KOMAC00607-09EN
15
Extension I/O Compressor #1 to #3
Analog Inputs
#
Description
Signal Source
Expected Range
X1 Discharge
Temperature
NTC
Thermister (10K@25°C)
-50°C – 120°C
X2 Evaporator
Pressure
Ratiometric (0,5-4,5 Vdc)
0 to 5 Vdc
X3 Oil
Pressure
Ratiometric
(0,5-4,5 Vdc)
0 to 5 Vdc
X4 Condenser
Pressure
Ratiometric (0,5-4,5 Vdc)
0 to 5 Vdc
X7 Motor
Protection
PTC
Thermistor
n/a
Analog Outputs
# Description
Output
Signal
Range
Not Needed
Digital Inputs
#
Description
Signal Off
Signal On
X6
Starter Fault
Fault
No fault
DI1
High Pressure Switch
Fault
No fault
Digital Outputs
U.S. Configuration
#
Description
Output Off
Output On
DO1 Start
Compressor
Compressor Off
Compressor On
DO2
Economizer
Solenoid Closed
Solenoid Open
DO3
Non-modulating Slide Load
Solenoid Closed
Solenoid Open
DO4
Liquid Injection
Solenoid Closed
Solenoid Open
DO5
Modulating Slide Load
Solenoid Closed
Solenoid Open
DO6
Modulating Slide Unload
Solenoid Closed
Solenoid Open
X5 Spare
X8 Spare
I/O EXV Circuit #1 to #3
Analog Inputs
#
Description
Signal Source
Expected Range
X2 Suction
Temperature
NTC
Thermister 10K@25°C)
-50°C – 120°C
Analog Outputs
# Description
Output
Signal
Range
Not Needed
Digital Inputs
#
Description
Signal Off
Signal On
DI1
Low Pressure switch (optional)
Fault
No fault (optional)
Digital Outputs
#
Description
Output Off
Output On
DO1
Liquid Line (optional)
Solenoid Closed
Solenoid Open (optional)
Stepper Motor Output
# Description
M1+
M1-
EXV Stepper Coil 1
M2+
M2-
EXV Stepper Coil 2
Summary of Contents for AWS