background image

OPERATION

During full load operation, check the compressor oil

level. It should be near the center of the oil sight
glass during operation.

A.

B.

C.

D.

E.

Check the refrigerant charge  frequently at the
moisture/liquid indicator. A steady clear glass of
liquid refrigerant indicates sufficient charge. A
green colored button in the center of the moisture

indicator indicates a dry system (should moisture

enter the system, the color will turn yellow). The

button was green  before it left the factory and

should be green  after a period of operation on
start-up. A filter-drier core change is recommended
for a persistent yellow indicator. (Page 26).

Check the temperature control thecmostat  by ob-
serving operation at reduced loads. The thermostat

is factory set for 44F leaving chilled water tem-

perature when the entering temperature is 54F.
Refer to CHECKING CONTROLS section, Pages
20 and 21.

Checkvoltage and amperage of the compressor mo-
tor(s) and fan motors (see Field Wiring, Page  11).

When gauges ace furnished, close gauge ports by
back seating valves after readings ace checked.
This will prolong the gauge life and prevent refrig-
erant loss. Replace seal caps.

See SERVICE INFORMATION section, Pages 28

and 29 for Trouble Shooting Chart.

PERIODIC SERVICE

(At end of first week of operation and once a month

thereafter.)

A.

B.

C.

D.

A. Turn on water circulating pump.

Check

 compressor oil level. Oil should cover ap-

proximately l/2 of the oil level glass. Copeland
Compressors ace furnished with oil fill plug on
the side of crankcase, should it be necessary to
add oil. (See Page 25, Paragraph E).

B. Turn pumpdown  switches S3 and S4 to "auto” posi-

tion.

Check liquid sight glass ahead of expansion valve
for proper refrigerant charge.

C. Observe operation for several minutes, noting un-

usual sounds, or possible unusual cycling of
compressors.

EXTENDED SHUTDOWN

On belt driven  units, check belt tension and ob-
serve condition of belts.

A. Close the liquid line shut-off valve.

Check the surface of the condenser coil for ob- B. Wait for the compressor to pump down until it

struction. If 

necessary, flush with cold water, 

shuts off.

brush off, or use vacuum cleaner.

E. Make general inspection of entice system for any

unusual sound or condition.

NORMAL REFRIGERANT CHARGE

The condenser coil has a built-in subcooler. For opti-
mum operation. the liquid sight glass in the liquid line
between the receiver and subcooler  should be substan-
tially free of bubbles. A completely clear sight glass

indicates a possible overcharged system. No adverse
affect need be expected unless overcharge is suffici-
ent to affect an excessive head pressure caused by
appreciable liquid flooding of condenser portion of
coil. The minimum charge at which the unit will oper-
ate properly is with clear  sight glass between the
filterdrier and thermostatic expansion valve.

WEEK END OR SHORT PERIOD SHUTDOWN

A.

B.

Turn pumpdown   s w i t c h e s  5%  a n d   S 4   t o   “ m a n ”
position. The compressor or compressors will con-
tinue to run for a short period, until the system
pumps down, and stops on opening of low pccssuce
control.

Turn off water circulating pump (Water circulating

pump is often left on the line as an assist against

damage by freezing of water).

WARNING:

Do not open main electrical discon-

n e c t  switch as heater cable and crankcase heater
will be de-energized.

START UP FOLLOWING WEEK END SHUTDOWN

Page 

18

Summary of Contents for Seasonpak PAB Series

Page 1: ...15 AUGUST 1967 FORM 206034Y INSTALLATION AND MAINTENANCE DATA MODEL PAB AIR COOLED WATER CHILLER 7 1 2 THRU 60 TONS INC 13600 INDUSTRIAL PARK BLVD P O BOX 1551 MINNEAPOLIS MINNESOTA 55440 PHONE 377 97...

Page 2: ......

Page 3: ...Lability not strictly in accordan further warranty is h this policy except to the extent that such in writing and signed by an official of Mc Quay for additional consideration n in accordance with an...

Page 4: ...charge for the job requirements see Table 6 Pages 8 and 9 Charge for specific units can be obtained f rom the nameplatc The McQUAY line of air cooled water chillers is de signed for outdoor applicatio...

Page 5: ......

Page 6: ......

Page 7: ......

Page 8: ......

Page 9: ......

Page 10: ......

Page 11: ...s covering specific rcquircments CRANKCASE HEATERS The compressors are equipped with crankcase heaters Some models have heaters installed externally below the crankcase and others have heaters inserte...

Page 12: ......

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ......

Page 17: ...Check to see that the water temperature thermo stat is installed in the entering water line The L thermostat well is to be full of heat conducting compound and the bulb must be secured with the retain...

Page 18: ...graph E B Turn pumpdown switches S3 and S4 to auto posi tion Check liquid sight glass ahead of expansion valve for proper refrigerant charge C Observe operation for several minutes noting un usual sou...

Page 19: ...or at the unit an impedance relay is incorporated in the control circuit Basically this type of control is centered around a relay with a high impedance holding coil connected in series with the basic...

Page 20: ...low side of the system and its purpose is to shut down the D E compressor at the end of the pumpdown cycle It will open at 35 psig and automatically reset at approximately 60 psig The control can be c...

Page 21: ...een switches Do NOT make any adjustments other than the dial as this is a preset precision control TO CHANGE THE SET POINT 1 2 3 Loosen the setscrews on the collar below the hex nut see Fig 7 Turn the...

Page 22: ...checked as follows A Make up a depth gauge for inserting through the adjusting nut opening and long enough to hit the CONTROLS B C D E bottom of the bellows section as indicated in the diagrams A piec...

Page 23: ......

Page 24: ...t the nuisance of water dripping from the lines If insulation is not of the self contained vapor barrier type it should be covered with a moisture seal Do not insulate piping until it has been tested...

Page 25: ...on chamber on the motor end of the compressor Shut off valves E F G VIEW FROM END OF COOLER STRAIGHT PIPE EE D x D x 1 are never installed in these control lines The compressor is pre charged with suf...

Page 26: ...or of the moisture indicator button is an indication of the dryness of the system and is ex tremely important when the system has been ser v i c e d Immediately after the system h a s been opened for...

Page 27: ...nto heavy duty steel tube sheets and s c a l e d by a cast steel refrigerant head B The water connection nozzles which enter and leave the shell are on the same side of the unit No special attention i...

Page 28: ...e s s d D i s c h a r g e s h u t o f f v a l v e p a r t i a l l y d O p e n v a l v e c l o s e d L o w D i s c h a r g e P r e s s u r e a F a u l t y c o n d e n s e r t e m p e r a t u r e r e g...

Page 29: ...A d j u s t t h e r m a l e x p a n s i o n v a l v e C o m p r e s s o r l o s e s o i l a L o c k o f r e f r i g e r a n t b E x c e s s i v e c o m p r e s s i o n r i n g b l o w b y a C h e c k...

Page 30: ...ng parts refer to the model number and serial number of with an explanation of the malfunctions and a descrip the unit as stamped on the serial plate attached to the tion of the replacement parts requ...

Reviews: