Technical
Manual
Temperature
Controller
SCN
‐
RT1
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de
27
4.5.5
Heating/Cooling
request
objects
The
following
settings
are
available
at
the
ETS
‐
Software:
Illustration
14:
Heating/Cooling
request
objects
The
following
chart
shows
the
dynamic
range
for
this
parameter:
ETS
‐
text
Dynamic
range
[default
value]
comment
Heating
request
object
enabled
No
Yes
activates
the
communication
object
for
the
visualization
of
a
beginning
heating
process
Cooling
request
object
enabled
No
Yes
activates
the
communication
object
for
the
visualization
of
a
beginning
cooling
process
Chart
29:
Heating/Cooling
request
objects
The
setting
“Heating/Cooling
request
enabled”
can
show
objects,
which
indicates
a
beginning
heating
or
cooling
process.
So
these
objects
are
status
objects.
The
objects
can
be
used
for
the
visualization
of
a
beginning
or
ending
heating/cooling
process.
So,
for
example,
a
red
LED
could
show
a
heating
process
and
a
blue
LED
a
cooling
process.
A
further
opportunity
for
the
usage
is
the
central
switch
of
a
heating
or
cooling
process.
So
can
be
realized
that
all
heating
devices
of
a
building
switch
on,
when
a
controller
gives
out
a
heating
request.
The
1
Bit
communication
object
gives
as
long
a
1
‐
signal
out
as
the
process
is
active.
The
following
chart
shows
the
relevant
communication
objects:
Number
Name
Length
Usage
15
Heating
request
1
Bit
indicates
a
beginning
heating
process
16
Cooling
request
1
Bit
indicates
a
beginning
cooling
process
Chart
30:
Communication
objects
heating/cooling
request