4.4 Button functions
The following settings are available:
Figure 12: Settings – Button functions
The
function of the buttons 1/2
is permanently set as a button pair to "Blinds/Shutter" and cannot
be assigned otherwise.
When "
Function button 3
" and "
Function button 4
" are activated, a corresponding submenu appears
for each of the buttons, which can be configured individually there. Buttons 3 and 4 can only be set
as single buttons.
With the setting "
Settings menu via simultaneous pressing of buttons 3/4
" => "active", the
"Settings" menu can be called up in the unit by pressing buttons 3 and 4 simultaneously.
The corresponding time can be set via "
Time for long key press (basic setting)
". This time applies to
all buttons.
4.4.1 Identical parameter
4.4.1.1 Identical parameter – Lock objects
A lock object can be activated for the button pair 1/2 as well as for the individual buttons 3 and 4. If
the lock object is active, a communication object is displayed in each case. If the lock object is
assigned a logical "1", the corresponding button is "locked" and can therefore no longer be switched.
The lock is cancelled with a "0".
The following table shows the associated communication objects:
Number
Name/Object Function
Length Usage
7
Blinds/Shutter (Buttons 1/2) –
Lock buttons
1 Bit
Lock/unlock button pair 1/2
19
Button 3 – Lock
1 Bit
Lock/unlock Button 3
24
Button 4 – Lock
1 Bit
Lock/unlock Button 4
Table 16: Communication objects – Lock objects