background image

                           

Installation Manual

 

 

3

1

2

4

 

4

Use wire that can withstand temperatures of at least 80°C such as UL1007. 

5

Recommended wire strapping length is 7mm/0.275inch. 

6

Recommended torque setting for terminals is 5 kgf-cm (4.4 Lb-in). 

7

Recommended screwdriver is 3mm, slotted type. 

8

Suggested fuse  and maximum number of the DR class

 PSUs that  can be  connected to a circuit breaker at 

230V are shown as below. 

Model 

Fuse 

Circuit breaker 

C16 

D16 

DR-15 

T2A/L250V 

19 

22 

DR-30 

F2A/L250V 

15 

DR-60

 

F3.15A/L250V 

DR-100

 

F3.15A/L250V 

9

Mounting Instruction

 

Mount as shown in figure only, with input terminals down, or else sufficient cooling will not be possible. 
Admissible DIN rail

TS35/7.5 or TS35/15 

For rail fastening

 

 

a

Tilt the unit slightly rearwards. 

b

Fit the unit over top hat rail. 

c

Slide it downward until it hits the stop. 

d

Press against the bottom for locking. 

e

Shake the unit slightly to check the locking action. 

 
 
 
 
 
 
 
 
 
 

10

For other information about the products, please refer to www.meanwell.com for details. 

 

 

Warning / Caution !! 

1

Risk of electrical shock and energy hazard. All failure should be examined by a qualified technician. Please do 

not remove the case of the power supply by yourself! 

2

Risk of electric arcs and electric shock (danger to life). Connecting both the primary and the secondary sides 

together is not allowed. 

3

Risk of burn hazard. Do not touch the unit in operation and shortly after disconnection! 

4

Risk of fire and short circuit. The openings should be protected from foreign objects or dripping liquids. 

5

Only install the unit in a pollution degree 2 environment (Note.1).

 

6

Please do not install the unit in places with high moisture or near the water. 

7

  The maximum operating temperatures is 50°C for DR-15 and DR-30 series and 40°C for DR-60 and DR-100 series, 

please do not install the unit in places with high ambient temperature or near fire source. 

8

Output current and output wattage must not exceed the rated values on its specification. 

"Click" 

2

DR15-100_1680-21407-0590-E-0418

Summary of Contents for DR-15-12

Page 1: ...nted on a TS35 Standard DIN rail Installation 1 Always allow good ventilation clearances 5mm left and right 40mm above and 20mm below around the unit in use to prevent it from overheating Also a 10 15 cm clearance must be kept when the adjacent device is a heat source 2 The appropriate mounting orientation for the unit is vertical the input terminals at the bottom and output on the top for DR 15 t...

Page 2: ...he locking action 10 For other information about the products please refer to www meanwell com for details Warning Caution 1 Risk of electrical shock and energy hazard All failure should be examined by a qualified technician Please do not remove the case of the power supply by yourself 2 Risk of electric arcs and electric shock danger to life Connecting both the primary and the secondary sides tog...

Page 3: ...gainst risk of fire replace only with same type and rating of fuse Pour ne pas compromettre la protection contre les risqué d incendie remplacer par un fusible de même type et de memes caractéristiques nominales Note 1 Pollution Degree 2 applies where there is only non conductive pollution that might temporarily become conductive due to occasional condensation Generally refer to dry well ventilate...

Page 4: ...B adopting table look up to verify the Environment Friendly Use Period Names and Contents of Hazardous Substances Lists Part Name Hazardous Substances Lead Pb Mercury Hg Cadmium Cd Hexavalent chromium Cr6 Polybrominated biphenyls PBB Polybrominated diphenyl ethers PBDE PCB and its components X O X O O O Metal structure parts X O O O O O Plastic structure parts O O O O O O Accessories O O O O O O C...

Page 5: ...e for you Addresses and Contacts Headquarter Switzerland Angst Pfister Sensors and Power AG Thurgauerstrasse 66 CH 8050 Zurich Phone 41 44 877 35 00 sensorsandpower angst pfister com Office Germany Angst Pfister Sensors and Power Deutschland GmbH Edisonstraße 16 D 85716 Unterschleißheim Phone 49 89 374 288 87 00 sensorsandpower de angst pfister com ...

Reviews: