131 55 27 12 3 T15 0126 GXXX 220 50...

Page 5: ...0 Coil Condenser 15 1001 02 15 1001 02 Coil Condenser Coated 15 1001 01 15 1001 01 Coil Evaporator 15 1001 03 15 1001 03 Compressor 10 1016 82 10 1026 101 Filter Air Reusable 10 1000 91 10 1000 91 Fil...

Page 6: ...10 1008 194 Rev 2 Page 5 T15 Wire Diagram T15 Schematic...

Page 7: ...is hermetically sealed properly lubricated at the factory and should provide years of satisfactory operating service Should the refrigerant charge be lost recharging ports access fittings on the suct...

Page 8: ...sis The inlet air filter is located behind the front cover To access filter pull ring protruding from slot in bottom of front cover The filter may now be cleaned or new filter installed Cleaning Instr...

Page 9: ...O possible Defective thermostat Open motor winding Stuck fan motor Obstructed blades 6 Carefully check the compressor for operation motor should cause slight vibration and the outer case of the compre...

Page 10: ...t run Low line voltage at start Should be 10 rated voltage Compressor motor stuck Bad contactor Bad overload switch Bad run start capacitor Unit blows breakers Under sized breaker fuse or not time del...

Page 11: ...s will assume the balance of the warranty on the part returned for warranty consideration Please be advised According to the Federal Register no person maintaining servicing repairing or disposing of...