Technical Manual
Blind Push Button Smart 55
BE-JTA5504.01
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Phone: +49-2263-
880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de
47
47
The interaction between automatic calculation of public holidays and manual activation via the bus
(via object) is described in the following table:
Public holiday
calculated?
Value of object 29
Action of object 29 Result: Public holiday active/not active?
No
Value 0
Sending a 0
No action
No
Value 0
Sending a 1
Public holiday active until set return,
automatic mode becomes active again
from the next day onwards
No
Value 1
Sending a 0
Manual deactivation, automatic mode
becomes active again the next day
No
Value 1
Sending a 1
Public holiday active until set return,
automatic mode becomes active again
from the next day onwards
Yes
Value 0
Sending a 0
Manual deactivation, automatic mode
becomes active again the next day
Yes
Value 0
Sending a 1
Public holiday active until set return,
automatic mode becomes active again
from the next day onwards
Yes
Value 1
Sending a 0
Manual deactivation, automatic mode
becomes active again the next day
Yes
Value 1
Sending a 1
Public holiday active until set return,
automatic mode becomes active again
from the next day onwards
Table 32: Automatic calculation of public holidays and manual activation
The following table shows the available communications objects:
Number
Name/Object Function
Length
Usage
25
Time switch – Blinds Up/Down 1 Bit
Sending the Up/Down command to the
shutter actuator
26
Time switch –
Absolute position of blinds
1 Byte
Sending the absolute height position to the
shutter actuator
27
Time switch –
Absolute position of slats
1 Byte
Sending the absolute slat position to the
shutter actuator.
Only with selection "height and slats".
30
Time switch –
Activation of public holiday
(for external logic)
1 Bit
Activation of the public holiday function via
bus, e.g. via Visu/Push button
31
Time switch –
Status public holiday
1 Bit
Indicates whether the unit is in public holiday
mode. Sends out its status when it changes
and always at 00:00h.
32
Time switch –
VisuControlEasy interface
14 Byte
Interface to the MDT VisuControl Easy (in
preparation, not yet implemented in the MDT
VisuControl Easy).
Table 33: Communication object – Time switch: Settings