b. Use a Variable Speed Drive for the Secondary Water Pump.
LO
A
D
LOA
D
LO
A
D
∆
P
INV
primary loop
When the differential pressure becomes higher, the inverter will slows
down the water pump to maintain the head pressure. If no demand,
the water pump will stop running.
c. Modify the Control Wiring for Chiller and Fan Coil Unit.
The above two methods will incur high cost due to the extra piping, pressure transmitter and
other
necessary
fittings/equipment.
An easier method is to change the control wiring of the system. Conventionally, when the
fan coil unit thermostat cuts-off, the power supply to the control 2-way valve will be off.
It is possible to run a line from the thermostat to the chiller remote switch whereby
when the thermostat cuts-off, the chiller unit (and the pump) will also switch off.
See Section 11 on 'Electrical Wiring Control' for more details.
However, the disadvantage with this method is that the chiller cycle on-off more frequently
and the water supply temperature will fluctuate up and down.
d. In view of the difficulties mentioned above, it is recommended that 3-way
diverting valves to be used in the mini chiller hydronic system.
Since the 3-way valve gives a constant flow system, there will not be any problem when
there is no load demand since the water will bypass through the valve when it is in the
fully closed position (with respect to the load).
Section 3
Page 50
Summary of Contents for AC 40A
Page 1: ...AM MAC ...
Page 153: ...Appendix 1 ...
Page 154: ...Appendix 2 Appendix 2 ...
Page 157: ...GRAPH OF PRESSURE DROP VS FLOW FOR VARIOUS C V RATINGS Appendix 5 1 ...
Page 158: ......
Page 159: ...Water Capacity Graph Appendix 5 2 ...
Page 160: ...CHART 3 FRICTION LOSS FOR CLOSED PIPING SYSTEMS Appendix 6 1 ...
Page 161: ...CHART 4 FRICTION LOSS FOR OPEN PIPING SYSTEMS Appendix 6 2 ...
Page 162: ...CHART 5 FRICTION LOSS FOR CLOSED AND OPEN PIPING SYSTEMS Appendix 6 3 ...
Page 168: ...Appendix 8 Appendix 8 ...
Page 169: ...Appendix 8 1 ...
Page 170: ...Appendix 8 2 ...
Page 171: ...Appendix 8 3 ...
Page 172: ...Appendix 8 4 ...
Page 173: ...Appendix 8 5 Appendix 8 5 ...
Page 174: ...Appendix 8 6 Appendix 8 6 ...
Page 175: ...Appendix 8 7 Appendix 8 7 ...
Page 176: ...Appendix 9 ...
Page 178: ...Appendix 11 1 Appendix 11 1 ...
Page 179: ...Appendix 11 2 Appendix 11 2 ...
Page 180: ...Appendix 13 ...
Page 181: ...Appendix 13 1 ...
Page 182: ...Appendix 14 Appendix 14 ...
Page 183: ...Appendix 15 1 Appendix 15 1 ...
Page 186: ...Appendix 17 Appendix 17 ...
Page 187: ...Appendix 18 ...
Page 188: ...CE20DW CE25DW Note PRESSURE DROP CORRECTION FACTOR 1 2947 0 0021 EWTºF Appendix 19 ...
Page 189: ... 2003 McQuay International 603 55194922 www mcquayup com ISO 9002 REGISTERED ...