Condenser Fan Control
The compressor must be running in order to stage fans on. All running fans will turn off
when compressor goes to the off state.
Saturated Condenser Temperature Target
The condenser fan control logic attempts to control the saturated condenser temperature
to a calculated target. A base condenser target is calculated based on evaporator
saturated temperature. The equation is:
Base saturated condenser target = 5/6 (saturated evaporator temperature) + 68.33
This value is then limited to a maximum and minimum determined by the Condenser
Target Maximum and Minimum set points. If these set points are both set to the same
value, then the saturated condenser temperature target will be locked at that value.
Fan Staging
The fan stage is adjusted in steps of 1 fan. The only exception is to accommodate forced
fan staging at compressor start.
Fan staging will accommodate anywhere from 5 to 12 fans according to the table below:
Output Number
1 2
3
4
5
6
# of fans
5
6
7
8
9
10
11
12
Staging Up
Six stage-up deadbands are used. Stages one through five use their respective dead
bands. Stages six through twelve all use the sixth stage up dead band.
When the saturated condenser temperature is above the the active deadband, a
Stage Up error is accumulated.
Stage Up Error Step = Saturated Cond. temperature – ( Stage-Up
deadband)
The Stage Up Error Step is added to Stage Up Accumulator once every 5 seconds, only
if the Saturated Condenser Refrigerant Temperature is not falling. When Stage Up Error
Accumulator is greater than 20 another stage is added.
When a stage up occurs or the saturated condenser temperature falls back within the
Stage Up dead band the Stage Up Accumulator is reset to zero.
Staging Down
Five stage down dead bands are used. Stages two through five use their respective dead
bands. Stages six through twelve all use the stage six dead band.
When the saturated condenser refrigerant temperature is below the Target – the active
deadband, a Stage Down error is accumulated.
Stage Down Error Step = (Target - Stage Down dead band) - Saturated Condenser
Refrigerant temperature
The Stage Down Error Step is added to Stage Down Accumulator once every Stage
Down Error Delay seconds. When the Stage Down Error Accumulator is greater than
the Stage Down Error Set Point another stage of condenser fans is removed.