A total of 8 logic blocks are available, each of which can be assigned 4 input objects.
The parameter "
Request logic objects after reset
" applies to all 8 logic blocks and defines whether a
read request for the input logics is sent out when the unit is restarted.
The "
Object type logic output
" determines which value is sent as the output of the logic.
The
sending conditions
behave as follows:
not automatic:
no sending, no request
input telegram:
Send on each input change
change of output:
Send only when output is changed
change of output only value 0/1
: Send only when the output is changed with additional filter
function of the value to be sent
The settings for the
input logics
are as follows:
not active:
Object for this input logic is deactivated
active normal:
Object is evaluated normally
active inverted:
Object is first inverted (1
0, 0
1) and then evaluated
The following table shows the available objects, here for logic A:
Number
Name/Object Function
Length Usage
41
Logic A – Input logic 1
1 Bit
Input object 1 of logic
42
Logic A – Input logic 2
1 Bit
Input object 2 of logic
43
Logic A – Input logic 3
1 Bit
Input object 3 of logic
44
Logic A – Input logic 4
1 Bit
Input object 4 of logic
45
Logic A – Output Switch /
Scene / Value / Percent value
1 Bit/
1 Byte
Output object of the logic. DPT according to
the setting
+5
next Logic
Table 37: Communication objects – Logic