FIGURE NO. 1
MOVING UNIT WITH FORK LIFT
NOTE:
ALWAYS LIFT ON SIDE OPPOSITE THE
CONTROL PANEL TO AVOID DAMAGING
THE CONTROLS.
L O C A T I O N
Unit is designed for indoor application and must be
located in an area where the surrounding ambient tem-
peratures are 40F or above. A good rule of thumb is
to place units where ambients are at least 5 degrees
above the leaving water temperature.
Because of the electric control devices, the units
should not be exposed to the weather. A plastic cover
over the control box is supplied as temporary protec-
tion during transfer.
A reasonably level and sufficiently strong floor is
all that is required for the SEASONPAK water chiller.
If necessary, additional structural members should be
provided to transfer the weight of the unit to the near-
est beams. Refer to Page 4 for foundation information.
SPACE REQUIREMENTS FOR CONNECTIONS
AND SERVICING
The c h i I led water piping for all units enters and
leaves the cooler from the rear. A clearance of 3 to 4
feet should be provided for this piping and for replac-
ing the fi Iter-driers, for servicing the solenoid valves,
or for changing the compressors, should it ever be-
come necessary.
The condenser water piping enters and leaves the
shell from the ends. Work space must be provided in
case water regulating valves are being used and for
general servicing.
Clearance should be provided for removing cooler
tubes on one end of the unit as specified in Table 1.
Condenser tubes cannot be replaced. It is also desir-
able to leave a small walk area on the end opposite
that used for replacement of a cooler tube.
M I N I M U M C L E A R A N C E F O R C O O L E R T U B E R E -
M O V A L M E A S U R E D F R O M C E N T E R L I N E O F
C H I L L E D W A T E R C O N N E C T I O N O N E I T H E R E N D
TABLE NO. 1 MINIMUM CLEARANCE
U N I T S I Z E
I
M I N I M U M C L E A R A N C E
007A THRU 015A 72”
020A THRU 041A 96”
050A THRU 070A 108”
080A
120”
FIGURE NO. 2
SUGGESTED RIGGING
OTE: ALWAYS USE SPREADER
BARS TO PROTECT UNIT
FROM DAMAGE.
P L A C I N G T H E U N I T
The small amount of vibration normally encountered
with the SEASONPAK water chiller makes this unit
particularly desirable for basement or ground floor in-
stallations where the unit can be bolted directly to
the floor. The floor construction should be such that
the unit wi II not affect the bui lding structure, or trans-
mit noise and vibration into the structure. See VI-
BRATION ISOLATORS section for additional mount-
ing information. Hold down bolt locations are indicated
in Figures 3 and 4, Page 4.
V I B R A T I O N I S O L A T O R S
Rubber-in-shear or spring isolators can be furnished
and field placed under each corner of the package. It
is recommended that a rubber-in-shear pad be used as
the minimum isolation on all upper level installations
or areas in which vibration transmission is a consid-
eration.
Transfer the unit as indicated under MOVING THE
UNIT, or use the methods as indicated in Figures 1
and 2. In all cases, set the unit in place and level
with a spirit level. When spring type isolators are re-
quired, install springs running under the main side
channels. Foundation hold down bolt locations for vi-
bration isolators are given in Figures 3 & 4. A rubber-
anti -skid pad should be standard under isolators if
hold down bolts are not used.
Vibration eliminators in all water piping connected
to the SEASONPAK water chiller are recommended to
avoid straining the piping and transmitting vibration
and noise.
I
090A THRU 1OOA
1 OX” I
110A T H R U 120A
I
132"
I