34
PFS 155C - 315C
OM 135
Menu 11, Schedule
Press the "NEXT MENU" key and Menu 10 will be displayed. This menu is pass word protected and requires the
operator password.
Item
Screen
Line
Display
Field
Range
1
Override=0.00Hr
1
00.00-63.75
Mon
2
00:00-23:59
1
2
NMP Schedule =x
1
1-32
Tue 00:00-23:59
2
00:00-23:59
3
Sun
1
00:00-23:59
Wed
2
00:00-23:59
1
Thu
1
00:00-23:59
2
Hol
2
00:00-23:59
2
Fri
1
00:00-23:59
3
Sat
1
00:00-23:59
Override=
This allows the operator (manual input) to input a time value that the MicroTech will ignore the normal or
holiday start/stop schedule. This timed override will start when the value is entered.
NMP Schedule=
Network schedules can be provided through a network master panel when the Mode is set to
auto:network. If a master/slave arrangement is active, the master panel will control the schedule. The slave unit should
be programmed the same as the master to have consistent operation should the network communications fail.
Sun through Fri
- The start time (first value) and stop time for each day of the week should be entered. The default
value (00:00-23:59) allows the chiller to operate continuously.
Hol -
The time entered at this menu will control the chiller run time for the holiday dates entered in Menu 11 (holiday
date).
Menu 12, Holiday Date
Press the "NEXT MENU" key and Menu 12 will be displayed. This menu is password protected and requires the
operator password. The month, day and number of days in the holiday is selected
Item
Screen
Line
Display
Field
Range
1
1
#1=N/A-00 00 Day(s)
1
Jan-Dec
2
00-31
3
00-31
#4=N/A-00 00 Day(s)
1
Jan-Dec
2
00-31
3
00-31
2
#2=N/A-00 00 Day(s)
1
Jan-Dec
2
00-31
3
00-31
#5=N/A-00 00 Day(s)
1
Jan-Dec
2
00-31
3
00-31
3
#3=N/A-00 00 Day(s)
1
Jan-Dec
2
00-31
3
00-31
#6=N/A-00 00 Day(s)
1
Jan-Dec
2
00-31
3
00-31
Menu continued on next page.