Table 5, Circuit Controller Setpoints
Description Default
Range
PW
Compressor
Circuit mode
Enable
Disable, Enable, Test
M
Slide control
Auto
Auto, Manual
M
Slide position
0
0-100%
M
Compressor Size
205
205,220,235
M
Clear Cycle Timers
N o
No, Yes
M
Maximum Slide Target
100.0
0-100.0%
M
EXV
EXV control
Auto
Auto, Manual
M
Manual EXV position
0
0-6386
M
Pre-open timer
60
20-120 sec
M
Service Pumpdown
No
No, Yes
M
Fans
Fan VFD enable
Yes
No, Yes
M
Number of fans
6
6,8
M
Saturated Condenser Temp Target
110.0
90.0 – 130.0
o
F M
Stage 1 Up Deadband
5.0
1.0-20.0
o
F M
Stage 2 Up Deadband
8.0
1.0-20.0
o
F M
Stage 3 Up Deadband
10.0
1.0-20.0
o
F M
Stage 4 Up Deadband
12.0
1.0-20.0
o
F M
Stage 1 Down Deadband
8.0
1.0-20.0
o
F M
Stage 2 Down Deadband
7.0
1.0-20.0
o
F M
Stage 3 Down Deadband
6.0
1.0-20.0
o
F M
Stage 4 Down Deadband
5.0
1.0-20.0
o
F M
VFD Max Speed
100%
90 to 110%
M
VFD Min Speed
25%
20 to 60%
M
Forced FanTrol
™
1
1 1-8
M
Forced FanTrol
™
2
2 1-8
M
Forced FanTrol
™
3
3 1-8
M
Sensors
Evap pressure offset
0
-10.0 to 10.0 psi
M
Cond pressure offset
0
-10.0 to 10.0 psi
M
Liquid pressure offset
0
-10.0 to 10.0 psi
M
Suction temp offset
0
-5.0 to 5.0 deg
M
Discharge temp offset
0
-5.0 to 5.0 deg
M
Liquid temp offset
0
-5.0 to 5.0 deg
M
Slide Minimum Position
0
-15 to 15%
M
Slide Maximum Position
0
-15 to 15%
M