background image

REFRIGERANT PIPING

REMOTE AIR COOLED CONDENSERS

For remote condenser application, such as an air
cooled condenser, the chillers, with and without
mounted receivers, are shipped containing a Refriger-
ant-22 holding charge. It is important that the unit be
kept tightly closed until the remote condenser is in-
stalled, piped to the unit and the high side evacuated.

Refrigerant piping,

to and from the remote unit,

should be sized and installed according to the latest

ASHRAE Guide. It is important that the piping be

properly supported with sound and vibration insulation
between tubing and hangerand that the discharge lines
be looped at the condenser and trapped at the com-
pressor to prevent refrigerant liquid from draining into
the compressor discharge manifold. Looping the dis-
charge line also provides greater line flexibility.

The discharge gas valve, liquid line solenoid,filter-

drier and moisture indicators are all provided as stan-
dard equipment with the SEASONPAK water chiller,
whether installed with remote or factory mounted re-
ceivers.

After the equipment is properly installed, the unit

may be charged with Refrigerant-22, then run at de-
sign load conditions, adding charge until the liquid

line sight-glass is clear, with no bubbles flowing to

expansion valve. Total operating charge will depend
on the air cooled condenser used and the length of
external piping, but generally will be equal to the
water cooled charge shown in Table 9, Page 26. With
S E A S O N T R O L   l o w   a m b i e n t   c o n t r o l   o n   a i r   c o o l e d
units, additional charge must then be added, as re-
quired (but not to exceed receiver pumpdown capacity)

UNIT LESS CONDENSER

SEASONPAK water chillers without condensers or
with mounted receivers require field piping to a re-
mote condenser of some type. As mentioned under the
R E M O T E   C O N D E N S E R   s e c t i o n   a b o v e ,   r e f r i g e r a n t

piping should be sized and installed according to the

latest ASHRAE Guide. The design of refrigerant pip-
ing when using air cooled condensers involves a num-

ber of considerations not commonly associated with
other types of condensing equipment. The following
discussion is intended for use as a general guide to
sound, economical and trouble-free piping of air cool-

ed condensers.

On remote condenser applications, discharge line

mufflers are recommended. The mufflers should be in-
stalled as close to the compressor discharge as pos-

sible, If oil separators are used, they will usually
perform the same function as a muffler and will elim-
inate the need for one. A muffler wi II reduce discharge

line pulsations; particularly those which occur during

unloaded compressor operation

Discharge lines must be designed to handle oil

properly and to protect the compressor from damage

that may result from condensing liquid refrigerant in
the line during shutdown. Total friction loss for dis-
charge lines of 

psi is considered good design. Care-

ful consideration must be given for sizing vertical
risers to insure that gas velocities are sufficient at
all operat,ing  conditions to carry oil. If the velocity

in a vertical discharge riser is too low, considerable

oil may collect in the riser and the horizontal header,

causing the compressor to lose its oil and resultant
damage due to lack of lubrication.

Another danger is when the compressor load is in-

creased, the oil that had collected during reduced

loads may be carried as a slug through the system

and back to the evaporator, where a sudden increase

of oil concentration may cause slopover  and damage

to the compressor.

Any horizontal run of discharge piping should be

pitched away from the compressor approximately 1/4"
per foot or more. This is necessary to move by gravity

any oil lying in the header. Oil pockets must be

avoided as oil needed in the compressor would  col-

lect at such points and the compressor crankcase may

become starved.

It is recommended that any discharge lines coming

into a horizontal discharge header rise above the

center line of the discharge header. This is necessary
to prevent any oil or condensed liquid from draining
to the top heads when the compressor is not running.

In designing liquid line, it is important that the

liquid reach the expansion valve with a minimum of

flash gas since this gas will reduce the capacity of

the valve. Because “flashing” can be caused by a

pressure drop in the liquid lines, the pressure losses

due to friction and changes in static head should be
kept to a minimum.

The liquid line from the condenser to the receiver

MUST be sized for sewer flow operation (100 fpm/ve-

locity  or less) and MUST be sloped to the receiver

with no traps in the line. Any shut off valve in this

line must have an orifice area equal to the inside area
of the line. Free drainage in this line is essential to
permit gas from the receiver to vent back to the con-

denser. Failure to adequately size and slope this line
wi II force liquid to back up into the condenser causing
high head pressure and bubbling sight glass.

A check valve should be installed in the liquid line

on installations that require operation at outside am-
bients below 60F. This prevents liquid migration to
the condenser and helps maintain a supply of refriger-
ant in the receiver for initial start up.

Typical Arrangements

Figure No. 11,

Page 9 illustrates a typical piping

arrangement involving a remote air cooled condenser

located at a higher elevation than the compressor and

receiver. This arrangement is commonly encountered
when the air cooled condenser is on a roof and the
compressor and receiver are on grade level or in a
basement equipment room.

In this case, the design of the discharge line is

very critical. If properly sized for full load condition,
the gas velocity might be too low at reduced loads to
carry oil up through the discharge line and condenser

coil. Reducing the discharge line size would increase
the gas velocity sufficiently at reduced load condi-
tions; however, when operating at full load, the line

might be greatly undersized and thereby create an ex-
cessive refrigerant pressure drop. This condition can
be overcome in one of the two following ways:

1. The discharge line may be properly sized for the

desired pressure drop at full load condition and an
oil separator installed at the bottom of the trap on
the discharge line from the compressor.

Page 8

Summary of Contents for Seasonpak PWA-008A

Page 1: ...BLE OF CONTENTS CONTROLS CHECKING 24 CROSSREFERENCE NEW TO OLD MO 2 ELECTRICAL 22 23 CONTROL CENTER SERVICE 26 27 ELECTRICALDATA 22 23 WIRING 10 13 WIRING DIAGRAMS 14 21 MAINTENANCE 26 29 MOVING PLACI...

Page 2: ...LL UNIT FROM ANYTHING OTHER THAN water cooled condensers Arrangement 1 is supplied THE BASE MOVING AND PLACING THE UNIT MOVING THE UNIT The McQUAY SEASONPAK water chiller is mounted on heavy wooden sk...

Page 3: ...EARANCE FOR COOLER TUBE RE MOVAL MEASURED FROM CENTER LINE OF CHILLED WATER CONNECTION ON EITHER END TABLE NO 1 MINIMUM CLEARANCE UNIT SIZE I MINIMUM CLEARANCE 007A THRU 015A 72 020A THRU 041A 96 050A...

Page 4: ......

Page 5: ......

Page 6: ...nded beyond the pro FIGURE NO 7 TO COOI ER 4 posed insulation thickness to make them accessible CHILLED WATER THERMOSTAT WHR 008A thru 060A The chilled water thermostat is mounted inside the control c...

Page 7: ...oop at the outlet end is recommended See Figure 9 WATER REGULATING VALVES EACH CONDENSER FIGURE NO 8 3 WAY WATER REGULATING VALVES COi lNG TOWER PURGE 4 MAIN CONDENSER WATER SUPPLY FROM PUMP BY PASS B...

Page 8: ...cal discharge riser is too low considerable oil may collect in the riser and the horizontal header causing the compressor to lose its oil and resultant damage due to lack of lubrication Another danger...

Page 9: ...E NO 11 PURGE VALVE DISCHARGE LINE HECK VALVE LIQUID LINE FIGURE NO 13 DISCHARGE LINE I TO EVAPORATOR RECEIVER LrQuro LINE EVAPORATORS or and receiver The discharge line piping in this case is not too...

Page 10: ...TAT 12 INDICATOR LIGHTS 6 HIGH MANUAL RESET AND LOW PRESSURE CUTOUTS 7 CONTROL SYSTEM ON OFF SWITCH FIGURE NO 16 MODELS WHR 070A THRU 120A 1 FREEZESTAT MANUAL RESET 7 CONTROL SYSTEM ON OFF SWITCH 2 OI...

Page 11: ...020A THRU 060A FIGURE NO 17 TOP VIEW OF UNIT Models WHR OO8A thru 015A are single compressor units 3 4 5 6 7 8 9 10 25 The power from 25 is fed thru NC contacts to relay R3 and R4 to energizethe compr...

Page 12: ...e operating before power can be applied to start this system Note that the crankcase heaters will be energized regard less of water flow The flow switch is recommended and does not have the shortcomin...

Page 13: ...itch LP1 opens Contactors Ml M3 and relay R3 will open and compressor 1A will turn off and stay off until relay R1 is again energized thru the thermostat In the event compressor 1A is off on oil press...

Page 14: ......

Page 15: ......

Page 16: ......

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ......

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ...aches the prescribed differential within 120 seconds the thermal time delay is de energized and the control circuit remains closed If during the operation the oil pressure differential falls below 10...

Page 25: ...d unloading sequence of the unit based on a full load cooling range of 10F It should be realized however that there will be a fluctuation in the leaving water temperature as the unit cycles unloads an...

Page 26: ...eaning of the finned surface of the conden ser coil Cleaning may be accomplished by using a cold water spray brushing vacuuming or high pres sure air No tools should be used that could damage the coil...

Page 27: ......

Page 28: ...s t e m c P u r g e t h e n o n c o n d e n s i b l e s d S y s t e m o v e r c h a r g e d w i t h r e f r i g e r a n t d R e m o v e e x c e s s e D i s c h a r g e s h u t o f f v a l v e p a r t...

Page 29: ...n d t i g h t e n s y s t e m k R e p l a c e g a s k e t I Adjust t h e r m a l e x p a n s i o n v a l v e C o m p r e s s o r l o s e s o i l _ _ _ a L a c k o f r e f r i g e r a n t a C h e c k f...

Page 30: ...ber and serial number of the date of installation of the unit and date of failure along with an explanation of the malfunctions and a the unit as stamped on the serial plate attached to the unit If re...

Reviews: