The following chart shows the objects that belong to general setting:
15
16
Device temperature
measured
Device temperature alarm
2bytes
1 bit
The device sends the measured output voltage
value in
regular intervals.
°C
When the measured value is above the threshold
a telegram with value 0 or 1 is sent. When the
measurement values return to the normal range
(less than the hysteresis) a telegram with value
0 or 1 is sent.
Number
Name
Length
Usage
Maximum tacking is available for the measurement sources Output Current and Maximum Device Temperature and is used to
"
"
"
"
find the maximum observed value over a certain period of time. At the end of each period, a measured value can be sent over the
bus.
3.3 Maximum Tracking
ETS
‐
text
Dynamic range
[default value]
Comment
Maximum Tracking Period
10 - 36,000S
[1800s]
Determine the time period for tracking
Maximum Current Tacking
Maximum Current Send
Maximum Temperature
Maximum Temperature
Send
Maximum Current Objet Type
Enable
Enable
Send at the end of period
Send at the end of period
2byte[DPT9,float]
Disable
Disable
Do not send
Do not send
4byte[DTP14]
2byte[DTP7,integer]
Enable or disable maximum current tracking
A telegram containing the maximum measured output
current value is sent after an expired tracking period,
when Send at the end of period is selected
Enable or disable Maximum temperature tracking
A telegram containing the maximum measured
temperature value of the device is sent after an
expired tracking period, when Send at the end of
period is selected
Select data point type