Closed
Any time the EXV is not in pre-open, pressure control, or subcool control, it will be in a
closed state. At this time, the EXV position is 0 steps and the EXV close signal is active.
Manual EXV Control
The EXV position can be set manually. Manual control can only be selected when the
compressor is in the run state. At any other time, the EXV control setpoint is forced to auto.
When EXV control is set to manual, the EXV position is equal to the manual EXV position
setting. If set to manual when the compressor state transitions from run to another state, the
control setting is automatically set back to auto.
To verify EXV operation in an off state, see Unit Test Mode on page 28.
Evaporator Oil Return Line Control
The oil return solenoid shall be on any time the compressor is running and any of the
following occurs:
Slide position target < 60 AND Discharge superheat > 35
Slide position target >= 60 AND Discharge superheat > 50
Oil Level input = open AND Discharge superheat > 35
Oil Heater Control
The oil heater shall be on when the compressor is not running AND the oil level input is
closed.
Interstage Injection
The purpose is to control the discharge temperature at low LWT conditions when the
dischare temperature is high. The interstage injection is activated when the compressor is
running AND the discharge temperature rises above 185
°
F. The output shall be turned off
when either the compressor is no longer running, OR the discharge temperature drops below
170
°
F.