CHILLED WATER FAN COILS MF – McQuay FCF PM0
5D
_ENG
page 20/36
CONTROL FEATURES
ELECTRONIC THERMOSTAT REMOTE CONTROL AC5300 (OPTIONAL)
Location
Wall Mounted
Models
All models; all versions
Parameters
On/Off
Temperature
Fan Speed
Auto Fan Speed selection
Date / Time setting
Mode
Main Functions
Selectable Temperature operation range:
10-30°C or 16-30°C
Automatic re-start with memory settings
Heating/Cooling change-over based on system control input
Auto-diagnosis
Timer with 2 daily setting (14 weekly)
Warm and cold draft protection
Antifreeze protection
Air sensor control
Valves 2 or 3 ways with ON/OFF control
Remote control – max. distance: 2.5 metres
Integration into FCU Network
Connection through AC2800 control
Direct connection [integrated NIM]
Integration with Smart Manager
Connection through AC2800 control
Direct connection [integrated NIM]
1
On/Off key
2
Heating/Cooling mode key
3
Clock/Timer setting
4
Fan Speed selection key (HIGH/MEDIUM/LOW)
5
Temperature up key
6
Temperature down key
7
Back-light LCD Display
a
On/Off key
b
Fan Speed selection key (HIGH/MEDIUM/LOW)
c
Temperature up key
d
Temperature down key
e
Heating/Cooling mode key
f
Clock/Timer setting
AUTO-DIAGNOSIS
E1
:
Ambient temperature sensor incorrect operation
E2
:
Water temperature sensor incorrect operation
E3
:
Potentiometer incorrect operation or on board control/wall mounted thermostat conflicting mode selection
E4
:
Fan Coil / Chiller conflicting mode selection