background image

Page 24 / IM 685

3. When it is necessary to remove any air baffles surrounding the heat exchanger, carefully note the

locations and clearances of these baffles before removing them so they can be replaced in the exact
same position.

4. Remove the two bottom bolts at the back of the heat exchanger.
5. Withdraw the heat exchanger through the back of the casing.

Furnace Condensation

A furnace will produce condensation when the flue gas temperature falls below its dew point
temperature. A more efficient furnace will transfer more of its heat into the building, and leave less heat
in the flue gas. This results in a lower flue gas temperature and more condensate.

A modulating burner will produce more condensate than an on-off burner. As the firing rate of the
burner is reduced the flue gas temperature will be reduced, and if it is reduced below its dew point
condensate will be produced.

A furnace that is heating a high percentage of outside air will also produce more condensate. The colder
the air contacting the heat exchanger, the lower the resulting flue gas temperature, and consequently the
more condensate.

Do not think a furnace has a problem because it produces condensate anymore than you would think a
cooling coil has a problem because it produces condensate. However suitable steps should be taken to
manage the flow of the condensate produced.

Most condensate will be produced in the secondary tubes where flue gas will sweep it into the flue box.
Condensate will also come from the combustion chamber. Models 020 and 025 have a piped
combustion chamber condensate drain, and Models 032 through 200 have a rear cleanout port with an
integral condensate drain.

On a properly prepared unit, the condensate should drip from drain openings in the two outer corners
of the flue box, and from the drip shield below the rear cleanout port. Condensate should not be
running down the unit, except at times the wind may blow the dripping condensate mentioned above.
At installation the flue box should be sealed with high temperature silicone (see “Installation – Flue Box,
Item 3”). The drip shield below the rear cleanout port must be correctly installed. See following section:
“Rear Cleanout Port”.

Rear Cleanout Port

The rear cleanout port is equipped with a stainless steel drip shield to direct the flow of condensate
coming out the cleanout port (see Figure 15). The shield (1) must fit snugly against the bottom of the
cleanout port tube (2) at (A) so condensate (B) cannot run back along the underside of the tube and
into the unit or down the side of the rear panel. Instead, the condensate is to run down the drip shield
and drip off its bottom edge, away from the rear casing door.

Figure 15. Rear cleanout port (models 032 thru 200)

Summary of Contents for IM 685

Page 1: ...Gas Fired Furnace on McQuay Applied Rooftop Systems HT A with RM7895A Flame Safeguard Installation Maintenance Manual IM 685 Group Applied Systems Part Number 629948Y 00 Date March 1998 1998 McQuay I...

Page 2: ...nty failure state the date of installation of the unit and the date of failure along with an explanation of the malfunctions and the description of the replacement parts required Parts are warranted f...

Page 3: ...ssembly and requires no additional chimney flue pipe Breidert cap draft inducer etc Factory Mounting This burner and gas train has been installed and wired at the factory See Gas Piping Also note that...

Page 4: ...the outside of the tube See Figure 1 Also apply a bead of high temperature silicone to seal both sides to the bottom of the flue box wrapper being careful not to obstruct the square drain holes in eac...

Page 5: ...e burner is shown in Table 5 under Column 13 thru 15 Gas piping must be sized to provide the minimum required pressure at the burner when the burner is operating at maximum input Consult the appropria...

Page 6: ...20 92 190 350 730 1100 2100 3300 5900 12000 30 73 152 285 590 890 1650 2700 4700 9700 40 63 130 245 500 760 1450 2300 4100 8300 50 56 115 215 440 670 1270 2000 3600 7400 60 50 105 195 400 610 1150 18...

Page 7: ...s to avoid interference with swinging of doors etc Through the Curb Piping Models 020 thru 140 1 Remove bottom access panel See Figure 3c 2 Remove knockout and make an opening through bottom deck dire...

Page 8: ...re only a connection to the supply gas line The manual shutoff valve is located within the burner vestibule If local codes require a manual shutoff valve that is accessible from outside the unit that...

Page 9: ...tc 2 Review the equipment and service literature and become familiar with the location and purpose of the burner controls Determine where the gas and power can be turned off at the unit and upstream o...

Page 10: ...electric gas valve in the line Open the gas line cocks upstream from there and bleed the gas line of all air Replace the 1 8 inch pipe plug 7 Leak check Using a rich soap water mixture and a brush ch...

Page 11: ...until after a period of main flame operation has further purged the gas lines before trying to adjust out something that may actually be caused by air in the lines Modulate Firing Rates Set the tempe...

Page 12: ...he flame safeguard FSG Upon a call for heat the control system will close OBA3 thus energizing relay R20 When 120 volt power is furnished through the system on off switch S1 through the burner on off...

Page 13: ...flame rod FD at the completion of the 10 second trial for ignition period terminal 10 ignition transformer IT will be de energized and terminal 9 relay coil R23 and main gas valves GV4 etc will be ene...

Page 14: ...history It can be mounted to the RM7895A and will retrieve information on the six most recent faults Consult the Honeywell bulletin 65 0090 1 7800 Series Keyboard Display Module and 65 0118 1 7800 Ser...

Page 15: ...e RM7895A which are energized to indicate operation as follows POWER The RM7895A is powered PILOT The prepurge period is complete and the terminal for the start combination gas control is powered FLAM...

Page 16: ...rly careful to correctly reinsert the air tube into the grommeted hole The tube should slip into the grommet so there is little leakage but it should not bear down on it or it can cause binding on the...

Page 17: ...ure is not an option the following discussion on the High Pressure Regulator would still apply High Pressure Regulator If a high pressure regulator is included as part of the burner gas train or is in...

Page 18: ...et that connects the air and gas valves must be correctly positioned on the control rod such that the bracket will be firmly held under tension against its stop when the actuator is in the minimum rat...

Page 19: ...of 2000 feet and higher the gas burner must be derated 4 for every 1000 feet of altitude Example Model HT080 at an altitude of 3000 feet is derated 0 04 x 3 0 12 At 1000 mbh input 1000 x 0 12 120 mbh...

Page 20: ...e adjusted to the flow rate used for this procedure is too high and must be reduced by repositioning the actuator to a lower firing rate or the gas supply line pressure is too low After adjusting valv...

Page 21: ...will be diluted with outside air and lower readings will result If flue gas temperature is to be measured this must be done in the flue box not in the tube The temperature gradient within the tubes w...

Page 22: ...bulator in each tube approximately flush with the tube end locking them in place with the wedge clips on each turbulator 8 Reinstall flue box front wrap Figure 14 Models 020 thru 025 Heat Exchanger Le...

Page 23: ...Rate 2 Control Failure The limit control does not function properly to shut off the burner when the heat exchanger temperature becomes excessive In most situations a properly controlled unit will nev...

Page 24: ...condensate However suitable steps should be taken to manage the flow of the condensate produced Most condensate will be produced in the secondary tubes where flue gas will sweep it into the flue box C...

Page 25: ...eyboard display module or a DC voltmeter Twice Yearly 1 Burner Air Check burner fan wheel for dirt build up and lint Check combustion air intake louver and flue box for dirt buildup and accumulation o...

Page 26: ...als 7 and L2 on the flame safeguard stays there the Keyboard when the burner fan is running Display Module indicates Purge Hold 2 2 Burner motor runs valve a Timer TD10 is not making after 20 seconds...

Page 27: ...ressure will build up on the downstream side thus exceeding the rating of the gas train components b Undersized piping can also cause problems by delivering reduced pressure during times of maximum de...

Page 28: ...64148A 04 040 Burner Gun Assembly 1 964148A 05 050 Burner Gun Assembly 1 964148A 06 064 065 Burner Gun Assembly 1 964148A 08 079 080 Burner Gun Assembly 1 964148A 10 100 Burner Gun Assembly 1 964148A...

Page 29: ...N n i M M F C x a M R T F g e D g n i r u D e g r u p e r P e t a R x a M r e n r u B g n i t a r e p O e t a R x a M g n i r u D e g r u p e r P e t a R x a M x a M e t a R n i M e t a R 5 e t o N 5...

Page 30: ...T t n e i b m A F g e D e r u t a r e p m e T s a G e u l F t n e c r e p 2 O C M P P O C C W n I x o B n i e r u s s e r P r i A Flue Gas Flue Gas s t n e m m o C y n a e z i r a m m u S k r o w e c...

Page 31: ...IM 685 Page 31 Notes...

Page 32: ...13600 Industrial Park Boulevard P O Box 1551 Minneapolis MN 55440 USA 612 553 5330...

Reviews: