background image

14 

IM 685-1

Air and Gas Adjustments

The burner has been adjusted and tested at the factory with
accurate instruments. There should not be a need to readjust
the burner after the unit has been installed.

Verify that the gas supply pressure is correct, the electrical
power is correct, and test the burner thoroughly. Do no make
adjustments unless there is a clear indication that there is a
problem, and proper instruments are available so the adjust-
ments can be made correctly.

Gas Supply Pressure

The maximum pressure rating of the combination gas con-
trol(s) used on this burner is 0.50 psi (13.9 in. w.c.), as mea-
sured at (2), Figure 16a. If the gas supply pressure is higher
than this an additional regulator must be installed so the
pressure will not exceed 0.50 psi. 

Many gas burner problems are due to gas supply pressure
problems. High or low gas pressures can cause nuisance
lockouts of the flame safeguard and combustion problems.
Low gas pressure will reduce the heat output of the furnace,
and if extreme, can cause combustion problems and flame
safeguard lockouts. Every gas supply system has a high pres-
sure regulator somewhere upstream. Perhaps it is at the
meter and adjusting the outlet pressure is not an option, the
following discussion on the "High Pressure Regulator"
would still apply.

High Pressure Regulator

If a high pressure regulator is included as part of the burner
gas train or is included elsewhere in the gas supply line, it
should be adjusted so the pressure at the inlet tap to the com-
bination gas valves is 7.0 in. w.c. The inlet tap is (2) on Fig-
ure 16a. Check that the pressure is relatively consistent as
the firing rate changes. If any other equipment is served by
that same gas line or pressure regulator, check that the gas
pressure also remains relatively consistent when that equip-
ment is turned on and off. Verify that the regulator closes off
tightly at zero flow by observing that the pressure does not
creep up when the unit is off. If it does, excessive pressure
will have built up over the off period, possibly exceeding the
pressure rating of the combination gas controls, and causing
other problems at light off.

Gas Adjustments

See the sections on "Gas Valve Pressure Regulator Adjust-
ment", "Gas Supply Pressure", and "High Pressure Regula-
tor". The gas flow rate is determined by the gas pressure and
a characterized element within the modulating gas valve.
The stem of the valve connects to the bracket that positions it
with lock nuts that are adjusted at the factory and determine
the minimum firing rate of the burner. Other than gas pres-
sure adjustments, this is the only adjustable control of the
gas. Adjusting the minimum rate is not intended to be a rou-
tine field adjustment. Properly adjusting the minimum rate
requires clocking a gas meter at very low flow rates, or con-
necting a test flow meter into the gas train.

Air Adjustments

Airflow and the resultant combustion characteristics have
been preset and tested at the factory and no further adjust-
ments should be required. Airflow to the burner is deter-
mined by the characterized plate on the air valve outlet (1)
and an adjustable plate (2) on Figure l0a. The adjustable
plate can increase or decrease airflow across the entire stroke
of the valve. If burner airflow is in question, measure the
static pressure at Ports (4) and (5), Figure 16, and compare
those readings with Columns 6 and 8 in Table 5. A signifi-
cant difference should be checked out.

Air and Gas Control Linkage

An L-shaped control rod is connected to the actuator and
passes through the burner housing and into the control box.
This control rod positions the valves that control the burner
air and gas, and actuates switches in the control box to prove
when it is at the maximum and minimum position. When the
actuator positions the control rod to the minimum rate posi-
tion, the bracket on that rod that connects to the air valve and
gas valve should be firmly bottomed against the end of the
gas valve which acts as its stop. The linkages to the air and
gas valve should be straight and in alignment. Although the
bracket is to bottom out, the plate connected to it which
slides from right to left to control airflow should slide freely
and not be forced against either the right or left side member
of the air box.

At the minimum rate position maintain a gap according to
dimension "D", Figure 10a. With that sliding plate in this
minimum rate position, check dimension "E", Figure 10a. To
gauge opening "E", use a drill blank held perpendicular to
the plate. For Models 050-200 opening "E" can be accessed
through the grommeted opening in the primary air collector.
See (3), Figure 10a. for Models 020-040 the primary air col-
lector must be removed. Generally, it is easier to remove the
collector with the inch diameter tube still attached by discon-
necting the tube at the other end.

At the maximum rate position the sliding blade should be
full open, but it should not be forced against the left side
piece of the air box.

The control rod bracket that connects the air and gas valves
must be correctly positioned on the control rod such that the
bracket will be firmly held under tension against its stop
when the actuator is in the minimum rate position, and so the
sliding blade will open fully without making contact at the
end of the stroke. When modulating towards the minimum
rate position the actuator will continue to travel after the
bracket contacts the stop, flexing the vertical end of the con-
trol rod so the bracket is held under tension. To correctly
locate the bracket on the rod, first adjust the air damper link-
age so there will be a gap per dimension "D", Figure 10a,
when the bracket is bottomed out against the end of the
valve. Second, loosen both set screws on the bracket assem-
bly so the bracket is free to slide on the rod. Third, position
the actuator to the maximum rate position. Position the slid-
ing blade to the wide open position. 

Summary of Contents for SuperMod IM-685-1

Page 1: ...n and Maintenance Manual IM 685 1 Group Applied Systems Part Number IM685 Date June 2001 SuperModTM Forced Draft Gas Fired Furnace on McQuay Applied Rooftop Systems HT A with RM7895A Flame Safeguard 2001 McQuay International ...

Page 2: ...Air Gas Adjustments 14 Gas Supply Pressure 14 High Pressure Regulator 14 Gas Adjustment 14 Air Adjustment 14 Air and gas Control Linkage 14 Actuator Crankarm 15 Switch Adjustments 15 Altitude Considerations 15 Gas Valve Pressure Regulator Adjustment 16 Adjustment Procedure for Parallel Valves 16 Check Manifold Pressure at Minimum rate 16 Combustion Testing 17 Verify Input Rate 17 Check CO2 CO and ...

Page 3: ...ill void all warranty coverage by the manufacturer Questions regarding specific con taminants should be referred to your local gas utility If the burner was specified for operation at higher altitudes combustion air adjustments were compensated to result in proper settings at the higher altitude This checkout nor mally eliminates on the job start up problems however the equipment is subject to var...

Page 4: ... be run from the meter to the gas burner without reductions Undersized piping will result in inadequate pressure at the burner The pressure will be at its lowest when it is needed the most at times of maximum demand Therefore it can cause intermit tent hard to find problems because the problem may have left before the service technician has arrived Avoid the use of bushings wherever possible WARNI...

Page 5: ... by IRI for over 1000 MBH input units must always be routed to the outdoors This is field piping Table 1 Capacity of pipe natural gas CFH WITH PRESSURE DROP OF 3 W C SPECIFIC GRAVITY OF 0 60 PIPE LENGTH FT PIPE SIZE INCHES IPS 1 1 1 2 2 3 4 10 132 278 520 1050 1600 2050 4800 8500 17500 20 92 190 350 730 1100 2100 3300 5900 12000 30 73 152 285 590 890 1650 2700 4700 9700 40 63 130 245 500 760 1450 ...

Page 6: ...ors etc Through The Curb Piping Models 020 140 1 Remove bottom access panel 5 See Figure 3c 2 Remove knockout 4 and make an opening 6 through bottom deck directly below knockout hole 3 Route gas pipeline through these openings and seal them off with suitable grommets 7 See Figure 3a Section A A 4 Replace bottom access panel 5 Typical Piping Connections Figure 4 A Shutoff Cock ball valve B Union Fu...

Page 7: ... be routed up to the burner from within the curb on Models 150 through 200 Gas piping must be routed across the roof to under the burner vesti bule or a pitch pocket can be provided there The installer must cut a hole in the bottom panel of the overhanging burner vestibule through which to route the gas line up to the burner gas train The bottom panel of the vestibule is at approximately the same ...

Page 8: ...he burner is controlled for proven low fire start The actua tor will position the modulating gas valve and the modulat ing air valve to the low fire position each time the burner is to light off Switch LS1 proves the air and gas valves are at the low fire position If LSl is not made at light off the gas valves cannot open and the flame safeguard will lock out requiring manual reset Pilot is Main F...

Page 9: ...ble deviation from these values would indicate a burner air problem that should be found before attempting to fire the burner These problems could include linkages dis turbed during shipment etc Flame Start up 1 Open the gas line cocks and position switch S3 to AUTO The flame safeguard will go through the 10 second Ini tiate period after which the burner motor will start The modulating air and gas...

Page 10: ...the unit through several start ups with the temperature controls calling for first minimum rates and finally maxi mum rates Be alert for any hints of trouble or unexplained inconsistencies that could indicate future problems Record Data After the gas burner has been successfully started up checked out and is operating correctly readings should be taken and recorded for future reference see Table 6...

Page 11: ...l go out on safety lockout After completion of the 60 second prepurge period there will be a 10 second trial for ignition during which terminal 8 combination gas valve GV1 and terminal 10 ignition transformer IT will be energized If flame is being detected through the flame rod FD at the completion of the 10 second trial for ignition period terminal 10 ignition transformer IT will be de energized ...

Page 12: ...r heat by the temperature control system Normal Start up Prepurge Upon a call for heat the prepurge period will begin If the air switch does not detect fan operation in the first 10 seconds into the prepurge period a recycle to the beginning of the prepurge will occur Ignition Trial The start combination gas control and the ignition transformer are powered for 10 seconds following the prepurge Fla...

Page 13: ...he grommet Flame Rod Adjustment The gun assembly is removed for flame rod inspection or service When correctly adjusted the flame rod insulator will be concentric with the hole it passes through not be shorted out against the disc the 0 75 inch long end tip will point toward the 0 086 inch diameter alignment hole and the end tip will clear the disc according to dimension C Figure 9 Figure 9 Flame ...

Page 14: ...as train Air Adjustments Airflow and the resultant combustion characteristics have been preset and tested at the factory and no further adjust ments should be required Airflow to the burner is deter mined by the characterized plate on the air valve outlet 1 and an adjustable plate 2 on Figure l0a The adjustable plate can increase or decrease airflow across the entire stroke of the valve If burner ...

Page 15: ...m out against the switch body When properly adjusted the lever can move an additional 0 02 inches as proven by slipping a feeler gauge between the switch lever and the collar when in the made position The collar on the control rod should be adjusted so the switch lever it is actuating will rest squarely on the outer surface of the collar but only 0 03 inches from the edge If the collar is located ...

Page 16: ...of the burner As the firing rate is increased the manifold pressure will be rela tively constant until the gas flow rate exceeds the capacity of that single valve and the manifold pressure starts to drop off The pressure adjustments should be made at the maximum gas flow rate just before the manifold pressure starts to drop off and the following should be considered a The manifold pressure does no...

Page 17: ...from inside one of the sec ondary tubes If the sample is taken from the flue box rather than the tube the sample will be diluted with outside air and lower readings will result If flue gas temperature is to be measured this must be done in the flue box not in the tube The temperature gradient within the tubes would cause high readings near the center of the tube and low readings near the edge Temp...

Page 18: ...O2 readings one with the supply fan running and one with the supply fan off If the CO2 increases with the supply fan off it could indicate leak age Note that CO2 samples must be taken from inside a tube not just from inside the flue box Checking for Leaks 1 Open up the rear casing panel while the unit is shut off and visually inspect the heat exchanger 2 Visually inspect the heat exchanger while t...

Page 19: ... the casing Furnace Condensation A furnace will produce condensation when the flue gas tem perature falls below its dew point temperature A more effi cient furnace will transfer more of its heat into the building and leave less heat in the flue gas This results in a lower flue gas temperature and more condensate A modulating burner will produce more condensate than an on off burner As the firing r...

Page 20: ...l screw hole is located 2 75 inches below the bottom of the inspection cover with the exception that several models are drilled at 3 15 inches below the inspection cover to avoid the no drill zone Install the Cover Channel Over Drain Pipe 1 Locate the copper channel 5 over the drain line The top of the channel should be approximately 75 inches below the bottom of the inspection cover and extend ap...

Page 21: ...stion chamber cleaning as required Keep burner vestibule clean Dirt and debris can result in burner air blockages Yearly 1 Gas Train Check all valves piping and connections for leakage Remove burner gun assembly Inspect and if required clean the flame rod ignition electrode main burner disc and blast tube Check tightness of linkage fas teners and bolts that could work loose from vibration and move...

Page 22: ... after 10 seconds and pressing the safety reset button has no effect replace the RM7895A BURNER MOTOR RUNS BUT 2 1 Burner motor runs valve actuator travels to the maxi mum rate position and stays there the Keyboard Display Module indicates Purge Hold a Switch LS2 is not being actuated by the collar on the control rod when at the maximum rate position b The air proving switch AS is not sensing burn...

Page 23: ...t for which the gas train is designed can also cause problems Line pres sure should not exceed 13 9 W C psi into the combination gas controls Pressures higher than this require an additional stepdown regulator to maintain the pressure below 13 9 W C even at no flow conditions The preferred pressure to the combination gas controls is 7 0 in W C A regulator that does not shut off tight at no flow wi...

Page 24: ...ly 1 0964148 04 040 Burner Gun Assembly 1 0964148 05 050 Burner Gun Assembly 1 0964148 06 064 065 Burner Gun Assembly 1 0964148 08 079 080 Burner Gun Assembly 1 0964148 10 100 Burner Gun Assembly 1 0964148 1 1 110 Burner Gun Assembly 1 0964148 12 140 Burner Gun Assembly 1 0964148 13 150 Burner Gun Assembly 1 0964148 14 200 Burner Gun Assembly 1 0373788 02 020 040 Blast Tube Assembly 4 00 x 20 1 03...

Page 25: ...1 25 1 25 HT 100 1250 62 5 15 000 61 1 63 2 09 4 60 3 20 3 72 6 5 7 5 1 25 1 25 1 25 HT 110 1375 68 8 10 100 100 2 50 2 60 4 45 2 90 3 50 5 0 7 8 1 50 1 25 1 25 HT 140 1750 87 5 21 000 61 2 25 2 45 4 45 2 80 3 30 5 0 7 8 1 50 1 25 1 25 HT 150 1875 93 8 13 700 100 2 32 2 50 4 50 3 10 3 60 5 0 8 4 1 50 1 25 1 25 HT 200 2500 125 0 30 000 61 2 60 3 65 4 90 3 70 4 10 6 0 11 2 2 00 1 50 1 25 Notes 1 Pre...

Page 26: ...s Manifold Pressure In W C 12 Gas Line Pressure In W C 13 Flame Signal DC Volts 14 Ambient Temperature Deg F 15 Flue Gas Temperature Deg F 16 Flue Gas CO 2 percent 17 Flue Gas CO PPM 18 Air Pressure in Box In W C 19 Min Rate Scale 5 Gas Manifold Pressure In W C 20 Gas Line Pressure In W C 21 Flame Signal DC Volts 22 Ambient Temperature Deg F 23 Flue Gas Temperature Deg F 24 Flue Gas CO 2 percent 2...

Page 27: ...IM 685 1 27 Notes ...

Page 28: ...28 IM 685 1 13600 Industrial Park Boulevard P O Box 1551 Minneapolis MN 55440 USA 612 553 5330 ...

Reviews: