Start-up and Shutdown
NOTICE
McQuay service personnel or factory authorized service agency
must perform initial start-up in order to activate warranty.
!
CAUTION
Most relays and terminals in the unit control center are powered when S1 is closed
and the control circuit disconnect is on. Therefore, do not close S1 until ready for
start-up or the unit may start unintentionally and possibly cause equipment damage.
Seasonal Start-up
1.
Double check that the discharge shutoff valve and the optional compressor suction
butterfly valves are open.
2.
Check that the manual liquid-line shutoff valves at the outlet of the subcooler coils
and the oil separator oil return line shutoff valves are open.
3.
Check the leaving chilled water temperature setpoint on the MicroTech III controller
to be sure it is set at the desired chilled water temperature.
4.
Start the auxiliary equipment for the installation by turning on the time clock, and/or
remote on/off switch, and chilled water pump.
5.
Check to see that pumpdown switches Q1 and Q2 (and Q3) are in the "Pumpdown
and Stop" (open) position. Throw the S1 switch to the "auto" position.
6.
Under the "Control Mode" menu of the keypad, place the unit into the automatic
cool mode.
7.
Start the system by moving pumpdown switch Q1 to the "auto" position.
8.
Repeat step 7 for Q2 (and Q3).
Temporary Shutdown
Move pumpdown switches Q1 and Q2 to the "Pumpdown and Stop" position. After the
compressors have pumped down, turn off the chilled water pump.
!
CAUTION
Do not turn the unit off using the "Override Stop" switch, without first moving Q1 and
Q2 (and Q3) to the "Stop" position, unless it is an emergency, as this will prevent the
unit from going through a proper shutdown/pumpdown sequence.
!
CAUTION
The unit has a one-time pumpdown operation. When Q1 and Q2 are in the
"Pumpdown and Stop" position the unit will pump down once and not run again
until the Q1 and Q2 switches are moved to the auto position. If Q1 and Q2 are in
the auto position and the load has been satisfied, the unit will go into one-time
pumpdown and will remain off until the MicroTech III control senses a call for
cooling and starts the unit.
!
CAUTION
Water flow to the unit must not be interrupted before the compressors pump down
to avoid freeze-up in the evaporator. Interruption will cause equipment damage.